Use the Optional Cover Plate when:
Push down on the tabs to put the wires into the inner holes of their corresponding termi nals on the UWP (one wire per terminal) until they are firmly in place. Gently tug on the wires to verify they are secure. If you need to release the wires again, push down the terminal tabs on the sides of the UWP.
This wiring is just an example, yours may vary.
Conventional Systems | Heat pump systems | ||
Terminal | Description | Terminal | Description |
S/S | Universal input for a wired indoor, outdoor sensor | S/S | Universal input for a wired indoor, outdoor sensor |
Y | Compressor Stage 1 | Y | Compressor Stage 1 |
Y2 | Compressor Stage 2 | Y2 | Compressor Stage 2 |
G | Fan Relay | G | Fan Relay |
C | 24VAC Common wire from secondary side of cooling transformer (if 2 transformers) | C | 24VAC Common wire from secondary side of cooling transformer |
K* | Connect to K on Wire Saver Module | K* | Connect to K on Wire Saver Module |
U/U** | Universal relay for ventilation | U/U** | Universal relay for ventilation |
A | L/A | Connect to compressor monitor | |
W | Heat Stage 1 | O/B | Changeover valve for heat pumps |
W2 | Heat Stage 2 | Aux | Backup Heat |
E | Emergency Heat | ||
R | 24 VAC Heating transformer | R | 24 VAC Heating transformer |
Rc | 24 VAC Cooling transformer | Rc | 24 VAC Cooling transformer |
* The THP9045A1023 Wire Saver Module is used on heat/cool systems when you only have four wires at the thermostat and you need a fifth wire for a common wire. Use the K terminal in place of the Y and G terminals on conventional or heat pump systems to provide control of the fan and the compressor through a single wire—the unused wire then becomes your common wire. See THP9045 instructions for more information.
** Ventilation is not available on all models. When the U slider is in the down position (2 wires), the U contacts are a dry set of contacts. If your ventilation system requires 24 volts, move the U slider to the up position (1 wire). Lower U terminal is internally jumped to the Rc terminal. In this application, you would hook up one wire from your damper to the upper U terminal and the other to the common side of the transformer.
Set R Slider Tab, see Figure 9.
Set U Slider Tab, see Figure 10.
NOTES:
1H/1C System (1 transformer)
R Power
Rc [R+Rc joined by Slider Tab]
Y Compressor contactor
C 24VAC common
W Heat relay
G Fan relay
1H/1C System (2 transformers)
R Power (heating transformer)
Rc Power (cooling transformer)
Y Compressor contactor
C 24 VAC common from cooling transformer
W Heat relay
G Fan relay
2H/2C System (1 transformer)
R Power
Rc [R+Rc joined by Slider Tab]
Y Compressor contactor (stage 1)
C 24VAC common
W Heat relay (stage 1)
G Fan relay
W2 Heat relay (stage 2)
Y2 Compressor contactor (stage 2)
Hot Water Relay Panel
R Power
Rc [R+Rc joined by Slider Tab]
W Heat Relay
C 24VAC common
NOTE: If the panel does not provide 24 volts AC at R and C, set the slider to down position and wire a separate transformer to Rc and C.
Heat-only System with Fan
R Power
Rc [R+Rc joined by Slider Tab]
C 24VAC common
W Heat relay
G Fan relay
Cool-only System with Fan
R Power
Rc [R+Rc joined by Slider Tab]
Y Compressor contactor
C 24VAC common
G Fan relay
1H/1C Heat Pump System
R Power
Rc [R+Rc joined by Slider Tab]
Y Compressor contactor
C 24VAC common
O/B Changeover valve
G Fan relay
2H/1C Heat Pump System
R Power
Rc [R+Rc joined by Slider Tab]
Y Compressor contactor
C 24VAC common
O/B Changeover valve
G Fan relay
Aux Auxiliary heat
E Emergency heat relay
L Heat pump fault input
2H/2C Heat Pump System
R Power
Rc [R+Rc joined by Slider Tab]
Y Compressor contactor (stage 1)
C 24VAC common
O/B Changeover valve
G Fan relay
Y2 Compressor contactor (stage 2)
L Heat pump fault input
3H/2C Heat Pump System
R Power
Rc [R+Rc joined by Slider Tab]
Y Compressor contactor (stage 1)
C 24VAC common
O/B Changeover valve
G Fan relay
Aux Auxiliary heat
E Emergency heat relay
Y2 Compressor contactor (stage 2)
L Heat pump fault input
NOTE: This application is not supported by all models of the thermostat.
