Chapter 6 - Parameter Description [FU2]
This must be set when using an external DB resistor.
The duty is calculated by ' %ED=Decel time * 100 /
(Accel time + Steady speed time + Decel time + Stop
status time)' .
FU2-79: Software Version
FU2? S/W Version
79
Ver X.X
Factory Default:
Ver. X.X
Displays the software version. This will vary depending
on software version integrated.
FU2-81 ~ FU2-90: 2
Motor Related Functions
nd
These functions are displayed only when one of the
multifunction inputs is set at ' 2nd func' in I/O-12 to I/O-14.
When using two motors with an inverter by exchanging
them, different values can be set for the 2
using the multifunction input terminal.
Following table is the 2
functions corresponding to the
nd
1
functions.
st
2
Functions
1
Functions
nd
st
FU2-81
DRV-01
[2nd Acc time]
[Acc. time]
FU2-82
DRV-02
[2nd Dec time]
[Dec. time]
FU2-83
FU1-21
[2nd BaseFreq]
[Base freq]
FU2-84
FU1-29
[2nd V/F]
[V/F Pattern]
FU2-85
FU1-27
[2nd F-boost]
[Fwd Boost]
FU2-86
FU1-28
[2nd R-boost]
[Rev Boost]
FU2-87
FU1-60
[2nd Stall]
[Stall Level]
FU2-88
FU1-51
[2nd ETH 1min]
[ETH 1min]
FU2-88
FU1-52
[2nd ETH cont]
[ETH cont]
FU2-90
FU2-33
[2nd R-Curr]
[Rated-Curr]
The 1
functions are applied if the multifunction terminal
l
st
is not defined to ' 2nd Func' or if it is not ON. The 2
function parameters are applied when the multifunction
input terminal set to ' 2nd Func' is ON. Parameters not
listed on the table above are applied to the 2
to the 1
motor.
st
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu
79
X.X
X.X
motor by
nd
Description
Acceleration time
Deceleration time
Base Frequency
Volts/Hz mode
Forward torque boost
Reverse torque boost
Stall prevention level
ETH level for 1 minute
ETH level for continuous
Motor rated current
nd
motor as
nd
116
Exchange the motor connection from the 1
l
2
motor or the opposite when the motor is stopped.
nd
Over voltage or over current fault can occur when the
motor connection is exchanged during operation.
The ' User V/F' function of FU1-29 [V/F Pattern] is used
l
for both the 1st motor and the 2nd motor.
FU2-91: Parameter Read
FU2-92: Parameter Write
FU2? Para. read
91
---
No ---
Factory Default:
No
FU2? Para. write
92
---
No ---
Factory Default:
No
This is useful for programming multiple inverters to have
same parameter settings. The LCD keypad can read
(upload) the parameter settings from the inverter
memory and can write (download) them to other
inverters. This function is only available with LCD
keypad.
DRV
FU1
F U 2
I / O
E X T
L E - 2 0 0
SHIFT
E S C
PROG
STOP
RUN
E N T
RESET
i S 5
VARIABLE FREQUENCY DRIVE
WARNING
Risk of Injury or Electric Shock
Risk of Electric Shock
Risk of Electric Shock
DRV
FU1
F U 2
I / O
E X T
L E - 2 0 0
SHIFT
E S C
PROG
STOP
RUN
E N T
RESET
i S 5
VARIABLE FREQUENCY DRIVE
WARNING
Risk of Injury or Electric Shock
Risk of Electric Shock
Risk of Electric Shock
motor to the
st
FU2? Para. read
91
---
Yes ---
Parameter Upload
Parameter Download
FU2? Para. write
92
---
Yes ---