Page 2
MULTI/SINGLE CAC Indoor unit General information Product data Wall Mounted Unit Wall Mounted Unit (2) ART COOL Mirror Ceiling Mounted cassette 4-way Ceiling concealed duct - Middle static pressure Ceiling concealed duct - Low static pressure Ceiling Suspended Unit...
Page 3
Indoor unit General information MULTI/SINGLE 1.Model Line Up 2.External Appearance 3.Nomenclature...
Page 4
MULTI/SINGLE Indoor unit General information 1. Model Line Up MULTI / SINGLE Model Capacity Index [kW (kBtu/h)] Chassis Category 10.0 12.0 14.0 15.0 Name (12) (15) (18) (24) (36) (42) (48) (60) Deluxe Wall Mounted Unit Standard plus (R410A/R32 Common) Standard Deluxe Wall Mounted Unit (2)
Page 5
MULTI/SINGLE Indoor unit General information 2. External Appearance • Wall Mounted Unit (R410A/R32 common) • Wall Mounted Unit (2) (R32 only) AMNW07GSJL0 [DM07RP NSJ] S3NM09JL1ZA [DC09RQ NSJ] ASNW09GJ1Z0 [DM09RP NSJ] S3NM12JL1ZA [DC12RQ NSJ] ASNW12GJ1Z0 [DM12RP NSJ] S3NM18KL1ZA [DC18RQ NSK] ASNW18GK1Z0 [DM18RP NSK]...
Page 6
MULTI/SINGLE Indoor unit General information 3. Nomenclature 3.1 Global Name Basic (Except for the exception case below) Model Name Signification Z*N : Indoor units using R32 * Indicates Product type M : Only for Multi systems T : Ceiling Mounted Cassette B : Ceiling Concealed Duct V : Ceiling Suspended Unit A*N, U*N : Indoor units using R410A and R32 Commonly...
Page 7
MULTI/SINGLE Indoor unit General information 3. Nomenclature Wall Mounted Unit (2) Model Name Signification Product Type S : Split Refrigerant 3 : R32 4 : R410A Supply Type N : Indoor Unit U : Outdoor Unit Model Type M : Common Indoor unit for Multi and Residential system Nominal Capacity Ex) 7,000 Btu/h Class '07', 18,000 Btu/h Class...
Page 8
MULTI/SINGLE Indoor unit General information 3. Nomenclature 3.2 European Name Basic (Except for the exception case below) Model Name Signification Connectable Outdoor unit type M : Indoor units only for Multi systems U : Indoor units only for Single CAC systems C : Common Indoor Unit for Multi and Single CAC Product type T : Ceiling Mounted Cassette...
Page 9
MULTI/SINGLE Indoor unit General information 3. Nomenclature Wall Mounted Unit / ARTCOOL Mirror Model Name Signification Product type D : Deluxe P : Standard or Standard plus A : ARTCOOL Mirror Connectable Outdoor unit type M : Common Indoor unit for Multi and Residential system Nominal Capacity Ex) 7,000 Btu/h Class '07', 18,000 Btu/h Class...
Page 10
MULTI/SINGLE Indoor unit General information 3. Nomenclature Wall Mounted Unit (2) Model Name Signification Product type D : Deluxe P : Standard plus S : Standard A : ARTCOOL Mirror Connectable Outdoor unit type C : Multi Compatible Nominal Capacity Ex) 7,000 Btu/h Class '07', 18,000 Btu/h Class '18'...
Page 11
Indoor unit Product data MULTI/SINGLE Wall Mounted Unit Wall Mounted Unit (2) ARTCOOL Mirror Ceiling Mounted cassette 4-way Ceiling concealed duct - Middle static pressure Ceiling concealed duct - Low static pressure Ceiling Suspended Unit...
Page 12
Indoor unit Wall Mounted Unit MULTI/SINGLE 1.List of Functions 2.Specifications 3.Dimensions 4.Piping diagrams 5.Wiring diagrams 6.Air flow and temperature distribution 7.Sound levels 8.Installation...
Page 13
MULTI/SINGLE Indoor unit Wall Mounted Unit 1. List of functions Deluxe Basic functions of Indoor Unit AMNW07GSJL0 [DM07RP NSJ], ASNW09GJ1Z0 [DM09RP NSJ] Category Functions ASNW12GJ1Z0 [DM12RP NSJ], ASNW18GK1Z0 [DM18RP NSK] ASNW24GK1Z0 [DM24RP NSK] Air supply outlet Airflow direction control (left & right) O (5 Steps) Airflow direction control (up &...
Page 14
MULTI/SINGLE Indoor unit Wall Mounted Unit 1. List of functions Network solution Accessory List AMNW07GSJL0 [DM07RP NSJ] ASNW09GJ1Z0 [DM09RP NSJ] Category Product Remark ASNW12GJ1Z0 [DM12RP NSJ] ASNW18GK1Z0 [DM18RP NSK] ASNW24GK1Z0 [DM24RP NSK] Wireless Remote Controller PQWRHQ0FDB Heat Pump PQRCVCL0Q(W)
Page 15
MULTI/SINGLE Indoor unit Wall Mounted Unit 1. List of functions Standard plus Basic functions of Indoor Unit AMNW05GSJB0 [PM05SP NSJ], AMNW07GSJB0 [PM07SP NSJ] USNW09GJ2F0 [PM09SP NSJ], USNW12GJ2F0 [PM12SP NSJ] Category Functions AMNW15GSJB0 [PM15SP NSJ], USNW18GK2F0 [PM18SP NSK] USNW24GK2F0 [PM24SP NSK] Air supply outlet Airflow direction control (left &...
Page 16
MULTI/SINGLE Indoor unit Wall Mounted Unit 1. List of functions Network solution Accessory List AMNW05GSJB0 [PM05SP NSJ] AMNW07GSJB0 [PM07SP NSJ] USNW09GJ2F0 [PM09SP NSJ] USNW12GJ2F0 [PM12SP NSJ] Category Product Remark AMNW15GSJB0 [PM15SP NSJ] USNW18GK2F0 [PM18SP NSK] USNW24GK2F0 [PM24SP NSK] Wireless Remote Controller PQWRHQ0FDB Heat Pump PQRCVCL0Q(W)
Page 17
MULTI/SINGLE Indoor unit Wall Mounted Unit 1. List of functions Standard Basic functions of Indoor Unit AMNW07GSJA0 [PM07EP NSJ], USNW09GJ3A0 [PM09EP NSJ] Category Functions USNW12GJ3A0 [PM12EP NSJ], USNW18GK3A0 [PM18EP NSK] AMNW24GSKA0 [PM24EP NSK] Air supply outlet Airflow direction control (left & right) O (Manual) Airflow direction control (up &...
Page 18
MULTI/SINGLE Indoor unit Wall Mounted Unit 1. List of functions Network solution Accessory List AMNW07GSJA0 [PM07EP NSJ] USNW09GJ3A0 [PM09EP NSJ] Category Product Remark USNW12GJ3A0 [PM12EP NSJ] USNW18GK3A0 [PM18EP NSK] AMNW24GSKA0[PM24EP NSK] Wireless Remote Controller PQWRHQ0FDB Heat Pump PQRCVCL0Q(W) Simple Simple PQRCHCA0Q(W) for Hotel...
Page 19
MULTI/SINGLE Indoor unit Wall Mounted Unit 2. Specifications Deluxe AMNW07GSJL0 ASNW09GJ1Z0 Model Name [DM07RP NSJ] [DM09RP NSJ] 220-240, 1, 50 220-240, 1, 50 Power Supply V, Ø, Hz 220, 1, 60 220, 1, 60 Cooling Capacity Heating Power Input Min./Nom./Max.
Page 20
MULTI/SINGLE Indoor unit Wall Mounted Unit 2. Specifications ASNW12GJ1Z0 ASNW18GK1Z0 Model Name [DM12RP NSJ] [DM18RP NSK] 220-240, 1, 50 220-240, 1, 50 Power Supply V, Ø, Hz 220, 1, 60 220, 1, 60 Cooling Capacity Heating Power Input Min./Nom./Max. 9 / 19 / 30 26 / 39 / 60 Running Current Min./Nom./Max.
Page 21
MULTI/SINGLE Indoor unit Wall Mounted Unit 2. Specifications ASNW24GK1Z0 Model Name [DM24RP NSK] 220-240, 1, 50 Power Supply V, Ø, Hz 220, 1, 60 Cooling Capacity Heating Power Input Min./Nom./Max. 27 / 45 / 60 Running Current Min./Nom./Max. 0.24 / 0.33 / 0.40 Casing Color Munsell 7.5BG 10/2 (RAL 9016) W x H x D...
Page 22
MULTI/SINGLE Indoor unit Wall Mounted Unit 2. Specifications Standard plus AMNW05GSJB0 AMNW07GSJB0 Model Name [PM05SP NSJ] [PM07SP NSJ] 220-240, 1, 50 220-240, 1, 50 Power Supply V, Ø, Hz 220, 1, 60 220, 1, 60 Cooling Capacity Heating Power Input Min./Nom./Max.
Page 23
MULTI/SINGLE Indoor unit Wall Mounted Unit 2. Specifications USNW09GJ2F0 USNW12GJ2F0 Model Name [PM09SP NSJ] [PM12SP NSJ] 220-240, 1, 50 220-240, 1, 50 Power Supply V, Ø, Hz 220, 1, 60 220, 1, 60 Cooling Capacity Heating Power Input Min./Nom./Max. 11 / 18 / 30 11 / 19 / 30 Running Current Min./Nom./Max.