NOTE: Ventilation is not available on all models.
Using U Slider Tab
Wired to ERV/HRV whole house ventilator with internal power supply.
Wired to fresh air damper powered by furnace transformer.
NOTES:
View ISU
Edit ISU
Download the Lyric app from App Store or Google Play to use a hidden PRO installation feature that will allow you to configure the thermostat and personally invite your customer to connect to the installed thermostat at the same time.
To enter Contractor Mode, press and hold the Lyric logo for 5 seconds. Then tap Confirm to begin using Contractor Mode. Follow steps to personally invite your customer to connect their Lyric App.
To access the advanced menu, press and hold the Menu button for 5 seconds. Touch or to go through the options in the advanced menu.
Device Setup
This is used to access the device ISU setting.
Screen Lock
The thermostat touch screen can be set to lock fully or partially.
Rater View
A read only place to view all the ventilation settings.
System Test
Test the heating and cooling system.
Range Stop (Temperature)
Set the minimum, maximum, cool and heat temperature set points.
Reset
Access all reset options on the thermostat. This is the only place to access factory reset.
The screen will wake up by pressing the center area of the displayed temperature.
The screen will stay lit for 45 seconds. Brightness can be adjusted in the Menu.
Note: ISU options available may vary upon the thermostat model and equipment setup.
Table 1.
#ISU | ISU Name | ISU Options (defaults in bold) | Notes |
120 | Schedule Type | No Schedule MO-SU = Every day the same MO-FR, SA, SU = 5-1-1 schedule MO-FR, SA-SU = 5-2 schedule Each Day = Every day individual | You can change default MO-FR, SA-SU schedule here. To edit periods during days, temperature setpoints, or to turn Schedule On/Off, from the home screen, go to MENU/SCHEDULE. |
125 | Temp Scale | Fahrenheit, Celsius | |
130 | Outdoor Temp | No, Wired, Internet | Select outdoor temperature data source. This ISU automatically defaults to Internet when registered to Lyric app and no wired outdoor sensor is selected, We recommend using a wired outdoor sensor connected to the "S" terminals on the UWP. (See Wiring') An outdoor temperature is required to set the allowing ISUs: ISU 355 Compressor Lockout, ISU 356 Aux Heat Lockout, ISU 1013 Low Outdoor Temperature Ventilation Lockout, ISU 1014 High Outdoor Temperature Ventilation Lockout, and ISU 1015 High Outdoor Dew Point Ventilation Lockout. |
200 | System Type | Conventional Forced Air Heat Pump Boiler Cool Only | Basic selection of system your thermostat will control. |
205 | Equipment Type | Conventional Forced Air Heat: Standard Gas (STD GAS), High Efficiency Gas (EFF GAS) Oil, Electric, Fan Coil Heat Pump: AirTo Air, Geothermal Boiler: Hot Water, Steam | This option selects the equipment type your thermostat will control, Note: This option is NOT displayed if ISU 200 is set to Cool Only. |
218 | Reversing Valve | 0/B on Cool, 0/B on Heat | This ISU is only displayed if ISU 200 is set to Heat Pump. Select whether reversing valve O/B should energize on cool or on heat |
220 | CoolStages (#200=Conv/ 200-HP) | 0, 1, 2 | |
221 | Heat Stages/Aux/E Stages (#200-Conv./ 200-HP) | Heat Stages: 0,1,2 AUX/E Stages: 0,1 | Maximum of 2 Heat Stages for conventional ystems, Maximum of 1 Aux/E stages for heat pump systems. |
230 | Fan Control | Equipment, Thermostat | This ISU is only displayed if ISU 205 is set to Electric Forced Air or Fan Coil |
253 | Aux/E Control | Both Aux/E, Either Aux/E | Set "EITHER AUX/E" if you want to setup and control Auxiliary and Emergency heating separately. This ISU is only displayed if ISU 200 is set to Heat Pump AND if ISU 221 Aux/E stages = 1 |
255 | Aux Heat Type | Electric, Gas/Oil(or Fossil Forced Ait) | This ISU is displayed only if ISU 200 is set to heat pump AND if ISU 221 Aux/E heat stages = 1 Note: Options of this ISU may vary depending on the model of the thermostat. |
Table 2.
