hit counter script

Wiring Connections - LG LD187HHV4 Engineering Manual

Single-zone ceiling-concealed ducted lgred system
Table of Contents

Advertisement

ELECTRICAL CONNECTIONS

Wiring Connections

Figure 32: Detailed Power / Communications System Schematic.
L
N
Power Supply
Main Switch
Circuit Breaker
Power Wiring
(Including Ground)
• Power wiring and communications cable sizes must comply with applicable federal UL / ETL, state, and local codes.
• Separately wire the high and low voltage lines to avoid damage to the unit.
• Local codes may require field-installed disconnect switches from outdoor unit to indoor unit.
• Use heat-proof electrical wire capable of withstanding temperatures up to 167°F to avoid damage to unit.
• Always use a circuit breaker or time delay fuse when connecting electrical wiring to the unit.
• Firmly connect the wire. Loose wiring may cause unit malfunction, the wires to burnout or the terminal to overheat and catch fire. There is a
risk of equipment malfunction or property damage.
• Use outdoor and waterproof connection cable rated up to 300V for the connection between the indoor and outdoor unit to avoid damage to
the unit.
• Comply with local codes while running wire from the indoor unit to the outdoor unit.
Do not allow wire to touch refrigerant tubing, the compressor or any moving parts since it can lead to mechanical failure.
40 | DUCTED
G
L
N
Fuse
©
Outdoor Unit
Terminal Block Outdoor
Terminal Block Outdoor
1(L1) 2(L2)
1(L1) 2(L2) 3
Power
Wiring
1(L1) 2(L2)
Terminal Block Indoor
Indoor Unit
Communication
Cable
3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lh248hhv4Lh368hhv4Lh428hhvLh488hhv

Table of Contents