Page 24
MULTI/SINGLE Indoor unit Wall Mounted Unit 2. Specifications AMNW15GSJB0 USNW18GK2F0 Model Name [PM15SP NSJ] [PM18SP NSK] 220-240, 1, 50 220-240, 1, 50 Power Supply V, Ø, Hz 220, 1, 60 220, 1, 60 Cooling Capacity Heating Power Input Min./Nom./Max. 12 / 21 / 30 26 / 39 / 60 Running Current Min./Nom./Max.
Page 25
MULTI/SINGLE Indoor unit Wall Mounted Unit 2. Specifications USNW24GK2F0 Model Name [PM24SP NSK] 220-240, 1, 50 Power Supply V, Ø, Hz 220, 1, 60 Cooling Capacity Heating Power Input Min./Nom./Max. 27 / 45 / 60 Running Current Min./Nom./Max. 0.24 / 0.33 / 0.40 Casing Color Munsell 7.5BG 10/2 (RAL 9016) W x H x D...
Page 26
MULTI/SINGLE Indoor unit Wall Mounted Unit 2. Specifications Standard AMNW07GSJA0 USNW09GJ3A0 Model Name [PM07EP NSJ] [PM09EP NSJ] 220-240, 1, 50 220-240, 1, 50 Power Supply V, Ø, Hz 220, 1, 60 220, 1, 60 Cooling Capacity Heating Power Input Min./Nom./Max. W x No.
Page 27
MULTI/SINGLE Indoor unit Wall Mounted Unit 2. Specifications USNW12GJ3A0 USNW18GK3A0 Model Name [PM12EP NSJ] [PM18EP NSK] 220-240, 1, 50 220-240, 1, 50 Power Supply V, Ø, Hz 220, 1, 60 220, 1, 60 Cooling Capacity Heating Power Input Min./Nom./Max. W x No. 11 / 19 / 30 26 / 39 / 60 Running Current...
Page 28
MULTI/SINGLE Indoor unit Wall Mounted Unit 2. Specifications AMNW24GSKA0 Model Name [PM24EP NSK] 220-240, 1, 50 Power Supply V, Ø, Hz 220, 1, 60 Cooling Capacity Heating Power Input Min./Nom./Max. W x No. 27 / 45 / 60 Running Current Min./Nom./Max.
Page 30
MULTI/SINGLE Indoor unit Wall Mounted Unit 3. Dimensions Standard Plus / Standard (SJ Chassis) AMNW05GSJB0 [PM05SP NSJ], AMNW07GSJB0 [PM07SP NSJ], USNW09GJ2F0 [PM09SP NSJ] USNW12GJ2F0 [PM12SP NSJ], AMNW15GSJB0 [PM15SP NSJ] AMNW07GSJA0 [PM07EP NSJ], USNW09GJ3A0 [PM09EP NSJ], USNW12GJ3A0 [PM12EP NSJ]...
Page 31
MULTI/SINGLE Indoor unit Wall Mounted Unit 3. Dimensions Deluxe / Standard Plus / Standard (SK Chassis) ASNW18GK1Z0 [DM18RP NSK], ASNW24GK1Z0 [DM24RP NSK] USNW18GK2F0 [PM18SP NSK], USNW24GK2F0 [PM24SP NSK] USNW18GK3A0 [PM18EP NSK], AMNW24GSKA0 [PM24EP NSK]...
Page 32
Th3* Thermistor for evaporator middle temperature CN-TH3 Thermistor for evaporator outlet temperature CN-TH2 • * : AMNW07GSJL0 [DM07RP NSJ] Model not available. Refrigerant pipe connection port diameters [Unit : mm (inch)] Model Liquid AMNW07GSJL0 [DM07RP NSJ] ASNW09GJ1Z0 [DM09RP NSJ]...
Page 33
MULTI/SINGLE Indoor unit Wall Mounted Unit 5. Wiring Diagrams Deluxe Model : AMNW07GSJL0 [DM07RP NSJ]...
Page 35
MULTI/SINGLE Indoor unit Wall Mounted Unit 5. Wiring Diagrams Standard plus Models : AMNW05GSJB0 [PM05SP NSJ], AMNW07GSJB0 [PM07SP NSJ] USNW09GJ2F0 [PM09SP NSJ], USNW12GJ2F0 [PM12SP NSJ] AMNW15GSJB0 [PM15SP NSJ], USNW18GK2F0 [PM18SP NSK] USNW24GK2F0 [PM24SP NSK]...
Page 36
MULTI/SINGLE Indoor unit Wall Mounted Unit 5. Wiring Diagrams Standard Models : AMNW07GSJA0 [PM07EP NSJ], USNW09GJ3A0 [PM09EP NSJ] USNW12GJ3A0 [PM12EP NSJ], USNW18GK3A0 [PM18EP NSK] AMNW24GSKA0 [PM24EP NSK]...
Page 37
MULTI/SINGLE Indoor unit Wall Mounted Unit 6. Air flow and temperature distributions (reference data) Models : AMNW07GSJL0 [DM07RP NSJ], ASNW09GJ1Z0 [DM09RP NSJ] ASNW12GJ1Z0 [DM12RP NSJ] Cooling Side View Discharge angle: 35° Air velocity [m/s] Temperature [°C] • Vertical Louver : Center •...
Page 38
MULTI/SINGLE Indoor unit Wall Mounted Unit 6. Air flow and temperature distributions (reference data) Heating Side View Discharge angle: 55° Air velocity [m/s] Temperature [°C] 2.7 m 2.7 m • Vertical Louver : Center • Fan speed : Power Top View Discharge angle: 55°...
Page 39
MULTI/SINGLE Indoor unit Wall Mounted Unit 6. Air flow and temperature distributions (reference data) Models : AMNW05GSJB0 [PM05SP NSJ], AMNW07GSJA0 [PM07EP NSJ] AMNW07GSJB0 [PM07SP NSJ], USNW09GJ3A0 [PM09EP NSJ] USNW09GJ2F0 [PM09SP NSJ], USNW12GJ3A0 [PM12EP NSJ] USNW12GJ2F0 [PM12SP NSJ], AMNW15GSJB0 [PM15SP NSJ] ...
Page 40
MULTI/SINGLE Indoor unit Wall Mounted Unit 6. Air flow and temperature distributions (reference data) Heating Side View Discharge angle: 55° Air velocity [m/s] Temperature [°C] 2.7 m 2.7 m • Vertical Louver : Center • Fan speed : Power Top View Discharge angle: 55°...
Page 41
MULTI/SINGLE Indoor unit Wall Mounted Unit 6. Air flow and temperature distributions (reference data) Models : ASNW18GK1Z0 [DM18RP NSK], USNW18GK3A0 [PM18EP NSK] USNW18GK2F0 [PM18SP NSK] Cooling Side View Discharge angle: 25° Air velocity [m/s] Temperature [°C] 2.7 m 2.7 m •...
Page 42
MULTI/SINGLE Indoor unit Wall Mounted Unit 6. Air flow and temperature distributions (reference data) Heating Side View Discharge angle: 45° Air velocity [m/s] Temperature [°C] 2.7 m 2.7 m • Vertical Louver : Center • Fan speed : Power Top View Discharge angle: 45°...
Page 43
MULTI/SINGLE Indoor unit Wall Mounted Unit 6. Air flow and temperature distributions (reference data) Models : ASNW24GK1Z0 [DM24RP NSK], AMNW24GSKA0 [PM24EP NSK] USNW24GK2F0 [PM24SP NSK] Cooling Side View Discharge angle: 25° Air velocity [m/s] Temperature [°C] 2.7 m 2.7 m •...
Page 44
MULTI/SINGLE Indoor unit Wall Mounted Unit 6. Air flow and temperature distributions (reference data) Heating Side View Discharge angle: 45° Air velocity [m/s] Temperature [°C] 2.7 m 2.7 m • Vertical Louver : Center • Fan speed : Power Top View Discharge angle: 45°...
Page 45
6.Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment in installed. 50Hz, 220-240V Model Sound pressure Levels [dB(A)] AMNW07GSJL0 [DM07RP NSJ] ASNW09GJ1Z0 [DM09RP NSJ] ASNW12GJ1Z0 [DM12RP NSJ] ASNW18GK1Z0 [DM18RP NSK] ASNW24GK1Z0 [DM24RP NSK] 50Hz, 220-240V...
Page 46
MULTI/SINGLE Indoor unit Wall Mounted Unit 7. Sound levels [Unit : mm (inch)] AMNW07GSJB0 [PM07SP NSJ] AMNW05GSJB0 [PM05SP NSJ] AMNW07GSJL0 [DM07RP NSJ] AMNW07GSJA0 [PM07EP NSJ] High High High High Middle Middle Middle Middle NC-65 NC-65 NC-65 NC-60 NC-60 NC-60 NC-55...
Page 47
MULTI/SINGLE Indoor unit Wall Mounted Unit 7. Sound levels USNW18GK2F0 [PM18SP NSK] USNW24GK2F0 [PM24SP NSK] USNW18GK3A0 [PM18EP NSK] ASNW24GK1Z0 [DM24RP NSK] AMNW24GSKA0 [PM24EP NSK] High High High Middle Middle Middle NC-65 NC-65 NC-65 NC-60 NC-60 NC-60 NC-55 NC-55 NC-55 NC-50 NC-50 NC-50 NC-45...
Page 49
MULTI/SINGLE Indoor unit Wall Mounted Unit 7. Sound levels AMNW07GSJB0 [PM07SP NSJ] AMNW05GSJB0 [PM05SP NSJ] AMNW07GSJL0 [DM07RP NSJ] AMNW07GSJA0 [PM07EP NSJ] High High High High High Middle Middle Middle Middle Middle NR-90 NR-90 NR-90 NR-85 NR-85 NR-85 NR-80 NR-80 NR-80...