#ISU | ISU Name | ISU Options (defaults in bold) | Notes |
256 | EM Heat Type | Electric, Gas/Oil(or Fossil Forced Air) | This ISU is displayed only if ISU 200 is set to Heat Pump AND if ISU 221 Aux/E heat stages = 1 AND if ISU 253 is set to run AUX/E heat separately. Note: This ISU may not be available at all on some models. |
260 | Fossil Kit Control | Thermostat, External (Fossil Fuel Kit Controls Backup Heat) | This ISU is displayed only if ISU 200 is set to Heat Pump AND if ISU 221 Aux/E heat stages = 1, AND if ISU 256 is set to Gas/Oil. Note: This ISU may not be available at all on some models. |
300 | Auto Changeover | On, Off | OFF: The user must elect heating or cooling as needed to maintain the desired indoor temperature. ON (Automatic): On (enabled) Allows user to select Auto Changeover as one of the system modes from the home screen. In auto mode, the thermostat can control either heating or cooling to maintain the desired indoor temperature. |
303 | Auto Differential | 0°F to 5°F or 0.0°C to 2.5°C | Differentials the minimum number of degrees allowed between the heat and cool setpoints when the thermostatis in auto-changeover. Differential is NOT deadband. The deadband temperature between when heating (or cooling) cycles on and cycles off to maintain setpoint is not adjustable. Honeywell uses an algorithm that fixes deadband at 0°F. This algorithm is more advanced than on previous thermostats. |
305 | High Cool Stage Finish | Yes, No | This ISU is only displayed when the thermostatis set to 2 cool stages. When set to YES, this feature keeps the higher stage of the cooling equipment running until the desired setpoint is reached. |
306 | High Heat Stage Finish | Yes, No | This ISU is only displayed when the thermostats set to 2 or more heat stages. When set to YES, this feature keeps the higher stage of the heating equipment running until the desired setpoint is reached. |
340 | Aux Heat Droop | 0 = Comfort; 2°F to 15°F from setpoint (in 1°F increments) or 1.0°C to 7.5°C from setpoint (in 0.5°C increments) | Aux heat droop can be set on heat pump systems with an auxiliary heat stage. The Comfort setting is NOT available for Dual Fuel systems, Default setting is 0°F (Comfort) for Electric while 2°F for Gas/Oil. The indoor temperature must drop to the selected droop setting before the thermostat wil tum Aux Heat on. For example, if Aux Heat is set to 2°F (1.0°C), the indoor temperature must be 2°F (1.0°C) away from the setpoint before Aux Heat turns on, When set to Comfort, the thermostat will use Aux Heat as needed to keep the indoor temperature within 1°F (0.5°C) degree of the setpoint. |
350 | Up Stage Timer Aux Heat | Off, 30, 45, 60, 75, 90 minutes 2, 3, 4, 5, 6, 8, 10, 12, 14, 16 hours | The Auxiliary Heat Upstage Timer starts when the highest stage of the previous heating equipment type turns on. Auxiliary heat will be used (if needed) when the timer expires. This ISU is only displayed when ISU 340 (AUX Heat Droop) is set to 2°F or higher. |
355 | Balance Point (Compressor Lockout) | Off, 5°F to 60°F (in 5°F increments) or -15.0°C to 15.5°C (in 2.5°C or 3.0°C increments) | Compressor Lockout requires an outdoor temperature. Set Compressor Lockout to the temperature below which itis inefficient to run the heat pump. When outside temperatures below this setting, thermostat will lockout heat pump and run Aux Heat only. This ISU is only displayed if ISU 130 = Wired or Internet, ISU 200 is set to Heat Pump, ISU 221 Aux/E stages = 1, AND ISU 260 is set to Thermostat. We recommend using a wired remote sensor as an outdoor temperature source. Default is 40°F if ISU 205 Heating Equipment is Airto Air Heat Pump and ISU 255 Aux Heat Type is Gas/Oil. Default is Off if ISU 205 Heating Equipment is Air to Air Heat Pump and ISU 255 Aux Heat Type is Electric. Default is Off if ISU 205 Heating Equipment is Geothermal, Compressor Lockout is optional for any type of heat pump (Air to Air Heat Pump, Geothermal Heat Pump). |
Table 3.
