Chapter 6 - Parameter Description [I/O]
Output Frequency
I/O-42
AXA-AXC
ON
[AXA-AXC configured as ' FDT-3' ]
[FDT-4]
AXA-AXC is CLOSED when the output frequency
reaches the FDT frequency. The output is OPENED
when the output frequency goes below the FDT
bandwidth centered on the FDT frequency.
Output Frequency
I/O-42
AXA-AXC
CLOSED
[AXA-AXC configured as ' FDT-4' ]
[FDT-5]
This is the inverted output of [FDT-4].
Output Frequency
I/O-42
AXA-AXC
ON
[AXA-AXC configured as ' FDT-5' ]
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu
[OL]
AXA-AXC is CLOSED when the output current has
reached the FU1-54 [Overload Warning Level] for the
FU1-55 [Overload Warning Time].
I/O-43 / 2
Output Current
FU1-54
Time
[OL level]
ON
Time
FU1-54
[OL level]
AXA-AXC
Related Functions:
[IOL]
I/O-43 / 2
AXA-AXC is CLOSED when the output current is above
the 150% of rated inverter current for 36 seconds. If this
situation is continued for one minute, the inverter will cut
Time
off its output and displays ' IOL' (Inverter overload) Trip.
See the nameplate for the rated inverter current.
Time
Output Current
150% of Rated
Inverter Current
150% of Rated
Inverter Current
AXA-AXC
I/O-43 / 2
Time
ON
Time
130
ON
t1
t1
t1: FU1-55 [Overload Warning Time]
[AXA-AXC configured as ' OL' ]
FU1-54 [Overload Warning Level]
FU1-55 [Overload Warning Time]
ON
36sec
24sec
[AXA-AXC configured as ' IOL' ]
Time
Time
Time
Time