Page 50
MULTI/SINGLE Indoor unit Wall Mounted Unit 7. Sound levels [Unit : mm (inch)] USNW18GK2F0 [PM18SP NSK] USNW24GK2F0 [PM24SP NSK] USNW18GK3A0 [PM18EP NSK] ASNW24GK1Z0 [DM24RP NSK] AMNW24GSKA0 [PM24EP NSK] High High High High High Middle Middle Middle Middle Middle NR-90 NR-90 NR-90 NR-85 NR-85...
Page 51
MULTI/SINGLE Indoor unit Wall Mounted Unit 8. Installation • Please read the instruction sheets completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards. •...
Page 52
MULTI/SINGLE Indoor unit Wall Mounted Unit 8. Installation [Unit : mm (inch)] Fixing Installation Plate • The wall you select should be strong and solid enough to prevent vibration. 1. Mount the installation plate on the wall with type "A" screws which are provided with product. (Refer to the Installation manual.) If mounting the unit on a concrete wall, use anchor bolts.
Page 53
MULTI/SINGLE Indoor unit Wall Mounted Unit 8. Installation SV chassis Unit Outline Installation plate Left rear piping Right rear piping (Unit : mm) * According to product type, model line up, sales region..etc, applicability of each chassis could be different. CAUTION In case that the unit is installed near the sea, the installation parts may be corroded by salt.
Page 54
MULTI/SINGLE Indoor unit Wall Mounted Unit 8. Installation Back side view Pipe Port Left Tubing holder Right Backwards Chassis Cover * The feature can be changed according to type of model. * According to product type, model line up, sales region..etc, applicability of each chassis could be different. Connecting the installation pipe and drain hose Open-end wrench (fixed)
Page 55
MULTI/SINGLE Indoor unit Wall Mounted Unit 8. Installation * Foamed polyethylene or equivalent is recommended. CAUTION • Press on the tubing cover and unfold the tubing to downward slowly. And then bend to the left side slowly. • Following bending case from right to left directly may cause damage to the tubing. The feature can be changed according to type •...
Page 56
MULTI/SINGLE Indoor unit Wall Mounted Unit 8. Installation 8.2.3 Finishing the indoor unit installation 1.Mount the tubing holder in the original positon. 2.Ensure that the hooks are properly seated on the installation plate by moving it left and right. 3.Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots (clicking sound).
Page 57
MULTI/SINGLE Indoor unit Wall Mounted Unit 8. Installation Drill a Hole in the wall 1.Drill the piping hole with a ø 70mm hole core drill. Wall Drill the piping hole at either the right or the left with the holes slightly slanted to the outdoor side. Indoor Outdoor ...
Page 58
MULTI/SINGLE Indoor unit Wall Mounted Unit 8. Installation – Never fail to have separate power specially for the air conditioner. – Provide a circuit breaker switch between power source and the unit. – Confirm the Specification of power source. – Confirm that electrical capacity is sufficient. –...
Page 59
MULTI/SINGLE Indoor unit Wall Mounted Unit 8. Installation Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature. • Do not install the remote controller where it can be affected by : –...
Page 60
Indoor unit Wall Mounted Unit (2) MULTI/SINGLE 1.List of Functions 2.Specifications 3.Dimensions 4.Piping diagrams 5.Wiring diagrams 6.Air flow and temperature distribution 7.Sound levels 8.Installation...
Page 61
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 1. List of functions Deluxe Basic functions of Indoor Unit S3NM09JL1ZA [DC09RQ NSJ], S3NM12JL1ZA [DC12RQ NSJ] Category Functions S3NM18KL1ZA [DC18RQ NSK] Air supply outlet Airflow direction control (left & right) O (5 Steps) Airflow direction control (up &...
Page 62
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 1. List of functions Network solution Accessory List S3NM09JL1ZA [DC09RQ NSJ] Category Product Remark S3NM12JL1ZA [DC12RQ NSJ] S3NM18KL1ZA [DC18RQ NSK] Wireless Remote Controller PQWRHQ0FDB Heat Pump PQRCVCL0Q(W) Simple Simple PQRCHCA0Q(W) for Hotel Wired PREMTB001 Standard (White)
Page 63
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 1. List of functions Standard plus Basic functions of Indoor Unit S3NM09JA2FA [PC09SQ NSJ], S3NM12JA2FA [PC12SQ NSJ] Category Functions S3NM18KL2FA [PC18SQ NSK] Air supply outlet Airflow direction control (left & right) O (5 Steps) Airflow direction control (up &...
Page 64
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 1. List of functions Network solution Accessory List S3NM09JA2FA [PC09SQ NSJ] Category Product Remark S3NM12JA2FA [PC12SQ NSJ] S3NM18KL2FA [PC18SQ NSK] Wireless Remote Controller PQWRHQ0FDB Heat Pump PQRCVCL0Q(W) Simple Simple PQRCHCA0Q(W) for Hotel Wired PREMTB001 Standard (White)
Page 65
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 1. List of functions Standard Basic functions of Indoor Unit S3NM09JA3BA [SC09EQ NSJ], S3NM12JA3BA [SC12EQ NSJ] Category Functions S3NM18KL3BA [SC18EQ NSK] Air supply outlet O (5 Steps) Airflow direction control (left & right) Airflow direction control (up &...
Page 66
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 1. List of functions Network solution Accessory List S3NM09JA3BA [SC09EQ NSJ], S3NM12JA3BA [SC12EQ NSJ] Category Product Remark S3NM18KL3BA [SC18EQ NSK] Wireless Remote Controller PQWRHQ0FDB Heat Pump PQRCVCL0Q(W) Simple Simple PQRCHCA0Q(W) for Hotel Wired PREMTB001 Standard (White)
Page 67
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 2. Specifications Deluxe S3NM09JL1ZA S3NM12JL1ZA Model Name [DC09RQ NSJ] [DC12RQ NSJ] 220-240, 1, 50 220-240, 1, 50 Power Supply V, Ø, Hz 220, 1, 60 220, 1, 60 Cooling Capacity Heating Power Input Min./Nom./Max.
Page 68
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 2. Specifications S3NM18KL1ZA Model Name [DC18RQ NSK] 220-240, 1, 50 Power Supply V, Ø, Hz 220, 1, 60 Cooling Capacity Heating Power Input Min./Nom./Max. 26 / 39 / 60 Running Current Min./Nom./Max. 0.22 / 0.28 / 0.40 Casing Color Munsell 7.5BG 10/2 (RAL 9016) W x H x D...
Page 69
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 2. Specifications Standard plus S3NM09JA2FA S3NM12JA2FA Model Name [PC09SQ NSJ] [PC12SQ NSJ] 220-240, 1, 50 220-240, 1, 50 Power Supply V, Ø, Hz 220, 1, 60 220, 1, 60 Cooling Capacity Heating Power Input Min./Nom./Max.
Page 70
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 2. Specifications S3NM18KL2FA Model Name [PC18SQ NSK] 220-240, 1, 50 Power Supply V, Ø, Hz 220, 1, 60 Cooling Capacity Heating Power Input Min./Nom./Max. 26 / 39 / 60 Running Current Min./Nom./Max. 0.22 / 0.28 / 0.40 Casing Color Munsell 7.5BG 10/2 (RAL 9016) W x H x D...
Page 71
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 2. Specifications Standard S3NM09JA3BA S3NM12JA3BA Model Name [SC09EQ NSJ] [SC12EQ NSJ] 220-240, 1, 50 220-240, 1, 50 Power Supply V, Ø, Hz 220, 1, 60 220, 1, 60 Cooling Capacity Heating Power Input Min./Nom./Max.
Page 72
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 2. Specifications S3NM18KL3BA Model Name [SC18EQ NSK] 220-240, 1, 50 Power Supply V, Ø, Hz 220, 1, 60 Cooling Capacity Heating Power Input Min./Nom./Max. W x No. 26 / 39 / 60 Running Current Min./Nom./Max.
Page 74
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 3. Dimensions Standard Plus / Standard (SJ Chassis) S3NM09JA2FA [PC09SQ NSJ], S3NM12JA2FA [PC12SQ NSJ] S3NM09JA3BA [SC09EQ NSJ], S3NM12JA3BA [SC12EQ NSJ]...
Page 75
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 3. Dimensions Deluxe / Standard Plus / Standard (SK Chassis) S3NM18KL1ZA [DC18RQ NSK], S3NM18KL2FA [PC18SQ NSK], S3NM18KL3BA [SC18EQ NSK]...
Page 76
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 4. Piping diagrams Models : Deluxe, Standard Plus, Standard Gas pipe connection port Heat exchanger (flare connection) Cross Flow Fan Liquid pipe connection port (flare connection) LOC. Description PCB Connector Thermistor for suction air temperature CN-TH1 Thermistor for evaporator inlet temperature Th3*...
Page 78
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 5. Wiring Diagrams Standard plus Models : S3NM09JA2FA [PC09SQ NSJ], S3NM12JA2FA [PC12SQ NSJ], S3NM18KL2FA [PC18SQ NSK] Factory Wiring Field Wiring OPTION P/No.: 5401363101 Rev.:...
Page 79
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 5. Wiring Diagrams Standard Models : S3NM09JA3BA [SC09EQ NSJ], S3NM12JA3BA [SC12EQ NSJ], S3NM18KL3BA [SC18EQ NSK] P/No.: 5401291937 Rev.:...
Page 80
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 6. Air flow and temperature distributions (reference data) Models : S3NM09JL1ZA [DC09RQ NSJ], S3NM12JL1ZA [DC12RQ NSJ] Cooling Side View Discharge angle: 35° Air velocity [m/s] Temperature [°C] • Vertical Louver : Center •...