#ISU | ISU Name | ISU Options (defaults in bold) | Notes |
356 | Aux Heat Lock Out (Aux Heat Outdoor Lockout) | Off, 5°F to 65°F (in 5°F increments) or -15.0°C to 18.5°C (in 2.5°C of 3.0°C increments) | Aux Heat Lockout requires an outdoor temperature. Set Aux Heat Lockout to optimize energy billsand to not allow itto run the more expensive Aux Heat source above certain outdoor temperature limit. This ISU is only displayed if ISU 200 is set to Heat Pump, AND ISU 260 is set to Thermostat control AND if ISU 221 Aux/E stages = 1. |
365 | Cool 1 CPH (Cooling cycle rate stage 1) | 1-6 CPH (3 CPH) | This ISU is only displayed when Cool Compressor Stages is set to 1 or more stages. Cycle rate limits the maximum number of times the system can cycle in a 1 hour period measured at a 50% load. For example, when set to 3 CPH, at a 50% load, the most the system will cycle is 3 times per hour (1O minutes on, 10 minutes off) The system cycles less often when load conditions are less than or greater than a 50% load. |
366 | Cool 2 CPH (Cooling cycle rate stage 2) | 1-6 CPH (3 CPH) | This ISU is only displayed when Cool/Compressor Stages is set to 2. |
370 | Heat 1 CPH (Heating cycle rate stage 1) | 1-12 CPH | This ISU is only displayed when Heat Stages is set to 1 stage or more stages. Cycle rate limits the maximum number of times the system can cycle in a 1 hour period measured at a 50% load. For example, when set to 3 CPH, at a 50% load, the most the system will cycle is 3 times per hour (1O minutes on, 10 minutes off), The system cycles less often when load conditions are less than or greater than a 50% load. The recommended (default) cycle rate settings are below for each heating equipment type: Standard Efficiency Gas Forced Air = 5 CPH; High Efficiency Gas Forced Air = 3 CPH; Oil Forced Air = 5 CPH; Electric Forced Air = 9 CPH; Fan Coil = 3 CPH; Hot Water Radiant Heat = 3 CPH; Steam = 1 CPH. |
371 | Heat 2 CPH (Heating cycle rate stage 2) | 1-12 CPH | This ISU is only displayed when Heat Stages is set to 2 stages. The recommended (default) cycle rate settings are below foreach heating equipment type: Standard Efficiency Gas Forced Air = 5 CPH; High Efficiency Gas Forced Air= 3 CPH; Oil Forced Air = 5 CPH; Electric Forced Air = 9 CPH; Fan Coil = 3 CPH; Hot Water Radiant Heat = 3 CPH; Steam = 1 CPH. |
375 | Aux Heat CPH (Heating cycle rate Auxiliary Heat) | 1-12 CPH | This ISU is only displayed when ISU 200 = Heat Pump and ISU 221=1. It is only displayed when Auxiliary Heat is configured. The recommended cycle rate settings are below for each heating equipment type: Standard Efficiency Gas Forced Air = 5 CPH; High Efficiency Gas Forced Air= 3 CPH; Oil Forced Air = 5 CPH; Electric Forced Air = 9 CPH. |
378 | EM Heat CPH (Heating cycle rate Emergency Heat) | 1-12 CPH | This ISU is only displayed when Emergency Heat is configured and ISU 253: Aux/E Terminal Control is set to control Aux and E heat Independently. The recommended cycle rate settings are below for each heating equipment type: Standard Efficiency Gas Forced Air = 5 CPH; High Efficiency Gas Forced Air = 3 CPH; Oil Forced Air = 5 CPH; Electric Forced Air = 9 CPH. |
387 | Compressor Protection | Off, 1-5 minutes | The thermostat has a built in compressor protection (minimum off timer) that prevents the compressor from restarting too early after a shutdown, The minimum-off timer is activated after the compressor turns off. If there is a call during the minimum-off timer, the thermostat shows "Wait" in the display. This ISU is displayed if ISU 220 is set to at least 1 stage. |
390 | Ext Fan Run Time in Cool | Off, 30, 60, 90 seconds 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15 minutes | After the call for cooling ends, the thermostat keeps the fan on for the selected amount of time for increased efficiency. This may reintroduce humidity into the living space. This ISU is displayed if ISU 220 is set to at least 1 stage. |
Table 4.
