Concrete Platform Specifications
• Concrete foundations must be made of one part cement, two parts sand, and four parts gravel.
• The surface of the foundation must be finished with mortar with rounded edges, and weatherproofed.
Figure 7: Example of Using an Insert for a Hole
in a Reinforced Concrete Beam.
Suspension Bolt
Concrete Beam
Outdoor Unit Platform Dimensional Requirements
Figure 9: Single Zone Extended Piping Wall Mount Outdoor Units.
Bolting the Outdoor Unit to the Platform
1. Ensure that the concrete platform will not degrade easily, and
has enough structural strength to bear the weight of the unit.
2. Include an H-beam support. Firmly attach the corners, otherwise
the support will bend.
3. Use a hexagon nut.
4. Use anti-vibration material.
5. Include enough space around the concrete foundation for con-
densate drainage.
6. Seal all wiring and piping access holes to prevent insects from
entering the unit.
GENERAL INSTALLATION GUIDELINES
Figure 8: Close up of Bolt Attachment.
Unit: Inch
Polyblock /
Anti-Vibration
Material
Nail Securing
Polyblock
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Anchor Bolt
7/16 (M10)
Table 6:
Model
LSU243HLV3,
LSU303HLV3,
LSU363HLV3
verify that outdoor dimension requirements are met.
Figure 10: Bolting the Outdoor Unit to the Platform (Piping Location Will
Differ Depending on Outdoor Unit Model).
Bolt
Placement
& Anti-Vibration
Pad
Foundation
Outdoor Unit Mounting
Foundation (Inches)
A
B
C
24-13/32 Minimum 4
16
Top of Unit
Piping Connection
Minimum 1
Leg
Thickness
(Inches)
3/32
17