Page 81
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 6. Air flow and temperature distributions (reference data) Heating Side View Discharge angle: 55° Air velocity [m/s] Temperature [°C] 2.7 m 2.7 m • Vertical Louver : Center • Fan speed : Power Top View Discharge angle: 55°...
Page 82
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 6. Air flow and temperature distributions (reference data) Models : S3NM09JA2FA [PC09SQ NSJ], S3NM12JA2FA [PC12SQ NSJ] S3NM09JA3BA [SC09EQ NSJ], S3NM12JA3BA [SC12EQ NSJ] Cooling Side View Discharge angle: 35° Air velocity [m/s] Temperature [°C] 2.7m 2.7 m •...
Page 83
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 6. Air flow and temperature distributions (reference data) Heating Side View Discharge angle: 55° Air velocity [m/s] Temperature [°C] 2.7 m 2.7 m • Vertical Louver : Center • Fan speed : Power Top View Discharge angle: 55°...
Page 84
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 6. Air flow and temperature distributions (reference data) Models : S3NM18KL1ZA [DC18RQ NSK], S3NM18KL2FA [PC18SQ NSK] S3NM18KL3BA [SC18EQ NSK] Cooling Side View Discharge angle: 25° Air velocity [m/s] Temperature [°C] 2.7 m 2.7 m •...
Page 85
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 6. Air flow and temperature distributions (reference data) Heating Side View Discharge angle: 45° Air velocity [m/s] Temperature [°C] 2.7 m 2.7 m • Vertical Louver : Center • Fan speed : Power Top View Discharge angle: 45°...
Page 86
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 7. Sound levels 7.1 Sound pressure level Overall Note 1.Sound measured at some distance away from the center of the unit. 2.Data is valid at free field condition. 3.Reference accoustic pressure 0dB = 20μPa. 4.Data is valid at nominal operation condition.
Page 87
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 7. Sound levels [Unit : mm (inch)] S3NM09JA2FA [PC09SQ NSJ] S3NM09JL1ZA [DC09RQ NSJ] S3NM09JA3BA [SC09EQ NSJ] S3NM12JL1ZA [DC12RQ NSJ] High High High High High High Middle Middle Middle Middle Middle Middle NC-65 NC-65 NC-65 NC-60 NC-60...
Page 88
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 7. Sound levels 7.2 Sound power level Note • Data is valid at diffuse field condition • Data is valid at nominal operating condition • Sound level can be increased in static pressure mode or used air guide. •...
Page 89
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 7. Sound levels S3NM09JA2FA [PC09SQ NSJ] S3NM09JL1ZA [DC09RQ NSJ] S3NM09JA3BA [SC09EQ NSJ] S3NM12JL1ZA [DC12RQ NSJ] High High High High High High Middle Middle Middle Middle Middle Middle NR-90 NR-90 NR-90 NR-85 NR-85 NR-85 NR-80 NR-80 NR-80...
Page 90
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 8. Installation • Please read the instruction sheets completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards. •...
Page 91
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 8. Installation [Unit : mm (inch)] Fixing Installation Plate • The wall you select should be strong and solid enough to prevent vibration. 1. Mount the installation plate on the wall with type "A" screws which are provided with product. (Refer to the Installation manual.) If mounting the unit on a concrete wall, use anchor bolts.
Page 92
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 8. Installation SV chassis Unit Outline Installation plate Left rear piping Right rear piping (Unit : mm) * According to product type, model line up, sales region..etc, applicability of each chassis could be different. CAUTION In case that the unit is installed near the sea, the installation parts may be corroded by salt.
Page 93
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 8. Installation Back side view Pipe Port Left Tubing holder Right Backwards Chassis Cover * The feature can be changed according to type of model. * According to product type, model line up, sales region..etc, applicability of each chassis could be different. Connecting the installation pipe and drain hose Open-end wrench (fixed)
Page 94
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 8. Installation * Foamed polyethylene or equivalent is recommended. CAUTION • Press on the tubing cover and unfold the tubing to downward slowly. And then bend to the left side slowly. • Following bending case from right to left directly may cause damage to the tubing. The feature can be changed according to type •...
Page 95
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 8. Installation 8.2.3 Finishing the indoor unit installation 1.Mount the tubing holder in the original positon. 2.Ensure that the hooks are properly seated on the installation plate by moving it left and right. 3.Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots (clicking sound).
Page 96
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 8. Installation Drill a Hole in the wall 1.Drill the piping hole with a ø 70mm hole core drill. Wall Drill the piping hole at either the right or the left with the holes slightly slanted to the outdoor side.
Page 97
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 8. Installation – Never fail to have separate power specially for the air conditioner. – Provide a circuit breaker switch between power source and the unit. – Confirm the Specification of power source. –...
Page 98
MULTI/SINGLE Indoor unit Wall Mounted Unit (2) 8. Installation Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature. • Do not install the remote controller where it can be affected by : –...
Page 99
Indoor unit ART COOL Mirror MULTI/SINGLE 1.List of Functions 2.Specifications 3.Dimensions 4.Piping diagrams 5.Wiring diagrams 6.Air flow and temperature distribution 7.Sound levels 8.Installation...
Page 100
MULTI/SINGLE Indoor unit ART COOL Mirror 1. List of functions Basic functions of Indoor Unit AMNW07GSJR0 [AM07BP NSJ], USNW09GJRZ0 [AM09BP NSJ] Category Functions USNW12GJRZ0 [AM12BP NSJ], USNW18GKRZ0 [AM18BP NSK] AMNW24GSKR0 [AM24BP NSK] Air supply outlet Airflow direction control (left & right) O (5 Steps) Airflow direction control (up &...
Page 101
MULTI/SINGLE Indoor unit ART COOL Mirror 1. List of functions Network solution Accessory List AMNW07GSJR0 [AM07BP NSJ] USNW09GJRZ0 [AM09BP NSJ] Category Product Remark USNW12GJRZ0 [AM12BP NSJ] USNW18GKRZ0 [AM18BP NSK] AMNW24GSKR0[AM24BP NSK] Wireless Remote Controller PQWRHQ0FDB Heat Pump PQRCVCL0Q(W) Simple Simple PQRCHCA0Q(W) for Hotel...
Page 102
MULTI/SINGLE Indoor unit ART COOL Mirror 2. Specifications AMNW07GSJR0 USNW09GJRZ0 Model Name [AM07BP NSJ] [AM09BP NSJ] 220-240, 1, 50 220-240, 1, 50 Power Supply V, Ø, Hz 220, 1, 60 220, 1, 60 Cooling Capacity Heating Power Input Min./Nom./Max. 11 / 17 / 30 11 / 18 / 30 Running Current Min./Nom./Max.
Page 103
MULTI/SINGLE Indoor unit ART COOL Mirror 2. Specifications USNW12GJRZ0 Model Name [AM12BP NSJ] 220-240, 1, 50 Power Supply V, Ø, Hz 220, 1, 60 Cooling Capacity Heating Power Input Min./Nom./Max. 11 / 19 / 30 Running Current Min./Nom./Max. 0.10 / 0.17 / 0.20 Exterior Color code Munsell 7.5PB 0.2/20 (RAL 9005) W ×...
Page 104
MULTI/SINGLE Indoor unit ART COOL Mirror 2. Specifications USNW18GKRZ0 AMNW24GSKR0 Model Name [AM18BP NSK] [AM24BP NSK] 220-240, 1, 50 220-240, 1, 50 Power Supply V, Ø, Hz 220, 1, 60 220, 1, 60 Cooling Capacity Heating Power Input Min./Nom./Max. 26 / 39 / 60 27 / 45 / 60 Running Current Min./Nom./Max.
Page 107
MULTI/SINGLE Indoor unit ART COOL Mirror 4. Piping diagrams Gas pipe connection port Heat exchanger (flare connection) Cross Flow Fan Liquid pipe connection port (flare connection) LOC. Description PCB Connector Thermistor for suction air temperature CN-TH1 Thermistor for evaporator inlet temperature Th3* Thermistor for evaporator middle temperature CN-TH3...
Page 109
MULTI/SINGLE Indoor unit ART COOL Mirror 6. Air flow and temperature distributions (reference data) Models : AMNW07GSJR0 [AM07BP NSJ], USNW09GJRZ0 [AM09BP NSJ] USNW12GJRZ0 [AM12BP NSJ] Cooling Side View Discharge angle: 35° Air velocity [m/s] Temperature [°C] 2.7m 2.7 m •...
Page 110
MULTI/SINGLE Indoor unit ART COOL Mirror 6. Air flow and temperature distributions (reference data) Heating Side View Discharge angle: 55° Air velocity [m/s] Temperature [°C] 2.7 m 2.7 m • Vertical Louver : Center • Fan speed : Power Top View Discharge angle: 55°...
Page 111
MULTI/SINGLE Indoor unit ART COOL Mirror 6. Air flow and temperature distributions (reference data) Models : USNW18GKRZ0 [AM18BP NSK] Cooling Side View Discharge angle: 25° Air velocity [m/s] Temperature [°C] 2.7 m 2.7 m • Vertical Louver : Center •...
Page 112
MULTI/SINGLE Indoor unit ART COOL Mirror 6. Air flow and temperature distributions (reference data) Heating Side View Discharge angle: 45° Air velocity [m/s] Temperature [°C] 2.7 m 2.7 m • Vertical Louver : Center • Fan speed : Power Top View Discharge angle: 45°...
