Page 1
Repair the product or products dealt with in this service information by anyone else could result in serious injury or death 2018 (Qingdao Haier Air Conditioner General corp. , Ltd) All rights reserved. Unauthorized copying and distribution is a violation of law...
Introduction 1. Introduction 1.1 Model name explanation Apply toT1; 220~240V50HZ/1ph DC inverter Heat pump & R32 refrigerant Version number Europe Platform of outdoor units: 0.8P Platform Nominal cooling capacity (12000BTU/h) Type of outdoor unit : U (normal type) The maximum combination number Domestic air conditioner...
Page 4
Introduction 1.2 Safety Cautions Be sure to read the following safety cautions before conducting repair work. The caution items are classified into “Warning” and “Caution”. The “Warning” items are especially important since they can lead to death or serious injury if they are not followed closely. The “Caution” items can also lead to serious accidents under some conditions if they are not followed.
Page 5
Introduction If the refrigerant gas discharges during the repair work, do not touch the discharging refrigerant gas .The refrigerant gas can cause frostbite. When disconnecting the suction or discharge pipe of the compressor at the welded section, release the refrigerant gas completely at a well-ventilated place first. If there is a gas remaining inside the compressor , the refrigerant gas or cooling machine oil discharges ●...
Page 6
Introduction 1.2.3 Cautions Regarding Products after Repair Warning Be sure to use parts listed in the service parts list of the applicable model and appropriate tools to conduct repair work. Never attempt to modify the equipment. The use of inappropriate parts or tools can cause an electrical shock, excessive heat generation or fire.
Page 7
Introduction stoves and ranges. When replacing the coin battery in the remote controller, be sure to disposed of the old battery to prevent children from swallowing it. If a child swallows the coin battery, see a doctor immediately. Caution Installation of a leakage breaker is necessary in some cases depending on the conditions of the ●...
Page 8
Introduction Caution Check to see if the parts and wires are mounted and connected properly, and if the connections at the soldered or crimped terminals are secure. Improper installation and connections can cause excessive heat generation, fire or an electrical shock. If the installation platform or frame has corroded, replace it.
Specification TECHNICAL SPECIFICATIONS-OTHERS Refrigerant type Refrigerant charge 0.53 Refrigerant Maximum allowable distance circuit between indoor an outdoor Maximum allowable level difference Refrigerant control CAPILLARY liquid 6.35 Piping connections 9.52 (external diameter) drain Heat insulation type Both liquid and Gas pipes Max.
Printed circuit board connector wiring diagram 6. Printed circuit board connector wiring diagram (Control PCB) For 1U35YEGFRA PE COMM L N 4-way valve Bottom heater DC fan motor E-valve Sensor PFC Reactor ● Compressor UNIT MODEL PCB MODEL 1U35YEGFRA 0011800879J...
Page 14
Functions and control Wiring diagrams OUTDOOR UNIT OUTDOOR UNIT WIRING DIAGRAM 0011501311E CONDENSER COMPRESSOR Domestic air conditioner...
Functions and control 7. Functions and control 7.1 Main functions and control specification 7.1.1 The operation frequency of outdoor unit and its control 7.1.1.1 The operation frequency control of compressor The operation frequency scope of compressor Mode Minimum operation frequency Maximum operation frequency Heating 12K 31Hz...
Page 16
Functions and control Wh_c<-2 Max_hz3 99HZ Wh_c<5 Max_hz4 91HZ Wh_c<10 Max_hz5 76HZ Wh_c<17 Max_hz6 69HZ Wh_c<20 Max_hz7 59HZ Wh_c> 20 Max_hz8 45HZ Remarks: The above are the maximum frequency limitations of the complete appliance which are affected by the environment, and they have nothing to do with the ability of the indoor unit. Refrigeration/dehumidification mode: Serial No.
Page 17
Functions and control F-MIN-d(compressor’s Min_hz)< F<F-MAX-d(compressor’s Max_hz) When heating, it is needed to satisfy F-MIN-r (compressor’s Min_hz)< F<F-MAX-r (compressor’s Max_hz) PID control : The innital frequency Sn is determined by Pn . We can calculate Hzoutf according to the value of Kp ,Ki ,Kd, Out_gain,Pn.Then , Fn = Sn + Hzoutf.
