10. Performance Data
Model No.: LV-D4881HL
Indoor
14.0
DB(°F)
TC
PI
60.8
32.4
2.6
64.4
31.4
2.7
68.0
30.5
2.8
71.6
29.4
2.9
75.2
28.4
3.0
Model No.: LV-D6081HL
Indoor
14.0
DB(°F)
TC
PI
60.8
40.5
3.6
64.4
39.3
3.8
68.0
38.1
3.9
71.6
36.7
4.0
75.2
35.4
4.1
Notes : 1. All capacities are net, indoor fan motor heat is deducted.
2. Capacities are based on the following conditions.
Outdoor air : 85%RH. However, the condition on nominal capacity is 44.6°FDB/42.8°FWB.
3. TC=Total heating capacity(Unit:kBtu/h)
4. PI=Power Input(Comp.+indoor fan motor+outdoor fan motor) (kW)
Correction Factor for Heating Capacity due to Frost on Heat Exchanger and Defrosting Operation.
The heating capacity in the "Heating Capacity" Table above indicates the actual heating capacity excluding the effect of frost on the heat
exchanger and the defrosting operation. Therefore, use the following factor to calculate the average heating capacity including capacity
reduction by frost on the exchanger and defrosting operation.
Correction Factor
Outdoor Air Temperature
(°FWB, RH=85%)
Correction Factor
50
Ceiling & Floor, Ceiling Suspended (50Hz, R22)
23.0
32.0
TC
PI
TC
PI
TC
38.2
2.9
44.2
3.1
46.4
37.0
3.0
42.8
3.2
44.9
35.9
3.1
41.5
3.3
43.6
34.6
3.2
40.0
3.4
42.0
33.4
3.3
38.6
3.5
40.6
23.0
32.0
TC
PI
TC
PI
TC
47.8
4.0
55.2
4.3
58.0
46.2
4.1
53.5
4.5
56.2
44.9
4.3
51.9
4.6
54.5
43.2
4.4
50.0
4.8
52.5
41.8
4.5
48.3
4.9
50.7
14
21.2
24.8
0.95
0.95
0.89
Outdoor WB (°F)
35.6
39.2
42.8
PI
TC
PI
TC
3.2
48.6
3.3
51.4
3.3
47.1
3.4
49.8
3.4
45.7
3.5
48.0
3.5
44.0
3.7
46.5
3.7
42.5
3.8
44.9
Outdoor WB (°F)
35.6
39.2
42.8
PI
TC
PI
TC
4.5
60.8
4.6
64.2
4.6
58.9
4.8
62.2
4.8
57.1
4.9
60.0
4.9
55.1
5.1
58.2
5.1
53.2
5.2
56.2
28.4
32
0.87
0.87
50.0
59.0
PI
TC
PI
TC
PI
3.4
55.6
3.6
61.4
3.8
3.5
53.9
3.7
59.5
3.9
3.6
52.3
3.8
57.7
4.1
3.7
50.4
3.9
55.6
4.2
3.8
48.6
4.0
53.7
4.3
50.0
59.0
PI
TC
PI
TC
PI
4.7
69.5
4.9
76.8
5.3
4.8
67.3
5.1
74.3
5.5
5.0
65.3
5.3
72.1
5.6
5.2
63.0
5.4
69.5
5.8
5.3
60.8
5.6
67.1
6.0
35.6
39.2
42.8
0.89
0.91
1.00