hit counter script

App-06: Traverse Offset (Hi) Setting; App-07: Traverse Offset (Lo) Setting; App-08: Runing Auxiliary Motor Number Display; App-09: Starting Auxiliary Motor Selection - LG SV-iS5 Instruction Manual

Variable frequency drives
Hide thumbs Also See for SV-iS5:
Table of Contents

Advertisement

The ' Trv Acc' terminal set in EXT-30 to EXT-32 is ON
during traverse acceleration time. (Open Collector
Output)
The ' Trv Dec' terminal set in EXT-30 to EXT-32 is ON
during traverse deceleration time. (Open Collector
Output)
APP-04 and APP-05 should be set to a value less than
APP-03. If not, traverse control does not accomplished
correctly.

APP-06: Traverse Offset (Hi) Setting

APP-07: Traverse Offset (Lo) Setting

APP? Trv Off Hi
06
0.0 %
Factory Default:
0.0 %
This code makes positive offset during traverse
operation by multi-function input terminal. When the ' Trv
Off Hi' terminal is ON, the offset frequency is added to
the reference frequency. To use this function, set a
terminal out of multi-function input terminals (P1, P2, P3)
to ' Trv Off Hi' in I/O-12 ~ I/O-14. The offset value is
determined by,
Trv. Off Hi Frequency =(Reference Frequency * Trv. Off
Hi)/100
APP? Trv Off Lo
07
0.0 %
Factory Default:
0.0 %
This code makes negative offset during traverse
operation by multi-function input terminal. When the ' Trv
Off Lo' terminal is ON, the offset frequency is subtracted
from the reference frequency. To use this function, set a
terminal out of multi-function input terminals (P1, P2, P3)
to ' Trv Off Lo' in I/O-12 ~ I/O-14. The offset value is
determined by,
Trv. Off Lo Frequency =(Reference Frequency * Trv. Off
Lo)/100
APP-08: Running Auxiliary Motor Number
Display
APP?Aux Mot Run
08
0
Factory Default:
0
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu
06
0.0
0.0
07
0.0
0.0
08
0
0
147
Chapter 6 - Parameter Description [APP]
This code shows how many auxiliary motors are running
by MMC control.

APP-09: Starting Auxiliary Motor Selection

APP?Starting Aux
09
1
Factory Default:
1
This code sets the starting auxiliary motor for MMC
control.
APP-10: Operation Time Display on Auto
Change
APP?Auto Op Time
10
00:00
Factory Default:
00:00
This code displays the operation time after Auto Change
is accomplished.
APP-11: Start Frequency of Aux. Motor 1
APP-12: Start Frequency of Aux. Motor 2
APP-13: Start Frequency of Aux. Motor 3
APP-14: Start Frequency of Aux. Motor 4
APP?Start freq1
11
49.99 Hz
Factory Default:
49.99 Hz
APP?Start freq2
12
49.99 Hz
Factory Default:
49.99 Hz
APP?Start freq3
13
49.99 Hz
Factory Default:
49.99 Hz
APP?Start freq4
14
49.99 Hz
Factory Default:
49.99 Hz
The inverter turns on AUX, RLY1, RLY2, and RLY3 in
09
1
1
10
00:00
00:00
11
49.99
49.99
12
49.99
49.99
13
49.99
49.99
14
49.99
49.99