hit counter script

Heating Capacity - LG ASNQ092BRW0 Manual

Inverter single wall mounted r410a(60hz) 6rmi0-05a(replaces 6rmi0-04c)
Table of Contents

Advertisement

Inverter Single
7. Capacity tables

7.2 Heating Capacity

AS-W092HDW0
Indoor Air
Temperature (°C)
-10
°CDB
TC
16.0
2.53
18.0
2.53
20.0
2.53
21.0
2.53
22.0
2.53
24.0
2.50
AS-W092B1U0
Indoor Air
Temperature (°C)
-10
°CDB
TC
16.0
2.53
18.0
2.53
20.0
2.53
21.0
2.53
22.0
2.53
24.0
2.50
AS-W092BRW0, AS-W092B4A0
Indoor Air
Temperature (°C)
-10
°CDB
TC
16.0
2.53
18.0
2.53
20.0
2.53
21.0
2.53
22.0
2.53
24.0
2.50
AS-W122HDW0
Indoor Air
Temperature (°C)
-10
°CDB
TC
16.0
3.17
18.0
3.17
20.0
3.17
21.0
3.17
22.0
3.17
24.0
3.14
Symbol
AFR : Air Flow Rate
DB : Dry Bulb Temperature
WB : Wet Bulb Temperature
TC : Total Capacity
PI : Power Input
(Comp.+ Indoor fan motor + Outdoor fan motor)
Outdoor Air Temperature : °CWB
-5
PI
TC
PI
TC
0.62
2.74
0.65
2.93
0.64
2.75
0.67
2.93
0.65
2.75
0.69
2.92
0.66
2.75
0.70
2.92
0.67
2.75
0.71
2.91
0.69
2.71
0.73
2.88
Outdoor Air Temperature : °CWB
-5
PI
TC
PI
TC
0.56
2.74
0.58
2.93
0.57
2.75
0.60
2.93
0.59
2.75
0.62
2.92
0.59
2.75
0.63
2.92
0.60
2.75
0.63
2.91
0.62
2.71
0.65
2.88
Outdoor Air Temperature : °CWB
-5
PI
TC
PI
TC
0.61
2.74
0.64
2.93
0.63
2.75
0.66
2.93
0.64
2.75
0.68
2.92
0.65
2.75
0.69
2.92
0.66
2.75
0.70
2.91
0.68
2.71
0.72
2.88
Outdoor Air Temperature : °CWB
-5
PI
TC
PI
TC
0.86
3.44
0.90
3.67
0.88
3.44
0.93
3.67
0.90
3.44
0.95
3.66
0.92
3.44
0.96
3.65
0.93
3.44
0.98
3.64
0.95
3.40
1.01
3.61
[m
3
/min]
[°C]
[°C]
[kW]
[kW]
0
6
PI
TC
PI
0.70
3.25
0.75
0.72
3.23
0.76
0.74
3.20
0.78
0.75
3.18
0.79
0.76
3.16
0.79
0.77
3.13
0.81
0
6
PI
TC
PI
0.63
3.25
0.67
0.64
3.23
0.69
0.66
3.20
0.70
0.67
3.18
0.71
0.68
3.16
0.71
0.69
3.13
0.72
0
6
PI
TC
PI
0.69
3.25
0.74
0.71
3.23
0.75
0.73
3.20
0.77
0.74
3.18
0.78
0.75
3.16
0.78
0.76
3.13
0.80
0
6
PI
TC
PI
0.97
4.08
1.03
0.99
4.05
1.06
1.02
4.01
1.08
1.03
3.98
1.09
1.05
3.96
1.10
1.07
3.92
1.12
Notes
1. All capacities are net, evaporator fan motor heat is deducted.
2. Indicates nominal maximum capacity.
3. Direct interpolation is permissible. Do not extrapolate
4. Capacities are based on the following conditions:
- Interconnecting Piping Length 7.5m
- Level Difference of Zero.
- Outdoor air : 85%RH. However, the condition on nominal capacity
is 7°CDB/6°CWB
Inverter Single-60Hz(R410A)
10
15
TC
PI
TC
PI
3.44
0.78
3.73
0.83
3.39
0.79
3.72
0.84
3.37
0.80
3.73
0.84
3.37
0.81
3.70
0.84
3.37
0.81
3.67
0.84
3.31
0.82
3.63
0.85
10
15
TC
PI
TC
PI
3.44
0.70
3.73
0.74
3.39
0.71
3.72
0.75
3.37
0.72
3.73
0.76
3.37
0.73
3.70
0.76
3.37
0.73
3.67
0.76
3.31
0.74
3.63
0.76
10
15
TC
PI
TC
PI
3.44
0.77
3.73
0.82
3.39
0.78
3.72
0.83
3.37
0.79
3.73
0.83
3.37
0.80
3.70
0.83
3.37
0.80
3.67
0.83
3.31
0.81
3.63
0.84
10
15
TC
PI
TC
PI
4.31
1.08
4.67
1.15
4.25
1.10
4.66
1.16
4.23
1.11
4.67
1.17
4.23
1.12
4.64
1.17
4.22
1.13
4.60
1.17
4.15
1.14
4.55
1.18
_ 81