High-Static Motor Connection (For 48K/60K Model)
[Table. 1]
Static Pressure(mmAq)
Model Name Step(Hi/Med/Lo)
LB-C246HSA0
16.5 CMM
LB-C306GTA0
LB-C366GTA0
LB-C428GTA0
26.5 CMM
1. Be sure to set the value refering table 1. Unexpected set value will cause mal-function.
NOTICE
2. Table 1 is based at 230V. According to the fluctuation of voltage, air flow rate varies.
High-Static Motor Connection (For 48K/60K Model)
• If working condition of indoor unit is higher
than that of standard static pressure
(10mmAq) change the Indoor Motor wire
housing for standard motor housing for higher
external static Pressure (15mmAq).
External Static Pressure & Air Flow
Static Pressure(mm Aq)
Model Name
LB-C488ETA0
LB-C608ETA0
1) The above table shows the correlation of External Static Pressure & AIR FLOW.
2) Duct work must be designed within the range of
3) Change the wiring diagram referring to page 23 of manual on condition fo High Static Pressure
(Static pressure 10mmAq
4) If duct work is designed under
applying air damper.
28 Ceiling Duct Type Air Conditioner
0
220
18 CMM
235
14 CMM
250
32 CMM
235
247
29 CMM
254
Step
CMM
High
Med
Low
High
Med
Low
).
External Static Pressure, adjust the External Static Pressure
2
4
Setting Value
205
190
230
220
240
235
230
230
245
245
253
253
0
2
4
CMM
CMM
48.5
46.5
45
43
41.5
39.5
39
37.5
36
56
54
52
49.5
48
46
43.5
42
40.5
on installing the unit.
6
8
50
1(16.5 CMM)
200
100(15 CMM)
230
210
150
1
235
230
250
248
Control box
Wire Color(BK, BL,
RD, OR) For Standard
E.S.P(10mmAq)
Wire Color(YL, BK,
BL, OR) For Higher
E.S.P(15mmAq)
6
8
CMM
CMM
43.5
42
38
36.5
34.5
33
50
48.5
44
42
38.5
37
10
-
-
-
1(29 CMM)
230(27.5 CMM)
240
10
15
CMM
CMM
40
40
35
35
31
30
46
46
40
40.5
35
34