Page 1
DESIGO™ Contents RXB (KNX) Technical manual Selection guide Version 2.37 and higher RXC, RXB, RXL, RXA System overview DESIGO RXB Hardware overview DESIGO RX Data sheets RXB (KNX) Room controllers, Room unit CLC & RAD Chilled ceiling and radiator applications...
Page 3
DESIGO™ RXB (KNX) Technical manual Version 2.37 and higher DESIGO™ RXB (KNX) Technical manual Version 2.37 and higher DESIGO™ RXB (KNX) Technical manual Version 2.37 and higher DESIGO™ RXB (KNX) Technical manual Version 2.37 and higher DESIGO™ RXB (KNX) Technical manual Version 2.37 and higher DESIGO™...
Page 7
Building Automation DESIGO™ ORKS RXC, RXB, RXL, RXA Room automation systems Proprietary Communications Selection guide Non-communicating Flexibility...
Page 8
Communication KNX / EIB ORKS standard standard Room controllers and devices devices accessories from Siemens or third-party manufacturers Identical range of functions in the RAD, CLC, FNC, VAV, FPB applications QAX... Identical room units Principal features The four ranges, RXC, RXB, RXL, and RXA are tailored to the various bus systems...
Page 9
Product scope Communication KNX / EIB Proprietary Applications (HVAC functions) and suitable RAD, CLC, FNC, VAV, RAD, CLC,FNC RAD, CLC,FNC controllers FPB, INT (downloadable) (selected via tool) (selected via tool) (selected via (see page 4 for details) DIP switch) Room units for HVAC operation Electrical controls (lighting, blinds) Conventional switches EIB third-party devices...
Contents Comfort and well-being in every room ................ 5 Range overview ......................6 Coordinated room controllers ..................7 The room units: the key to individual comfort ............8 Applications ......................... 10 Installation........................11 Engineering and commissioning ................12 Integration into building automation and control systems ........15 RXB overview.......................
Comfort and well-being in every room Most people in the industrial world spend 90 % of their time indoors. About one third of this time is spent at work. In this context it is clear that good indoor air quality, the right room temperature and draught- free air renewal are vital prerequisites for motivation and a sense of well-being.
"application") comprising a set of HVAC applications. The application actually required is enabled in the commissioning phase. The Building Automation section of Siemens Building Technologies holds a library of applications, which is continuously being expanded (see Overview, page 10). For the engineering and commissioning of a network of RXB controllers, use is made of...
Coordinated room controllers RXB21.1 and RXB22.1 compact room controllers for fan-coil units The input/output configuration and mounting options of these room controller s makes them ideal for fan coil applications. They can be installed in fan coil units, in control panels or on ducting.
The room units: the key to individual comfort The room units of the RXB range cover the widely varying requirements of individual room occupants. When designing these stylish room units, the designers also paid special attention to ergonomic factors. The HVAC system, lighting and blinds can be operated in various ways: •...
Page 19
Functions of the room units QAX... 30.1 31.1 32.1 33.1 34.1 34.3 39.1 84.1 90.1 91.1 Built-in room temperature sensor Room temperature setpoint adjustment Selection of operating mode ( /Auto) Selection of operating mode ( /Auto) and fan speed LCD display for room temperature, operating mode and fan speed PPS2 interface to RXB room controller...
Applications The scope of the RXB controllers is defined by the pre-programmed application modules. The following is an overview of the various applications and associated controllers. The controllers are shipped from the factory pre-programmed with a set of applications. The required application is then enabled with a tool (ETS3, ACS or the "HandyTool"). Due to the fact that the applications are largely pre-defined, engineering simply involves the definition of a small number of parameters, e.g.: •...
Installation The RXB controllers are designed for various types of installation (mounted with screws or on DIN rail): • In fan coil units • In control panels • In ceiling voids • Under floors • In sill or floor ducting. 01654 Various options for installation Terminal covers are required when mounting the controllers outside control panels or...
Engineering and commissioning The RXB controllers can be operated either as stand-alone controllers or in conjunction with a building automation and control system. They are commissioned with one of the following tools, depending on their intended function: – ETS3 Professional –...
Page 23
Parameter setting For details, please refer to documents CM110384 and CM110385. Communications links For the integration in building automation and control systems, communications links are created by use of group addresses (ETS3).