Page 18
Functions and control 7.1.4 Four way control For the details of defrosting four-way valve control, see the defrosting process. Four way working in other ways: Under the mode of heating, open the four-way valve, when the compressor is not started or changed to non-heating mode, make sure the compressor is stoped for 2 minutes, and then close the four-way valve.
Page 19
Functions and control (09K) TC( ) The compressor stops Fgh_t1 63 Fgh_t1 2 Fgh_t2 2 N Decreasing the frequency rapidly Fgh_t2 60 P Decreasing the frequency slowly Fgh_t3 57 Fgh_t3 2 Fgh_t4—2 Q Prohibiting increasing the frequency Fgh_t4 52 R Increasing slowly Fgh_t5 40 Fgh_t5—2 Normal...
Page 20
Functions and control the compressor decreases at the speed of 0.1HZ/second. During the starting process of the compressor, if the AC current is greater than 7.5A, the frequency of the compressor increases at the prohibited speed. During the starting process of the compressor, if the AC current is greater than 6.5A, the frequency of the compressor increases at the speed of no faster than 0.1HZ/second.
Page 21
Functions and control modification rate. If during the course of weak magnetic control, the modification rate is still not high enough, enter into the control of decreasing frequency until the alarm of modification rate is relieved. 7.1.5.7 Temperature protection of the outdoor refrigerating coil When the defrosting temperature and the sensor’s temperature are higher than 68 , the frequency of the compressor decreases 1hz/10seconds.
Service diagnosis 10 Service Diagnosis 10.1 Caution for Diagnosis The operation lamp flashes when any of the following errors is detected. 1. When a protection device of the indoor or outdoor unit is activated or when the thermistor malfunctions, disabling equipment operation. 2.
Page 31
Service diagnosis 10.2 Problem Symptoms and Measures Check the power supply. Check to make sure that the rated voltage is supplied. None of the units operates Check the indoor PCB Check to make sure that the indoor PCB is broken Operation A power failure of 2 to 10 cycles can stop air conditioner Check the power supply.
Page 32
Service diagnosis 10.3 Error Codes and Description indoor display Code indication Indoor displaying panel code indication Outdoor Referenc Only For 498 and (LED1 fault description e Page 498A display flash Other display (Red/Green Time Run times) □On★Flash■Off) Indoor Communication fault between ■...
Page 33
Service diagnosis 10.3.1 Thermistor or Related Abnormality Indoor Display E1: Room temperature sensor failure E2: Heat-exchange sensor failure Outdoor display LED1 flash 10 times Defrost temperature sensor failure LED1 flash 11 times Suction temperature sensor failure LED1 flash 12 times Ambient temperature sensor failure LED1 flash 13 times Discharge temperature sensor failure Method of The temperatures detected by the thermistors are used to determine thermistor errors...
Page 34
Service diagnosis 10.3.2 EEPROM abnormal Indoor Display E4: Indoor EEPROM error Indoor display F12: Outdoor EEPROM error; Outdoor LED1 flash 1 times Method of The Data detected by the EEPROM are used to determine MCU Malfunction Detection Malfunction When the data of EEPROM is error or the EEPROM is damaged Decision Conditions Supposed...
Page 35
Service diagnosis 10.3.3 Indoor DC fan motor malfunction Indoor Display Method of The rotation speed detected by the Hall IC during fan motor operation is used to determine Malfunction abnormal fan motor operation Detection Malfunction when the detected rotation feedback signal don’t received in 2 minutes Decision Conditions Supposed...
Page 36
Service diagnosis 10.3.4 Outdoor DC fan motor fault Outdoor display LED1 flash 9 times Method of DC fan motor is detected by checking the fan running condition and so on Malfunction Detection Malfunction when the data of EEPROM is error or the EEPROM is damaged Decision Conditions Supposed...
Page 37
Service diagnosis Domestic air conditioner...
