Connecting Pipe To Indoor Unit; Connecting Pipe To Outdoor Unit - LG THERMA V HN0913T Installation Manual

Air-to-water heat pump
Table of Contents

Advertisement

PIPING AND WIRING FOR OUTDOOR UNIT
50
Connecting Pipe to Indoor
Unit
Connecting pipe to the indoor unit is two
steps. Read following directions carefully.
Step 1. Pre-tightening.
- Align the center of the pipes and sufficiently
tighten the flare nut by hand.
Indoor unit tubing
Step 2. Tightening.
- Tighten the flare nut with a wrench.
- Tightening torque is as following.
Torque wrench
Indoor unit tubing
Outside diameter
[mm(inch)]
9.52 (3/8)
15.88 (5/8)
Flare nut
Pipings
Open-end wrench (fixed)
Flare nut
Connection pipe
Torque [kgf·m]
3.4 ~ 4.2
6.6 ~ 8.2
Connecting Pipe to Outdoor
Unit
Connecting pipe to the outdoor unit is five
steps including PCB setting.
Step 1. Determine direction of pipes.
- The pipes can be connectable in three
directions.
- The directions are expressed in below figure.
- When connecting in a downward direction,
knock out the knock-out hole of the base
pan.
- Detailed geometry may vary by model.
Backward
Sideways
Forward
Knock-out
Base pan