#ISU | ISU Name | ISU Options (defaults in bold) | Notes |
391 | Ext Fan Run Time in Heat | Off, 30, 60, 90 seconds 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15 minutes | After the call for heating ends, the thermostat keeps the fan on for the selected amount of time for increased efficiency. This ISU is displayed if ISU 230 is set to Thermostat Controls Fan. |
425 | Adaptive Recovery | On, Off | Adaptive Intelligent Recovery (AIR) is a comfort setting. Heating or cooling equipment will turn on earlier, ensuring the indoor temperature will match the setpoint at the scheduled time. |
429 | Max Cool Temperature | from Min. Coal Temp. to 99°F or to 37.0°C (90°F or 32°C) | The user cannot set the cooling temperature above this level. |
430 | Min Cool Temperature | from 50°F or 10.0°C to Max. Cool Temp. (50°F or 10°C) | The user cannot set the cooling temperature below this level. |
431 | Max Heat Temperature | from Min. Heat Temp. to 90°F or to 32.0°C (90°F or 32°C) | The user cannot set the heating temperature above this level. |
432 | Min Heat Temperature | from 40°F or 4.4°C to Max. Heat Temp. (50°F or 10°C) | The user cannot set the heating temperature below this level. |
435 | Lock Screen | None, Partial, Full | Unlocked: User has access to all thermostat settings. Partially Locked: User can modify only temperature settings. Fully Locked: User cannot modify any settings, Screen will be locked by default factory code and cannot be changed. This code is displayed for a short time, when you are about to lock the thermostat screen. Please note the code insafe place for future reference. |
500 | Indoor Sensor | Yes, No | Set this ISU when you want to wire a remote indoor sensor to the "S" terminals on the UWP - see "Wiring". This ISU is only displayed only if ISU 130 is set to NO wired outdoor sensor configured. |
515 | Sensor type | 10k, 20k | Choose resistance type of wired indoor sensor. This ISU is only displayed when indoor sensor is configured - ISU 500. |
520 | Temperature Control | Thermostat, Wired, Average | This ISU is only displayed when indoor sensor is configured - ISU 500. You can choose what temperature source to be used or you can ask thermostat to use both thermostat and remote sensors for higher accuracy of measurement. |
702 | Air Filters | 0 - 2 | This ISU refers to the number of air filters in the system. |
711 | Air Filter 1 Reminder | Off 10, 20, 30, 45, 60, 90, 120, 150 Run Time Days 30, 45, 60, 75 Days 3, 4, 5, 6, 9, 12, 15 Months | Choose either calendar or equipment run time-based reminder. |
712 | Air Filter 2 Reminder | Off 10, 20, 30, 45, 60, 90, 120, 150 Run Time Days 30, 45, 60, 75 Days 3, 4, 5, 6, 9, 12, 15 Months | Choose either calendar or equipment run time-based reminder. |
810 | Hum Pad Reminder | Off 6, 12 Calendar Months | |
921 | Dehum Filter Reminder | Off 30, 60 Calendar Days 3 - 12 Calendar Months (in 1 month increments) |
Table 5.