Page 113
MULTI/SINGLE Indoor unit ART COOL Mirror 6. Air flow and temperature distributions (reference data) Models : AMNW24GSKR0 [AM24BP NSK] Cooling Side View Discharge angle: 25° Air velocity [m/s] Temperature [°C] 2.7 m 2.7 m • Vertical Louver : Center •...
Page 114
MULTI/SINGLE Indoor unit ART COOL Mirror 6. Air flow and temperature distributions (reference data) Heating Side View Discharge angle: 45° Air velocity [m/s] Temperature [°C] 2.7 m 2.7 m • Vertical Louver : Center • Fan speed : Power Top View Discharge angle: 45°...
Page 115
MULTI/SINGLE Indoor unit ART COOL Mirror 7. Sound levels 7.1 Sound pressure level Overall Note 1.Sound measured at some distance away from the center of the unit. 2.Data is valid at free field condition. 3.Reference accoustic pressure 0dB = 20μPa. 4.Data is valid at nominal operation condition.
Page 116
MULTI/SINGLE Indoor unit ART COOL Mirror 7. Sound levels [Unit : mm (inch)] USNW18GKRZ0 [AM18BP NSK] AMNW24GSKR0 [AM24BP NSK] High High Middle Middle NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 Approximate Approximate...
Page 117
MULTI/SINGLE Indoor unit ART COOL Mirror 7. Sound levels [Unit : mm (inch)] 7.2 Sound power level Note • Data is valid at diffuse field condition • Data is valid at nominal operating condition • Sound level can be increased in static pressure mode or used air guide. •...
Page 118
MULTI/SINGLE Indoor unit ART COOL Mirror 8. Installation • Please read the instruction sheets completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards. •...
Page 119
MULTI/SINGLE Indoor unit ART COOL Mirror 8. Installation Fixing Installation Plate • The wall you select should be strong and solid enough to prevent vibration. 1. Mount the installation plate on the wall with type "A" screws which are provided with product. (Refer to the Installation manual.) If mounting the unit on a concrete wall, use anchor bolts.
Page 120
MULTI/SINGLE Indoor unit ART COOL Mirror 8. Installation SV chassis Unit Outline Installation plate Left rear piping Right rear piping (Unit : mm) * According to product type, model line up, sales region..etc, applicability of each chassis could be different. CAUTION In case that the unit is installed near the sea, the installation parts may be corroded by salt.
Page 121
MULTI/SINGLE Indoor unit ART COOL Mirror 8. Installation Back side view Pipe Port Left Tubing holder Right Backwards Chassis Cover * The feature can be changed according to type of model. * According to product type, model line up, sales region..etc, applicability of each chassis could be different. Connecting the installation pipe and drain hose Open-end wrench (fixed)
Page 122
MULTI/SINGLE Indoor unit ART COOL Mirror 8. Installation * Foamed polyethylene or equivalent is recommended. CAUTION • Press on the tubing cover and unfold the tubing to downward slowly. And then bend to the left side slowly. • Following bending case from right to left directly may cause damage to the tubing. The feature can be changed according to type •...
Page 123
MULTI/SINGLE Indoor unit ART COOL Mirror 8. Installation 8.2.3 Finishing the indoor unit installation 1.Mount the tubing holder in the original positon. 2.Ensure that the hooks are properly seated on the installation plate by moving it left and right. 3.Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots (clicking sound).
Page 124
MULTI/SINGLE Indoor unit ART COOL Mirror 8. Installation Drill a Hole in the wall 1.Drill the piping hole with a ø 70mm hole core drill. Wall Drill the piping hole at either the right or the left with the holes slightly slanted to the outdoor side. Indoor Outdoor ...
Page 125
MULTI/SINGLE Indoor unit ART COOL Mirror 8. Installation – Never fail to have separate power specially for the air conditioner. – Provide a circuit breaker switch between power source and the unit. – Confirm the Specification of power source. – Confirm that electrical capacity is sufficient. –...
Page 126
MULTI/SINGLE Indoor unit ART COOL Mirror 8. Installation Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature. • Do not install the remote controller where it can be affected by : –...
Page 127
Indoor unit Ceiling Mounted cassette 4-way MULTI/SINGLE 1.List of Functions 2.Specifications 3.Dimensions 4.Piping diagrams 5.Wiring diagrams 6.Air flow and temperature distribution 7.Sound levels 8.Installation...
Page 128
MULTI/SINGLE Indoor unit Ceiling Mounted cassette 4-way 1. List of functions Basic functions of Indoor Unit ZMNW05GTRA0 [MT06R NR0] ZTNW09GRLA0 [CT09R NR0] Category Functions ZMNW07GTRA0 [MT08R NR0] ZTNW12GRLA0 [CT12R NR0] Air supply outlet Airflow direction control (left & right) Airflow direction control (up &...
Page 129
MULTI/SINGLE Indoor unit Ceiling Mounted cassette 4-way 1. List of functions Network solution Accessory List ZMNW05GTRA0 [MT06R NR0] Category Product Remark ZMNW07GTRA0 [MT08R NR0] Wireless Remote Controller PQWRHQ0FDB Heat Pump PQRCVCL0Q(W) Simple Simple PQRCHCA0Q(W) for Hotel Wired PREMTB001 Standard (White) Remote Standard PREMTBB01...
Page 130
MULTI/SINGLE Indoor unit Ceiling Mounted cassette 4-way 1. List of functions Basic functions of Indoor Unit Category Functions ZTNW18GQLA0 [CT18R NQ0] ZTNW24GPLA0 [CT24R NP0] Air supply outlet Airflow direction control (left & right) Airflow direction control (up & down) Auto Auto Auto swing (left &...
Page 131
MULTI/SINGLE Indoor unit Ceiling Mounted cassette 4-way 1. List of functions Network solution Accessory List Category Product Remark ZTNW18GQLA0 [CT18R NQ0] Wireless Remote Controller PQWRHQ0FDB Heat Pump PQRCVCL0Q(W) Simple Simple PQRCHCA0Q(W) for Hotel Wired PREMTB001 Standard (White) Remote Standard PREMTBB01 Standard (Black) Controller...
Page 132
MULTI/SINGLE Indoor unit Ceiling Mounted cassette 4-way 1. List of functions Basic functions of Indoor Unit ZTNW36GMLA0 [UT36R NM0], ZTNW42GMLA0 [UT42R NM0] Category Functions ZTNW48GMLA0 [UT48R NM0], ZTNW60GMLA0 [UT60R NM0] Air supply outlet Airflow direction control (left & right) Airflow direction control (up &...
Page 133
MULTI/SINGLE Indoor unit Ceiling Mounted cassette 4-way 1. List of functions Network solution Accessory List ZTNW36GMLA0 [UT36R NM0] ZTNW42GMLA0 [UT42R NM0] Category Product Remark ZTNW48GMLA0 [UT48R NM0] ZTNW60GMLA0 [UT60R NM0] Wireless Remote Controller PQWRHQ0FDB Heat Pump PQRCVCL0Q(W) Simple Simple PQRCHCA0Q(W) for Hotel Wired...
Page 134
MULTI/SINGLE Indoor unit Ceiling Mounted cassette 4-way 2. Specifications ZMNW05GTRA0 ZMNW07GTRA0 Model Name Unit [MT06R NR0] [MT08R NR0] 220-240, 1, 50 220-240, 1, 50 Power Supply V , Ø , Hz 220, 1, 60 220, 1, 60 Casing Dimensions W x H x D 570 ×...
Page 135
MULTI/SINGLE Indoor unit Ceiling Mounted cassette 4-way 2. Specifications ZTNW09GRLA0 ZTNW12GRLA0 Model Name Unit [CT09R NR0] [CT12R NR0] 220-240, 1, 50 220-240, 1, 50 Power Supply V , Ø , Hz 220, 1, 60 220, 1, 60 Casing Dimensions W x H x D 570 ×...
Page 136
MULTI/SINGLE Indoor unit Ceiling Mounted cassette 4-way 2. Specifications ZTNW18GQLA0 ZTNW24GPLA0 Model Name Unit [CT18R NQ0] [CT24R NP0] 220-240, 1, 50 220-240, 1, 50 Power Supply V , Ø , Hz 220, 1, 60 220, 1, 60 Casing Dimensions W x H x D 570 ×...
Page 137
MULTI/SINGLE Indoor unit Ceiling Mounted cassette 4-way 2. Specifications ZTNW36GMLA0 ZTNW42GMLA0 Model Name Unit [UT36R NM0] [UT42R NM0] 220-240 , 1 , 50 220-240 , 1 , 50 Power Supply V , Ø , Hz 220 , 1 , 60 220 , 1 , 60 Casing Galvanized Steel Plate...
Page 138
MULTI/SINGLE Indoor unit Ceiling Mounted cassette 4-way 2. Specifications ZTNW48GMLA0 ZTNW60GMLA0 Model Name Unit [UT48R NM0] [UT60R NM0] 220-240 , 1 , 50 220-240 , 1 , 50 Power Supply V , Ø , Hz 220 , 1 , 60 220 , 1 , 60 Casing Galvanized Steel Plate...
Page 143
MULTI/SINGLE Indoor unit Ceiling Mounted cassette 4-way 4. Piping diagrams Gas pipe connection port Heat exchanger (flare connection) Heating Cooling Thermistor for Turbo fan Evaporator Thermistor for outlet temperature suction air temperature Thermistor for Humid sensor Evaporator inlet temperature Liquid pipe connection port (flare connection) Description PCB Connector...
Page 146
MULTI/SINGLE Indoor unit Ceiling Mounted cassette 4-way 6. Sound levels 6.1 Sound pressure level Overall Note • Sound measured at 1.5m away from the center of the unit. • Data is valid at free field condition. • Data is valid at nominal operation condition. Ceiling •...
