FU2? SS P-gain
24
100
Factory Default:
100
FU2? SS I-gain
25
200
Factory Default:
200
This function is used to permit automatic restarting after
Power ON, Fault Reset, and Instant Power Failure
without waiting for the motor to stop.
The speed search gain should be set after considering
the inertia moment (GD
) and magnitude of torque of the
2
load. FU2-37 [Load Inertia] must be set at the correct
value to make this function operate correctly.
FU2-22 [Speed Search Select]
Setting Range
4
bit 3
bit 2
bit 1
bit
th
rd
nd
st
0
0
0
0
Speed search function does not work
0
0
0
1
Speed search during Accelerating
Speed search during a Fault Reset
0
0
1
0
restarting (FU2-21) and Auto
restarting (FU2-26)
Speed search during Instant Power
0
1
0
0
Failure restarting.
Speed search during Power ON
1
0
0
0
starting (FU2-20)
When FU2-22 is set to ' 1111' , Speed Search works for all
conditions.
FU2-22 [Speed Search Selection] selects the speed
search function.
FU2-23 [Current Limit Level] is the current that the
inverter limits its current rise during speed searching.
(The set value is the percentage of FU2-33 [Rated Motor
Current])
FU2-24 [P Gain] is the proportional gain used for speed
search. Set this value according to load inertia set in
FU2-37.
FU2-25 [I Gain] is the Integral gain used for speed
search. Set this value according to load inertia set in
FU2-37.
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu
24
100
100
25
200
200
Description
103
Chapter 6 - Parameter Description [FU2]
Input Power
Input Power loss
Motor Speed
Output Frequency
Output Voltage
[Speed Search Operation]
Related Functions:
FU2-20 [Power ON Start]
FU2-21 [Restart after Fault Reset]
FU2-26 ~ FU2-27 [Auto Restart]
FU2-30 ~ FU2-37 [Motor Parameters]
FU2-26: Number of Auto Restart Attempt
FU2-27: Delay Time Before Auto Restart
FU2?Retry number
26
0
Factory Default:
0
FU2?Retry delay
27
1.0 sec
Factory Default:
1.0 sec
This function is used to allow the inverter to reset itself
for a selected number of times after a fault has occurred.
The inverter can restart itself automatically when a fault
occurs. To use the speed search function during auto
restarting set FU2-22 to ' xx1x' . See FU2-22 ~ FU2-25.
When an under voltage (LV) fault, inverter disable (BX)
Time
Time
Time
Time
26
0
0
27
1.0
1.0