#ISU | ISU Name | ISU Options (defaults in bold) | Notes |
1000 | Vent Type | None, ERV/HRV, Passive, Fresh Air Damper | None: The thermostat does not control ventilation. ERV/HRV: The thermostat controls an Energy Recovery Ventilator or Heat Recovery Ventilator for ventilation. Passive (Fan Only): The thermostat turns on the fan for ventilation. When set to passive fan, the thermostat does not control a damper or ventilator. The passive ventilation/passive fan setting only runs the indoor blower fan. This setting does not open a damper or run a ventilator. To use this setting for ventilation, the home would need to be setup with a pipe from outdoors into the return duct that is either permanently open or has a damper that automatically opens whenever the blower fan is on. Note: Some models only offer the passive fan setting. |
1005 | Vent Method | ASHRAE 2010, ASHRAE 2013, Percent On Time | Note: Options of this ISU may vary depending on the model of the thermostat. |
1006 | Vent Fan Control | Thermostat, Equipment | Thermostat: The thermostat turns on the ventilation and the fan when ventilation is needed. Equipment: Ventilation equipment controls the blower fan. |
1007 | Bedrooms | 1-6 (2) | This ISU is only displayed when ISU 1005 Ventilation Method is set to ASHRAE 2010 or 2013. |
1008 | Home Size | 1000 - 5000 Sq. Ft. (1000 Sq. Ft.) | This ISU is only displayed when ISU 1005 Ventilation Method is set to ASHRAE 2010 or 2013. |
1009 | Vent Rate | 30 - 350 CFM (in 5 CFM increments) (150 CFM) | This ISU is only displayed when ISU 1005 Ventilation Method is set to ASHRAE 2010 or 2013. |
1011 | Vent Percent On Time | 10% - 100% (30%) | The thermostat operates ventilation equipment based on a percentage entered in the installer setup (ISU 1012). For example, if Percent on Time is set to 50%, the ventilation equipment will un at random times during a 1 hour period until it reaches a 50% run time (approximately 30 minutes). This ISU is only displayed if ISU 1005 is set to Percent On Time. |
1012 | Vent Priority | Lockouts, ASHRAE | Lockouts are Priority: The thermostat places a priority on lockouts versus the ASHRAE ventilation standard. The thermostat will not run ventilation during the following lockout conditions (if configured), unless you manually call for ventilation: Lockout Ventilation during Outdoor Conditions (ISU 1013, 1014 and 1015). Lockout Ventilation during "Sleep" program periods. Note: This option is set by the user on the Ventilation screen in the Menu. ASHRAE is Priority: ASHRAE requires additional ventilation following a long off cycle. The thermostat meets the ASHRAE ventilation standard by running additional ventilation when outdoor conditions are favorable, If ASHRAE cannot be met when outdoor conditions are favorable, the thermostat will override the outdoor lockouts and run ventilation. When using this option, it is recommended that you increase the rate (CFM) of the ventilation equipment to meet the ASHRAE ventilation standard in a shorter run time. The ability to lockout ventilation during the "Sleep" is not an option when you select ASHRAE is Priority. |
1013 | Low Outdoor Temp Vent Lockout | Off, -20°F to -40°F (in 5°F increments) or -28.0°C to -4.0°C(in 2.0°C increments) | ISU 130 must be set to Wired or Internet. This ISU is only displayed when ISU 1000 Ventilation Type is set to ERV/HRV or Fresh Air Damper. |
1014 | High Outdoor Temp Vent Lockout | Off, 80°F to 110°F (in 5°F increments) or 26°C to 44°C (in 2°C increments) | ISU 130 must be set to Wired or Internet. This ISU is only displayed when ISU 1000 Ventilation Type is set to ERV/HRV or Fresh Air Damper. |
1015 | High Outdoor Dewpoint Vent | Off, 65°F to 85°F (in 5°F increments) or 18°C to 30°C (in 2°C increments) | ISU 130 must be set to Internet. This ISU is only displayed if ISU 1000 Ventilation Type is set to ERW/HRV or Fresh Air Damper. |
Table 6.
