Anti-Freezing Option 1 (For Split R32 Indoor Unit 5 Series, For Split R410A Unit 4 Series, For Hydrosplit 1-Pipe, For Hydrosplit 2-Pipe) - LG THERMA V HU123MRB Installation Manual

Air-to-water heat pump
Hide thumbs Also See for THERMA V HU123MRB:
Table of Contents

Advertisement

INSTALLER SETTING
238
Anti-Freezing Option 1 (For Split R32 Indoor unit 5 Series, For Split
R410A unit 4 Series, For Hydrosplit 1-Pipe, For Hydrosplit 2-pipe)
This function is to select whether to use Type1 or Type2 to prevent freezing when the remote
control is turned off.
• Change setting values using [<,>(left/right)] button.
CAUTION
!
If the function is set to Type2, there is a risk of freezing.
Function
Detection
Type2 + Inlet
Type1
Water Temp.
Type2
Air Temp.
Value
Type1(Default)
Case
Air Temp. < Certain Level and
Inlet Water Temp. < Certain Level
Air Temp. < Certain Level and
Inlet Water Temp. > Certain Level
Air Temp. > Certain Level and
Inlet Water Temp. > Certain Level
Air Temp. < Certain Level
Air Temp. > Certain Level
Type2
Operation
Pump always ON
Pump intermittently On
Pump always OFF
Pump intermittently On
Pump always OFF