hit counter script

Setting Of ʻSetting_Swʼ - LG V-Net PQDSBNGCM1 Installation Manual

Dry contact module for thermostat
Table of Contents

Advertisement

Setting and using method
3. Setting of ʻSETTING_SWʼ
n Using ʻSETTING_SWʼ , select the Option of control Function
as described below
<SETTING_SW Function>
WIND Signal
No.
en/disable
0
Disable
1
Disable
2
Disable
3
Disable
4
Disable
5
Disable
6
Disable
7
Disable
8
Enable
9
Enable
A
Enable
B
Enable
C
Enable
D
Enable
E
Enable
F
Enable
1) Enable CN_WIND signal – Amount of wind flow (Low, Middle, High) signal enable
2) Enable Thermo ON/OFF input signal
- Desired Temperature 18℃ in cooling mode
- Desired Temperature 30℃ in heating mode
- No function in FAN mode
3) Enable CN_MODE signal – Operation mode (Cool, Heat, Fan) signal enable
4) Enable Thermostat priority control mode – Indoorʼs remote-controller signal will be disregarded
Notes
• Information of ʻSETTING_SWʼ is sensed only initial step by Dry contact module therefore , once the
configuration changed , Reset of Dry contact module is required.
• After power input or unitʼs reset , wait 25~30sec(Display LED 10times blinking) for unit stabilization
then Dry contact module will operate normally.
10 Dry contact Module for thermostat
CN_Ther/Oper
CN_Mode
CHANGEOVERSW
RESET_SW
TEMP_SW
CN_OUT
Thermal
en/disable
Disable
Disable
Disable
Disable
Enable
Enable
Enable
Enable
Disable
1)
Disable
Disable
Disable
Enable
Enable
Enable
Enable
CN_WIND
STEETING_SW
DISPLAY_LED
Oper Mode
en/disable
2)
STEETING_SW
Dry Contact Control
Disable
Disable
Enable
3)
Enable
Disable
Disable
Enable
Enable
Disable
Disable
Enable
Enable
Disable
Disable
Enable
Enable
Priority
Disable
Enable
4)
Disable
Enable
Disable
Enable
Disable
Enable
Disable
Enable
Disable
Enable
Disable
Enable
Disable
Enable

Advertisement