Page 38
Service diagnosis 10.3.5 IPM protection / F1 LED1 flash 2 times Outdoor display: Method of IPM protection is detected by checking the compressor running condition and so on Malfunction Detection Malfunction The system leads to IPM protection due to over current Decision The compressor faulty leads to IPM protection Conditions...
Page 39
Service diagnosis 10.3.6 Over-current of the compressor Outdoor Display: F2 LED1 flash 3 or 24 or 25 times Method of The current of the compressor is too high Malfunction Detection Malfunction when the IPM Module is damaged Decision or the compressor is damaged. Conditions power supply voltage is too low or too high Supposed...
Page 40
Service diagnosis 10.3.7 The communication fault between IPM and outdoor PCB Outdoor display: LED1 flash 4 times Method of Communication is detected by checking the IPM module and the outdoor PCB Malfunction Detection Malfunction The outdoor PCB broken leads to communication fault Decision The IPM module broken leads to communication fault Conditions...
Page 41
Service diagnosis 10.3.8 Power Supply Over or under voltage fault Outdoor display: LED1 flash 6 times The power supply is over voltage Method of An abnormal voltage rise or fall is detected by checking the specified voltage detection circuit. Malfunction Detection Malfunction An voltage signal is fed from the voltage detection circuit to the microcomputer...
Page 42
Service diagnosis 10.3.9 Overheat Protection For Discharge Temperature Outdoor display: F4 LED1 flash 8 times Method of The Discharge temperature control is checked with the temperature being detected Malfunction by the Discharge pipe thermistor Detection Malfunction when the compressor discharge temperature is above 110 Decision Conditions Supposed...
Page 43
Service diagnosis 10.3.10 The communication fault between indoor and outdoor Indoor display outdoor display LED1 flash 15 times Method of Communication is detected by checking the indoor PCB and the outdoor PCB. Malfunction Detection Malfunction The outdoor PCB broken leads to communication fault. Decision The indoor PCB broken leads to communication fault.
Page 44
Service diagnosis If the voltage is a constant value The indoor mainboard is of 0V DC to 5V DC.Or the voltage damaged; replace it with a between Communication line(red ) and N(white new one. line) is not close to18V DC when only indoor charged. Test the outdoor power is Check the cable supply 230VAC with a...
Page 45
Service diagnosis 10.3.11 Loss of synchronism detection Inverter side current detection is abnormal Outdoor Display LED1 flash 18 times LED1 flash 19 times Method of The position of the compressor rotor can not detected normally Malfunction Detection Malfunction when the wiring of compressor is wrong or the connection is poor; Decision or the compressor is damaged Conditions...
Page 46
Service diagnosis 10.3.12 High work-intense protection Outdoor display LED1 flash 21 times Method of High work-intense control is activated in the heating mode if the temperature Malfunction being sensed by the heat exchanger thermistor exceeds the limit. Detection Malfunction Activated when the temperature being sensed by the heat exchanger Decision rises above 65 twices in 30 minutes.
Page 57
Circuit diagrams Sincere Forever Haier Group Edited by : Shi Haiyan Haier Industrial Park, No.1, Haier Road Yang Xiaodong 266101, Qingdao, China_ Signed by : Yang Wenjun Http //www.haier.com Approved by: Wu Hongjin Domestic air conditioner...
Page 58
Repair the product or products dealt with in this service information by anyone else could result in serious injury or death 2015 (Qingdao Haier Air Conditioner General corp. , Ltd) All rights reserved. Unauthorized copying and distribution is a violation of law...
Page 59
Removal Procedure 1.Removal of Outdoor panel...
Page 60
Removal Procedure Domestic Air Condition...
Page 61
Removal Procedure Domestic Air Condition...
Page 62
Removal Procedure 2.Removal of Electrical Box...
Page 63
Removal Procedure 3.Removal of Fan and Fan Motor...
Page 64
Removal Procedure 4.Removal of fan motor brcked and partition...
Page 65
Removal Procedure Domestic Air Condition...
Page 66
Removal Procedure 5.Removal of compressor and heat exchanger...
Page 67
Removal Procedure Domestic Air Condition...