Table 2: Single Zone Extended Pipe Indoor Unit Electrical Data.
Nominal
Unit Model
Hertz Voltage
Tons
Number
2
LS243HLV3
2-1/2
LS303HLV3
60
2-3/4
LS363HLV3
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Voltage Range
MCA
(Min. to Max.)
19.0
208 - 230
187 - 253
23.0
23.0
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Compressor Motor
Compressor
RLA
MOP
Qty.
Cooling Heating
30
1
14.41
30
1
15.1
30
1
15.1
Maximum Overcurrent Protection (MOP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size.
RLA = Rated Load Amps.
FLA = Full Load Amps.
GENERAL DATA
Electrical
Outdoor Fan
Indoor Fan
Motor
W
FLA
W
14.41
124
0.4
58
15.1
124
0.25
110
15.1
124
0.25
110
Motor
FLA
0.5
0.5
0.5
11