Page 148
MULTI/SINGLE Indoor unit Ceiling Mounted cassette 4-way 6. Sound levels [Unit : mm] 6.2 Sound power level Note 1. Reference acoustic intensity 0dB = 10E-6μW/m 2. Sound level will vary depending on a range of factors such as the construction (acoustic absorption coefficient) of particular room in which the equipment in installed.
Page 150
MULTI/SINGLE Indoor unit Ceiling Mounted cassette 4-way 7. Air flow and temperature distributions (reference data) Model : ZMNW05GTRA0 [MT06R NR0], ZMNW07GTRA0 [MT08R NR0] Heating Cooling Discharge angle: 50° Discharge angle: 40° Air velocity [m/s] Air velocity [m/s] 2.7m 2.7m 2.5m 1.5m 1.5m 2.5m...
Page 151
MULTI/SINGLE Indoor unit Ceiling Mounted cassette 4-way 7. Air flow and temperature distributions (reference data) Model : ZTNW12GRLA0 [CT12R NR0] Cooling Heating Discharge angle: 40° Discharge angle: 50° Air velocity [m/s] Air velocity [m/s] 2.7m 2.7m 0.25 0.25 0.25 0.25 2.5m 2.5m 2.5m...
Page 152
MULTI/SINGLE Indoor unit Ceiling Mounted cassette 4-way 7. Air flow and temperature distributions (reference data) Model : ZTNW24GPLA0 [CT24R NP0] Cooling Heating Discharge angle: 40° Discharge angle: 50° Air velocity [m/s] Air velocity [m/s] 2.7m 2.7m 0.25 0.25 0.25 0.25 Temperature [°C] Temperature [°C] 2.7m...
Page 153
MULTI/SINGLE Indoor unit Ceiling Mounted cassette 4-way 7. Air flow and temperature distributions (reference data) Model : ZTNW42GMLA0 [UT42R NM0] Cooling Heating Discharge angle: 40° Discharge angle: 50° Air velocity [m/s] Air velocity [m/s] 3.2m 3.2m 0.25 0.25 0.25 0.25 Temperature [°C] Temperature [°C] 3.2m...
Page 154
MULTI/SINGLE Indoor unit Ceiling Mounted cassette 4-way 7. Air flow and temperature distributions (reference data) Model : ZTNW60GMLA0 [UT60R NM0] Cooling Heating Discharge angle: 40° Discharge angle: 50° Air velocity [m/s] Air velocity [m/s] 3.2m 3.2m 0.25 0.25 0.5 1.0 0.25 0.25 Temperature [°C]...
Page 155
MULTI/SINGLE Indoor unit Ceiling Mounted cassette 4-way 8. Installation • Please read the instruction sheets completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards. •...
Page 156
MULTI/SINGLE Indoor unit Ceiling Mounted cassette 4-way 8. Installation • Make sure that ventilation fan is enough to cover all noxious gases from this place. • Ensure enough distance from the cooking room to install the air conditioner in such a place where it may not suck oily steam.
Page 157
MULTI/SINGLE Indoor unit Ceiling Mounted cassette 4-way 8. Installation TP Chassis * According to product type, model line up, sales region..etc, applicability of each chassis could be 10(13/32) different. or more Ceiling Ceiling Board Ceiling Board 500(19-11/16) 500(19-11/16) or more 15(19/32) or more ±3(1/8)
Page 158
MULTI/SINGLE Indoor unit Ceiling Mounted cassette 4-way 8. Installation Indoor Low temperature of the floor Discharge Suction High elevation Hot air (50~100mm Outdoor side of the ceiling Insulation required) Outdoor side Garage Outdoor Cold air side (Entering of air by Outdoor side frequent opening and closing of door)
Page 159
MULTI/SINGLE Indoor unit Ceiling Mounted cassette 4-way 8. Installation In case of multiple indoor cassette units (recommended) Indoor unit Indoor unit Ventilator Lighting 1,500mm or more 2,000mm or more 3,000mm or more 8.3 Ceiling opening dimensions and hanging bolt location CAUTION •...
Page 160
MULTI/SINGLE Indoor unit Ceiling Mounted cassette 4-way 8. Installation • The following parts are local purchasing. Hanging bolt 1.Hanging bolt - W 3/8 or M10 (W3/8 or M10) 2.Nut - W 3/8 or M10 Flat washer for M10 (W3/8 or M10) 3.Spring washer - M10 (accessory) 4.Plate washer - M10...
Page 161
MULTI/SINGLE Indoor unit Ceiling Mounted cassette 4-way 8. Installation 8.4 Connecting Cables between Indoor Unit and Outdoor Unit Remote controller cord Power supply cord Transmission cord Transmission cord Remote controller cord Power supply cord 8.4.1 General instructions • All field supplied parts and materials, electric works must conform to local codes. Use copper wire only. •...
Page 162
MULTI/SINGLE Indoor unit Ceiling Mounted cassette 4-way 8. Installation 8.4.2 Wiring connection • Connect the wires to the terminals on the control board ind vidually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.
Page 163
MULTI/SINGLE Indoor unit Ceiling Mounted cassette 4-way 8. Installation 8.5 Installation of Decoration Panel • The decoration panel has its installation direction. • Before installing the decoration panel, always remove the paper template. CAUTION • Install certainly the decoration panel. Cool air leakage causes sweating or falling of water-drops. Good case Bad case Good example...
Page 164
MULTI/SINGLE Indoor unit Ceiling Mounted cassette 4-way 8. Installation • Possible drain head height is upto 700 mm (27-6/19 inch). So the drain head should be installed below 700 mm (27-6/19 inch). • Be sure to install heat insulation on the drain piping. –...
Page 165
MULTI/SINGLE Indoor unit Ceiling Mounted cassette 4-way 8. Installation 8.6.4 Ground drain piping • It is standard work practice to make connections to the main pipe from above. The pipe down from the combination should be as large as possible. •...
Page 166
Indoor unit Ceiling concealed duct - Middle static pressure MULTI/SINGLE 1.List of Functions 2.Specifications 3.Dimensions 4.Piping diagrams 5.Wiring diagrams 6.External static pressure & Air flow 7.Sound levels 8.Installation...
Page 167
MULTI/SINGLE Indoor unit Ceiling concealed duct - Middle static pressure 1. List of functions Basic functions of Indoor Unit ZBNW18GM1A0 [CM18R N10] ZBNW24GM1A0 [CM24R N10] Category Functions ZBNW36GM2A0 [UM36R N20] ZBNW42GM2A0 [UM42R N20] ZBNW48GM3A0 [UM48R N30] ZBNW60GM3A0 [UM60R N30] Air supply outlet Airflow direction control (left &...
Page 168
MULTI/SINGLE Indoor unit Ceiling concealed duct - Middle static pressure 1. List of functions Network solution Accessory List ZBNW18GM1A0 [CM18R N10] Category Product Remark ZBNW24GM1A0 [CM24R N10] Wireless Remote Controller PQWRHQ0FDB Heat Pump O*** PQRCVCL0Q(W) Simple Simple PQRCHCA0Q(W) for Hotel Wired PREMTB001 Standard (White)
Page 169
MULTI/SINGLE Indoor unit Ceiling concealed duct - Middle static pressure 1. List of functions ZBNW36GM2A0 [UM36R N20] ZBNW42GM2A0 [UM42R N20] Category Product Remark ZBNW48GM3A0 [UM48R N30] ZBNW60GM3A0 [UM60R N30] Wireless Remote Controller PQWRHQ0FDB Heat Pump O*** PQRCVCL0Q(W) Simple Simple PQRCHCA0Q(W) for Hotel Wired PREMTB001...
Page 170
MULTI/SINGLE Indoor unit Ceiling concealed duct - Middle static pressure 2. Specifications ZBNW18GM1A0 ZBNW24GM1A0 Model Name Unit [CM18R N10] [CM24R N10] 220-240, 1, 50 220-240, 1, 50 Power Supply V , Ø , Hz 220, 1, 60 220, 1, 60 Casing Dimensions W x H x D...
Page 171
MULTI/SINGLE Indoor unit Ceiling concealed duct - Middle static pressure 2. Specifications ZBNW36GM2A0 ZBNW42GM2A0 Model Name Unit [UM36R N20] [UM42R N20] 220-240 , 1 , 50 220-240 , 1 , 50 Power Supply V , Ø , Hz 220 , 1 , 60 220 , 1 , 60 Casing Galvanized Steel Plate...
Page 172
MULTI/SINGLE Indoor unit Ceiling concealed duct - Middle static pressure 2. Specifications ZBNW48GM3A0 ZBNW60GM3A0 Model Name Unit [UM48R N30] [UM60R N30] 220-240 , 1 , 50 220-240 , 1 , 50 Power Supply V , Ø , Hz 220 , 1 , 60 220 , 1 , 60 Casing Galvanized Steel Plate...
Page 176
MULTI/SINGLE Indoor unit Ceiling concealed duct - Middle static pressure 4. Piping diagrams Model : ZBNW18GM1A0 [CM18R N10], ZBNW24GM1A0 [CM24R N10] Gas pipe connection port Heat exchanger (flare connection) Heating Thermistor for Cooling Sirocco Fan evaporator outlet Thermistor for temperature suction air temperature Thermistor for...
Page 177
MULTI/SINGLE Indoor unit Ceiling concealed duct - Middle static pressure 4. Piping diagrams Models : ZBNW36GM2A0 [UM36R N20], ZBNW42GM2A0 [UM42R N20], ZBNW48GM3A0 [UM48R N30], ZBNW60GM3A0 [UM60R N30] Gas pipe connection port Heat exchanger (flare connection) Heating Thermistor for Cooling Sirocco Fan evaporator outlet Thermistor for temperature...
