F
MULTI
F
MULTI
MAX
Table 1:
Model Number
Cooling Capacity (Btu/h)
(Min.~Rated~ Max.)
1
Heating Capacity (Btu/h)
(Min.~Rated~ Max.)
1
Continuous Operating Range
Cooling (°F DB)
7
Heating (°F WB)
Operative Operating Range
8
Cooling (°F DB)
7
Heating (°F WB)
Compressor
Inverter Quantity
Oil/Type
Fan (Side Discharge)
Type
Motor Output (W) x Qty.
Motor / Drive
Maximum Air Volume (CFM)
Unit Data
Refrigerant Type
Refrigerant Control/Location
Min. ~ Max. Number Indoor Units/System
Min. ~ Max. Allowable Total IDU Connected
Capacity (Btu/h)
Sound Pressure (Cooling / Heating) dB(A)
Dimensions (W x H x D [inch])
Net / Shipping Unit Weight (lbs.)
Power Supply (V, Phase, Hz)
Power Wiring / Comm. Cable (No. x AWG)
Heat Exchanger
Material and Fin Coating
Rows / Columns/Fins per inch x Qty.
Piping
Liquid Line Connection (in., OD) x Qty.
Vapor Line Connection (in., OD) x Qty.
Factory Charge lbs. of R410A
Piping Lengths
Maximum Total Piping (ft.)
6
Piping Length (No Additional Refrigerant [ft])
Min./Max. Outdoor Unit to Indoor Unit Piping (ft)
Maximum Elevation between ODU and IDU (ft.)
Maximum Elevation between IDU and IDU (ft.)
1
Capacity is rated with non-ducted indoor units, 0 ft. above sea level, with a 0 ft. level
difference between outdoor and indoor units, and the following refrigerant pipe lengths:
LMU183HV: 16.4 ft. x 2 = 32.8 ft.
LMU243HV: 16.4 ft. x 3 = 49.2 ft.
LMU303HV: 16.4 ft. x 4 = 65.6 ft.
LMU363HV: 16.4 ft. x 4 = 65.6 ft.
All capacities are net with a combination ratio between 95 – 105%.
Rated cooling capacity obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF
wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Rated heating capacity obtained with air entering the indoor unit at 70ºF dry bulb (DB) and
60ºF wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
2
At least two indoor units must be connected. For allocated capacity information, see
the combination tables in the "Multi F / Multi F MAX Combination Data Manual" on www.
lghvac.com. For performance data, see "Multi F / Multi F MAX Performance Data Manual"
on www.lghvac.com.
LMU183HV
8,400~18,000~21,600 8,400~24,000~25,000 8,400~30,000~36,000 8,400~32,800~38,400
10,080~22,000~25,000 10,080~24,600~29,000 10,080~32,000~38,400 10,080~36,000~41,600
14 to 118
14 to 122
Twin Rotary x 1
FVC68D
Propeller
85.4 x 1
1,766
R410A
EEV / Outdoor Unit
2~2
2
14,000~24,000
49 / 54
3
34-1/4 x 25-19/32 x 13
101 / 109.8
4C x 14
4,5
(2 x 28 x 14) x 1
1/4 x 2
3/8 x 2
3.97
164.0
98.4
9.8 / 82.0
49.2
24.6
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
GENERAL DATA
LMU243HV
14 to 118
14 to 122
Twin Rotary x 1
FVC68D
Propeller
85.4 x 1
Brushless Digitally Controlled / Direct
1,766
R410A
EEV / Outdoor Unit
EEV/Outdoor Unit
2~3
14,000~33,000
50 / 54
101.4 / 110.2
208 / 230V, 1, 60
4C x 14
Copper Tube/Aluminum Fin and GoldFin™/Hydrophilic
(2 x 28 x 14) x 1
(2 x 38 x 14) x 1
1/4 x 3
3/8 x 3
3.97
230.0
98.4
9.8 / 82.0
49.2
24.6
3
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745 and
are the same in both cooling and heating mode. These values can increase due to ambient
conditions during operation.
4
the applicable local and national codes. For detailed information, please refer to electrical
characteristics on page 10.
All power wiring / communication cable to be minimum 14 AWG, 4-conductor from the
5
outdoor unit to the indoor units, stranded, shielded or unshielded (if shielded, it must be
grounded to the chassis of the outdoor unit only), and must comply with applicable local
and national codes. For detailed electrical information, please refer to electric characteris-
tics on page 10.
Piping lengths are equivalent.
6
7
Operation outside of Continuous Operating Range is subject to safety interruption.
8
LMU303HV
LMU363HV
14 to 118
14 to 118
14 to 122
14 to 122
Twin Rotary x 1
Twin Rotary x 1
FVC68D
FVC68D
Propeller
Propeller
124.2 x 1
124.2 x 1
2,119
2,119
R410A
R410A
EEV/Outdoor Unit
2~4
2~4
14,000~40,000
14,000~48,000
51 / 54
51 / 54
37-13/32 x 32-27/32 x 13
138.9 / 154.3
138.9 / 154.3
4C x 14
4C x 14
(2 x 38 x 14) x 1
1/4 x 4
1/4 x 4
3/8 x 4
3/8 x 4
6.17
6.17
246.1
246.1
98.4
98.4
9.8 / 82.0
9.8 / 82.0
49.2
49.2
24.6
24.6
9