Auto Operation for Dehumidification(only Heating Model)
• The Setting temperature will be same that of the auto operation for cooling.
- Compressor ON temperature; Setting temperature +2°F
- Compressor OFF temperature; Setting temperture -1°F
Intake-air temp.
Setting temp.
Auto Operation for Heating(only Heating Model)
- Compressor ON temperature; Setting temperature
- Compressor OFF temperature; Setting temperature + 6°F
Vertical louver auto operation : During Auto Operation, pressing the chaos swing button makes the horizon-
tal louvers swing up and down automatically.
If you want to stop auto-swing, press chaos swing button again.
5. Healthy Dehumidification
• When the dehumidification operation input by the remote control is received, the intake air temperature is
detected and the setting temp is automatically set according to the intake air temperature.
79°F
Intake Air Temp
75°F
Intake Intake Air Temp<79°F
64°F
Intake Intake Air Temp<75°F
Intake Air Temp<64°F
• While in compressor off, the indoor fan repeats low airflow speed and pause.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification
operation and 4-min compressor off repeat.
Compressor ON Temp.
Compressor OFF Temp.
• In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
below 68°F
68°F
77°F
Intake Air Temp-2°F
Intake Air Temp-1°F
64°F
Setting Temp+1°F
Setting Temp-1°F
Over 68°F~below 70°F
Intake air temperature +1°F
Operation
over 86°F
86°F
Service Manual 39