#ISU | ISU Name | ISU Options (defaults in bold) | Notes |
1017 | Vent Core Reminder | Off, 3, 6, 9, 12 months | This ISU is displayed only if ISU 1000 is set to ERV/HRV. |
1018 | Vent Filter Reminder | Off, 3, 6, 9, 12 months | |
1100 | UV Devices | 0 - 2 | Some systems may have two UV devices, one for the A-Coil and another for Air Treatment. A replacement reminder can be setup for each ane separately. |
1105 | UV Bulb 1 Reminder | Off, 6, 12, 24 months | |
1106 | UV Bulb 2 Reminder | Off, 6, 12, 24 months | |
1401 | Idle Brightness | 0 = Off, 0 - 5 | Adjust brightness of an inactive backlight (idle screen) from default 0 (backlight off) to 5 (maximum brightness). |
1410 | Clock Format | 12 hour, 24 hour | |
1415 | Daylight Saving | On, Off | Set to Off in areas that do not follow Daylight Saving Time. |
1420 | Temp Offset | Off, -3°F to 3°F (in 1°F increments) or -1.5°C to 1.5°C (in 0.5°C increments) | 0°F - No difference in displayed temperature and the actual room temperature. The thermostat can display up to 3°F (1.5°C) lower or higher than the actual measured temperature. |
You can test the system setup in ADVANCED MENU under SYSTEM TEST option.
NOTE: The clock is used as a timer while the stages are running. The Heat On and Cool On indicators are displayed when the system test is running.
Alerts and reminders are displayed via the alert symbol and alert number in the clock area on the home screen. You can read more information about active alerts, snooze or dismiss non-critical alerts in Menu/Alerts.
Number | Alert/Reminder | Definition |
164 | Heat Pump Needs Service | Heat pump needs service. Contact dealer to diagnose and service heat pump. |
168 | Wi-Fi Radio Error | Wireless module is not operating. Wireless features are not available. Please contact dealer to replace the thermostat. |
170 | Internal Memory Error | The memory of the thermostat has encountered an error. Please contact dealer for assistance. |
171 | Set the Date and Time | Set the date and time on your thermostat. The date and time are required for certain features to operate, like the program schedule. |
173 | Thermostat Temperature Sensor Error | The sensor of the thermostat has encountered an error. Please contact dealer to replace the Thermostat. |
175 | AC Power Resumed | AC power resumed to thermostat after power loss. |
177 | Indoor Temperature Sensor Error | Wired indoor temperature sensor is not connected or there is a wiring short. Please contact dealer for assistance. |
178 | Outdoor Temperature Sensor Error | Wired outdoor temperature sensor is not connected or there is a wiring short. Please contact dealer for assistance. |
181 | Replace Air Filter (1) | Replace air filter (1). Reset the timer by touching the "dismiss" button on thermostat screen after it is replaced. |
182 | Replace Air Filter (2) | Replace air filter (2). Reset the timer by touching the "dismiss" button on thermostat screen after it is replaced. |
183 | Clean Humidifier Tank and Replace Water Filter | Clean humidifier tank and replace the water filter, or contact dealer to do this for you. Reset the timer by touching the "dismiss" button on the thermostat screen after it is replaced. |
184 | Replace Humidifier Pad | Replace humidifier pad. Reset the timer by touching the "dismiss" button on the thermostat screen after it is replaced. |
185 | Replace Dehumidifier Filter | Replace the dehumidifier filter. Reset the timer by touching "dismiss" button on thermostat screen after it is replaced. |
186 | Clean Ventilator Core | Clean ventilator core. Reset the timer by touching the "dismiss" button on thermostat screen after it is replaced. |
187 | Clean or Replace Ventilator Filter | Clean or replace ventilator filter. Reset the timer by touching the "dismiss" button on thermostat screen after it is replaced. |
188 | Replace UV Bulb (1) | Replace UV Bulb (1). Reset the timer by touching the "dismiss" button on thermostat screen after it is replaced. |
189 | Replace UV Bulb (2) | Replace UV Bulb (2). Reset the timer by touching the "dismiss" button on thermostat screen after it is replaced. |
210 | Register Online For Outdoor Temperature | Online registration is required to receive outdoor temperature from the Internet. Outdoor temperature is needed for your current system setup. Download the Lyric app to register your thermostat. |
388 | Register Online for Remote Access and Outdoor Temperature | Online registration is required for remote access and outdoor temperature. Download the Lyric app to register your thermostat. |
399 | No Internet | The connection to the Internet has been lost. Please check your network settings. |
400 | No Wi-Fi Signal | The Wi-Fi signal has been lost. Please wait for the thermostat to reconnect or select a new Wi-Fi network. Follow steps in the Lyric app |
508 | Wi-Fi Not Configured | Please download the Lyric app and follow the steps to connect thermostat to your Wi-Fi network. |
ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before beginning installation.