Page 181
MULTI/SINGLE Indoor unit Ceiling concealed duct - Middle static pressure 6. External Static Pressure & Air Flow How to Set E.S.P. on the remote controller? This is the function that decides the strength of the wind for each wind level and because this function is to make the installation easier.
Page 182
MULTI/SINGLE Indoor unit Ceiling concealed duct - Middle static pressure 6. External Static Pressure & Air Flow Installer Setting - Static Pressure Step Setting This function is applied to only duct type. Setting this in other cases will cause malfunction. This function is only available on some products.
Page 184
MULTI/SINGLE Indoor unit Ceiling concealed duct - Middle static pressure 6. External Static Pressure & Air Flow Note 1. Be sure to set the value refering table 1. Unexpected set value will cause mal-function. 2. Table 1 is based at 230V. According to the fluctuation of voltage, air flow rate varies. 3.
Page 187
MULTI/SINGLE Indoor unit Ceiling concealed duct - Middle static pressure 7. Installation • Please read the instruction sheets completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards. •...
Page 188
MULTI/SINGLE Indoor unit Ceiling concealed duct - Middle static pressure 7. Installation 2. Avoid installing air conditioner in such places where cooking oil or iron powder is generated. 3. Avoid places where inflammable gas is generated. 4. Avoid place where noxious gas is generated. 5.
Page 189
MULTI/SINGLE Indoor unit Ceiling concealed duct - Middle static pressure 7. Installation 7.2 Ceiling dimension and hanging bolt location CAUTION • During the installation, care should be taken not to damage electric wires. • In case of using a drain pump, install the unit horizontally using a level gauge. Ceiling Level gauge ※...
Page 190
MULTI/SINGLE Indoor unit Ceiling concealed duct - Middle static pressure 7. Installation Installation dimension of Indoor unit M1/M2/M3 Chassis * According to product type, model line up, sales region..etc, applicability of each chassis could be different. Drain hole Dimension (mm) Chassis name 933.4 971.6...
Page 191
MULTI/SINGLE Indoor unit Ceiling concealed duct - Middle static pressure 7. Installation 7.3 Connecting pipes to the indoor unit Refrigerant piping work To detail information for connecting the refrigerant pipes, please refer to the installation manual included withproduct. Piping insulation work •...
Page 192
MULTI/SINGLE Indoor unit Ceiling concealed duct - Middle static pressure 7. Installation 7.4 Indoor Unit Drain Piping Important • The drain pipe should be at least equal in size to drain conduit of the indoor unit. • The drain pipe is thermally insulated to prevent the formation of condensation inside the pipe. •...
Page 193
MULTI/SINGLE Indoor unit Ceiling concealed duct - Middle static pressure 7. Installation 7.4.2 Drain pipe connection without drain pump • Drain piping must have down-slope (1/50 to 1/100). Be sure not to provide up-and-down slope to prevent reversal flow. • During drain piping connection, be careful not to exert force on the drain port on the indoor unit.
Page 194
MULTI/SINGLE Indoor unit Ceiling concealed duct - Middle static pressure 7. Installation 7.4.3 Method of Drainage test Drainage test of indoor unit Use the following procedure to test the drainage. 1.In case that there are air filter, remove the air filter first. 2.Spray one or two glasses of water on the evaporator.
Page 195
MULTI/SINGLE Indoor unit Ceiling concealed duct - Middle static pressure 7. Installation 7.4.5 Ground drain piping • It is standard work practice to make connections to the main pipe from above. The pipe down from the combination should be as large as possible. •...
Page 196
MULTI/SINGLE Indoor unit Ceiling concealed duct - Middle static pressure 7. Installation 7.5 Electric wiring work 7.5.1 General instructions • All field supplied parts and materials, electric works must conform to local codes. Use copper wire only. • Follow the "WIRING DIAGRAM” attached to the unit body to wire the outdoor unit, indoor units and the remote controller.
Page 197
MULTI/SINGLE Indoor unit Ceiling concealed duct - Middle static pressure 7. Installation WARNING • Make sure that the screws of the terminal are fixed tightly. • The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation.
Page 198
Indoor unit Ceiling concealed duct - Low static pressure MULTI/SINGLE 1.List of Functions 2.Specifications 3.Dimensions 4.Piping diagrams 5.Wiring diagrams 6.External static pressure & Air flow 7.Sound levels 8.Installation...
Page 199
MULTI/SINGLE Indoor unit Ceiling concealed duct - Low static pressure 1. List of functions Basic functions of Indoor Unit ZBNW09GL2A0 [CL09R N20] / ZBNW12GL2A0 [CL12R N20] Category Functions ZBNW18GL2A0 [CL18R N20] / ZBNW24GL3A0 [CL24R N30] Air supply outlet Airflow direction control (left & right) Airflow direction control (up &...
Page 200
MULTI/SINGLE Indoor unit Ceiling concealed duct - Low static pressure 1. List of functions Network solution Accessory List ZBNW09GL2A0 [CL09R N20] Category Product Remark ZBNW12GL2A0 [CL12R N20] Wireless Remote Controller PQWRHQ0FDB Heat Pump O*** PQRCVCL0Q(W) Simple Simple PQRCHCA0Q(W) for Hotel Wired PREMTB001 Standard (White)
Page 201
MULTI/SINGLE Indoor unit Ceiling concealed duct - Low static pressure 1. List of functions ZBNW18GL2A0 [CL18R N20] Category Product Remark ZBNW24GL3A0 [CL24R N30] Wireless Remote Controller PQWRHQ0FDB Heat Pump O*** PQRCVCL0Q(W) Simple Simple PQRCHCA0Q(W) for Hotel Wired PREMTB001 Standard (White) Remote Standard PREMTBB01...
Page 202
MULTI/SINGLE Indoor unit Ceiling concealed duct - Low static pressure 2. Specifications ZBNW09GL2A0 ZBNW12GL2A0 Model Name Unit [CL09R N20] [CL12R N20] 220-240, 1, 50 220-240, 1, 50 Power Supply V , Ø , Hz 220, 1, 60 220, 1, 60 Casing Dimensions W x H x D...
Page 203
MULTI/SINGLE Indoor unit Ceiling concealed duct - Low static pressure 2. Specifications ZBNW18GL2A0 ZBNW24GL3A0 Model Name Unit [CL18R N20] [CL24R N30] 220-240, 1, 50 220-240, 1, 50 Power Supply V , Ø , Hz 220, 1, 60 220, 1, 60 Casing Dimensions W x H x D...
Page 205
MULTI/SINGLE Indoor unit Ceiling concealed duct - Low static pressure 4. Piping diagrams L2 Chassis ZBNW09GL2A0 [CL09R N20] / ZBNW12GL2A0 [CL12R N20] / ZBNW18GL2A0 [CL18R N20] : Cooling : Heating Evaporator Out Temperature Thermistor Evaporator In Temperature Sirocco Fan Thermistor Indoor Unit Inlet Air Temperature...
Page 206
MULTI/SINGLE Indoor unit Ceiling concealed duct - Low static pressure 4. Piping diagrams L3 Chassis ZBNW24GL3A0 [CL24R N30] : Cooling : Heating Evaporator Out Temperature Thermistor Evaporator In Temperature Sirocco Fan Thermistor Indoor Unit Inlet Air Temperature Thermistor Description PCB Connector Inlet Air Temperature Thermistor CN-ROOM Evaporator In Temperature Thermistor...
Page 208
MULTI/SINGLE Indoor unit Ceiling concealed duct - Low static pressure 6. External Static Pressure & Air Flow How to Set E.S.P. on the remote controller? This is the function that decides the strength of the wind for each wind level and because this function is to make the installation easier.
Page 210
MULTI/SINGLE Indoor unit Ceiling concealed duct - Low static pressure 7. Installation • Please read the instruction sheets completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards. •...
Page 211
MULTI/SINGLE Indoor unit Ceiling concealed duct - Low static pressure 7. Installation • Make sure that ventilation fan is enough to cover all noxious gases from this place. • Ensure enough distance from the cooking room to install the air conditioner in such a place where it may not suck oily steam.
Page 212
MULTI/SINGLE Indoor unit Ceiling concealed duct - Low static pressure 7. Installation 7.2 Ceiling dimension and hanging bolt location CAUTION • During the installation, care should be taken not to damage electric wires. • In case of using a drain pump, install the unit horizontally using a level gauge. Ceiling Level gauge ※...
Page 213
MULTI/SINGLE Indoor unit Ceiling concealed duct - Low static pressure 7. Installation Installation of Unit Install the unit above the ceiling correctly. Drainage hole Dimension (mm) Chassis 1,133 1,172 1,060 1,100 7.3 Connecting cables between Indoor Unit and Outdoor Unit 7.3.1 General instructions •...
Page 214
MULTI/SINGLE Indoor unit Ceiling concealed duct - Low static pressure 7. Installation 7.3.2 Wiring connection • Connect the wires to the terminals on the control board ind vidually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.
Page 215
MULTI/SINGLE Indoor unit Ceiling concealed duct - Low static pressure 7. Installation 7.4 Indoor Unit Drain Piping 7.4.1 Drain piping of indoor unit with drain pump • Drain piping must have down-slope (1/50 to 1/100). Be sure not to provide up-and-down slope to prevent reversal flow.
Page 216
MULTI/SINGLE Indoor unit Ceiling concealed duct - Low static pressure 7. Installation 7.4.2 Drain pipe connection without drain pump • Drain piping must have down-slope (1/50 to 1/100). Be sure not to provide up-and-down slope to prevent reversal flow. • During drain piping connection, be careful not to exert force on the drain port on the indoor unit.