EQUIPMENT DAMAGE HAZARD
Compressor protection is bypassed during testing. To prevent equipment damage, avoid cycling the compressor quickly.
MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash. Contact your local waste management authority for instructions regarding recycling and proper disposal.
Temperature Ranges
Heat: 40°F to 90°F (4.5°C to 32.0°C)
Cool: 50°F to 99°F (10.0°C to 37.0°C)
Operating Ambient Temperature
37°F to 102°F (2.8°C to 38.9°C)
Shipping Temperature
-20°F to 120°F (-28.9°C to 48.9°C)
Operating Relative Humidity
5% to 90% (non-condensing)
Physical Dimensions in inches (mm) (H x W x D)
Lyric T6 PRO Wi-Fi Thermostat (TH6320WF2003):
4-5/64 x 4-5/64 x 1-1/16 (104 x 104 x 27)
Lyric T6 PRO Wi-Fi Thermostat (TH6220WF2006):
4-5/64 x 4-5/64 x 1-1/16 (104 x 104 x 27)
UWP Mounting System (THP2600A1009):
2-9/32 x 2-13/64 x 2-43/64 (58 x 56 x 10)
Standard Installation Adapter (THP2400A1076):
3-29/32 x 3-57/64 x 21/32 (99 x 99 x 17)
Decorative Cover Plate – Small (THP2400A1050):
4-49/64 x 4-49/64 x 11/32 (121 x 121 x 9)
Decorative Cover Plate – Large (THP2400A1068):
6-7/64 x 6-7/64 x 9/32 (155 x 155 x 7)
Terminal | Voltage (50/60Hz) | Running Current |
W Heating (Powerpile) | 20-30 Vac 750 mV DC | 0.02-1.0 A 100 mA DC |
W2 (Aux) Heating | 20-30 Vac | 0.02-1.0 A |
E Emergency Heat | 20-30 Vac | 0.02-0.5 A |
Y Compressor Stage 1 | 20-30 Vac | 0.02-1.0 A |
Y2 Compressor Stage 2 | 20-30 Vac | 0.02-1.0 A |
G Fan | 20-30 Vac | 0.02-0.5 A |
O/B Changeover | 20-30 Vac | 0.02-0.5 A |
L/A Input | 20-30 Vac | 0.02-0.5 A |
U Universal | 20-30 Vac | 0.02-0.5 A |
Power Consumption
Backlight On: 1.48VA
Backlight Off: 0.88VA
FCC REGULATIONS
§ 15.19 (a)(3)
This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions:
IC REGULATIONS
RSS-GEN
This device complies with Industry Canada's license-exempt RSSs.
Operation is subject to the following two conditions:
FCC Warning (Part 15.21) (USA only)
Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment.
For Warranty information go to http://customer.honeywell.com
Automation and Control Systems
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
http://customer.honeywell.com
® U.S. Registered Trademark.
© 2016 Honeywell International Inc.
33-00153—07 M.S. Rev. 08-16
Printed in U.S.A.