Page 217
MULTI/SINGLE Indoor unit Ceiling concealed duct - Low static pressure 7. Installation 7.4.3 Method of Drainage test Drainage test of indoor unit Use the following procedure to test the drainage. 1.In case that there are air filter, remove the air filter first. 2.Spray one or two glasses of water on the evaporator.
Page 218
MULTI/SINGLE Indoor unit Ceiling concealed duct - Low static pressure 7. Installation 7.4.5 Ground drain piping • It is standard work practice to make connections to the main pipe from above. The pipe down from the combination should be as large as possible. •...
Page 219
Indoor unit Ceiling Suspended Unit MULTI/SINGLE 1.List of Functions 2.Specifications 3.Dimensions 4.Piping diagrams 5.Wiring diagrams 6.Air flow and temperature distribution 7.Sound levels 8.Installation...
Page 220
MULTI/SINGLE Indoor unit Ceiling Suspended Unit 1. List of functions Basic functions of Indoor Unit ZVNW18GM1A0 [UV18R N10] ZVNW24GM1A0 [UV24R N10] Category Functions ZVNW36GM2A0 [UV36R N20] ZVNW42GM2A0 [UV42R N20] ZVNW48GM2A0 [UV48R N20] ZVNW60GM2A0 [UV60R N20] Air supply outlet Airflow direction control (left & right) Airflow direction control (up &...
Page 221
MULTI/SINGLE Indoor unit Ceiling Suspended Unit 1. List of functions Network solution Accessory List ZVNW18GM1A0 [UV18R N10] ZVNW24GM1A0 [UV24R N10] ZVNW36GM2A0 [UV36R N20] Category Product Remark ZVNW42GM2A0 [UV42R N20] ZVNW48GM2A0 [UV48R N20] ZVNW60GM2A0 [UV60R N20] Wireless Remote Controller PQWRHQ0FDB Heat Pump PQRCVCL0Q(W) Simple...
Page 222
MULTI/SINGLE Indoor unit Ceiling Suspended Unit 2. Specifications ZVNW18GM1A0 ZVNW24GM1A0 Model Name Unit [UV18R N10] [UV24R N10] 220-240 / 1 / 50 220-240 / 1 / 50 Power Supply V , Ø , Hz 220 / 1 / 60 220 / 1 / 60 Casing Morning Fog Morning Fog...
Page 223
MULTI/SINGLE Indoor unit Ceiling Suspended Unit 2. Specifications ZVNW36GM2A0 ZVNW42GM2A0 Model Name Unit [UV36R N20] [UV42R N20] 220-240 , 1 , 50 220-240 , 1 , 50 Power Supply V , Ø , Hz 220 , 1 , 60 220 , 1 , 60 Casing Morning Fog Morning Fog...
Page 224
MULTI/SINGLE Indoor unit Ceiling Suspended Unit 2. Specifications ZVNW48GM2A0 ZVNW60GM2A0 Model Name Unit [UV48R N20] [UV60R N20] 220-240 , 1 , 50 220-240 , 1 , 50 Power Supply V , Ø , Hz 220 , 1 , 60 220 , 1 , 60 Casing Morning Fog Morning Fog...
Page 225
MULTI/SINGLE Indoor unit Ceiling Suspended Unit 3. Dimensions ZVNW18GM1A0 [UV18R N10] / ZVNW24GM1A0 [UV24R N10]...
Page 227
MULTI/SINGLE Indoor unit Ceiling Suspended Unit 4. Piping diagrams Models : ZVNW18GM1A0 [UV18R N10], ZVNW24GM1A0 [UV24R N10] Gas pipe connection port Heat exchanger (flare connection) Heating Thermistor for Cooling Cross Flow Fan Evaporator Thermistor for outlet temperature suction air temperature Thermistor for Humid sensor Evaporator inlet...
Page 228
MULTI/SINGLE Indoor unit Ceiling Suspended Unit 4. Piping diagrams [Unit : mm] Models : ZVNW36GM2A0 [UV36R N20], ZVNW42GM2A0 [UV42R N20], ZVNW48GM2A0 [UV48R N20], ZVNW60GM2A0 [UV60R N20] Gas pipe connection port Heat exchanger (flare connection) Heating Cross Flow Fan Thermistor for Cooling evaporator outlet Thermistor for...
Page 230
MULTI/SINGLE Indoor unit Ceiling Suspended Unit 6. Sound levels 6.1 Sound pressure level Overall Note • Data is valid at nominal operation condition. • Reference accoustic pressure 0dB=20μPa. • Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.
Page 231
MULTI/SINGLE Indoor unit Ceiling Suspended Unit 6. Sound levels ZVNW48GM2A0 [UV48R N20] ZVNW60GM2A0 [UV60R N20] High Middle NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 Approximate Hearing NC-20 Threshold NC-15 1000 2000 4000 8000 Octave Band Center Frequency (Hz)
Page 232
MULTI/SINGLE Indoor unit Ceiling Suspended Unit 6. Sound levels 6.2 Sound power level Note 1. Reference acoustic intensity 0dB = 10E-6μW/m 2. Sound level will vary depending on a range of factors such as the construction (acoustic absorption coefficient) of particular room in which the equipment in installed. Sound power level [dB(A)] Model ZVNW18GM1A0 [UV18R N10]...
Page 233
MULTI/SINGLE Indoor unit Ceiling Suspended Unit 7. Air flow and temperature distributions (reference data) Model : ZVNW18GM1A0 [UV18R N10] Cooling Heating Discharge angle: 0° Discharge angle: 40° Air velocity [m/s] Air velocity [m/s] 2.7m 2.7m 0.25 0.25 0.25 Temperature [°C] Temperature [°C] 2.7m 2.7m...
Page 234
MULTI/SINGLE Indoor unit Ceiling Suspended Unit 7. Air flow and temperature distributions (reference data) Model : ZVNW36GM2A0 [UV36R N20] Cooling Heating Discharge angle: 0° Discharge angle: 40° Air velocity [m/s] Air velocity [m/s] 2.7m 2.7m 0.25 0.25 Temperature [°C] Temperature [°C] 2.7m 2.7m Model : ZVNW42GM2A0 [UV42R N20]...
Page 235
MULTI/SINGLE Indoor unit Ceiling Suspended Unit 7. Air flow and temperature distributions (reference data) Model : ZVNW48GM2A0 [UV48R N20] Cooling Heating Discharge angle: 0° Discharge angle: 40° Air velocity [m/s] Air velocity [m/s] 2.7m 2.7m 0.25 0.25 Temperature [°C] Temperature [°C] 2.7m 2.7m 30 31...
Page 236
MULTI/SINGLE Indoor unit Ceiling Suspended Unit 8. Installation • Please read the instruction sheets completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards. •...
Page 237
MULTI/SINGLE Indoor unit Ceiling Suspended Unit 8. Installation • Make sure that ventilation fan is enough to cover all noxious gases from this place. • Ensure enough distance from the cooking room to install the air conditioner in such a place where it may not suck oily steam.
Page 238
MULTI/SINGLE Indoor unit Ceiling Suspended Unit 8. Installation 8.2 Installation of indoor units 8.2.1 Ceiling dimension and hanging bolt location CAUTION • During the installation, care should be taken not to damage electric wires. • In case of using a drain pump, install the unit horizontally using a level gauge. Ceiling Level gauge ※...
Page 239
MULTI/SINGLE Indoor unit Ceiling Suspended Unit 8. Installation • The following parts are local purchasing. Hanging bolt 1.Hanging bolt - W 3/8 or M10 (W3/8 or M10) 2.Nut - W 3/8 or M10 Flat washer for M10 (W3/8 or M10) 3.Spring washer - M10 (accessory) 4.Plate washer - M10...
Page 240
MULTI/SINGLE Indoor unit Ceiling Suspended Unit 8. Installation 8.2.2 Preparing work for Installation Open side cover 1) Remove two screws from Left and Right side-cover. 2) Unlock side-cover from side panel by slightly pulling the edge of side cover. Tap the side-cover with your palm on the backside. Right side cover Left side cover...
Page 241
MULTI/SINGLE Indoor unit Ceiling Suspended Unit 8. Installation Drill a hole in the wall • Drill the piping hole with a ø70mm hole core Wall drill. • Drill the piping hole at either the right or the left Indoor Outdoor with the hole slightly slanted to the outdoor side.
Page 242
MULTI/SINGLE Indoor unit Ceiling Suspended Unit 8. Installation 8.3 Indoor Unit Drain Piping 8.3.1 Drain piping of indoor unit • Drain piping must have down-slope (1/50 to 1/100). Be sure not to provide up-and-down slope to prevent reversal flow. • During drain piping connection, be careful not to exert force on the drain port on the indoor unit.
Page 243
MULTI/SINGLE Indoor unit Ceiling Suspended Unit 8. Installation Important • Hook on the bracket after connecting the drain hose as shown figure. • The drain hose should point downward for easy drain Downward slope flow. • Do not make drain piping like the following. Accumulated •...
Page 244
MULTI/SINGLE Indoor unit Ceiling Suspended Unit 8. Installation 8.3.2 Drain test Drainage test of indoor unit Use the following procedure to test the drainage. 1.In case that there are air filter, remove the air filter first. 2.Spray one or two glasses of water on the evaporator. 3.Check the drainage.
Page 245
MULTI/SINGLE Indoor unit Ceiling Suspended Unit 8. Installation 8.4.2 Wiring connection • Connect the wires to the terminals on the control board ind vidually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.