Page 24
Addressing Every device must have its own physical address. Addresses can be assigned with one of the three tools. Options for connecting the tools Building autometion interface PPS2 PPS2 1. ETS3 or ACS connected to standard room unit *) 2. ETS3 or ACS connected to RXB controller *) 3.
Integration into building automation and control systems BACnet PX KNX 1 PX KNX 2 OCI700 KNX / EIB Backbone Area coupler 2.0.0 KNX Area 2 Line coupler Line coupler 2.3.0 2.7.0 RMH... RMU... RMB795 Bus supply Bus supply Room Room Room supply controllers...
Page 26
Integration into the management level Depending on the degree of complexity required, a management station incorporates the following program modules for the user: • Graphics-based operation of the site (plant graphics) • Time schedules for a wide range of switching routines •...
Page 27
Central and local control of operating mode The diagram below shows an example of how the central time schedules (Building use and Room occupancy) interact with the local /Auto control on the room unit (operating as an occupancy function in this case). It is also possible to use a presence detector for local control.
RXB overview RXB room controllers Document RXB21.1, Room controller for fan-coil units CM2N3873 RXB22.1 RXB24.1 Room controllers for chilled ceilings and radiators CM2N3874 RXB room units QAX30.1 Room unit with temperature sensor CA2N1741 QAX31.1 Room unit with temperature sensor and setpoint adjuster CA2N1741 QAX32.1 Room unit with temperature sensor, setpoint adjuster and...
Page 30
Siemens Schweiz AG Building Technologies Group International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41-724 24 24 Fax +41 41-724 35 22 www.siemens.com/sbt Building Automation Subject to technical change CM110380en_02 • 30.11.2007...
Page 31
DESIGO™ Hardware overview RX Integration Room controllers Room units Field devices Engineering Accessories Integration Engineering Room controllers Room units Field devices Accessories 1/10 Siemens Hardware overview RX CA2N3804en_06 Building Technologies 25 May 2009...
Page 32
Room controllers for fan coil systems, chilled ceilings and radiators CA2N3881 RXA29.1 Room controller for fan coil systems CA2N3882 DESIGO RXB room controllers with EIB bus communications RXB10.1 Room controller in room-style housing for CLC, RAD and VAV systems, supply or extract air (EIB) CA2N3870 RXB21.1...
Page 33
Room unit with temperature sensor (without PPS2, for RXA) CM1N1721 QAA27 Room unit with temperature sensor and setpoint adjustment (without PPS2, for RXA) CM1N1721 BSGN-U1 Universal setpoint adjuster (without PPS2, for RXA) CA1N1985 3/10 Siemens Hardware overview RX CA2N3804en_06 Building Technologies 25 May 2009...
Page 34
As QBM65-.../C, output signal 4 … 20 mA QBM81-... CA1N1552 Differential pressure switch QBM62.1.. (Replaced) CM1N1913 Differential pressure sensor with extracting-the-root characteristic QBM62.2.. (Replaced) CM1N1914 Differential pressure sensor with linear characteristic 4/10 Siemens Hardware overview RX CA2N3804en_06 Building Technologies 25 May 2009...
Page 35
Fixed combination valve + actuator 2W.., 4W.., 5W.. Fixed combination CE1N4846 X Preferred solution o Admitted solution (eventually with restrictions) consider only if X is not feasible. Details see table "Suitable valve actuators" 5/10 Siemens Hardware overview RX CA2N3804en_06 Building Technologies 25 May 2009...
Page 36
M30 x 1.5 VMP43... Small valves CM1N4841 X Preferred solution o Admitted solution (eventually with restrictions) consider only if X is not feasible. Details see table "Suitable valve actuators" 6/10 Siemens Hardware overview RX CA2N3804en_06 Building Technologies 25 May 2009...
Page 37
Technical manual and applications library RXL for CC-02, FC-10, FC-11, FC-12 CM110789 Applications library RXC V1 CA1Z3810 Applications library RXC V2 CA110300 Planning and installation manual RXC V1 CA1Z3800 Planning and installation manual RXC V2 CA110330 7/10 Siemens Hardware overview RX CA2N3804en_06 Building Technologies 25 May 2009...
Page 38
STP71 STP72E 3rd party thermic SQS81 SSA81 SSB81 SSD81 SSC81 SSP81 3rd party motoric Key: Discontinued Default in tool Selectable in tool Not selectable in tool select 3rd party motoric 8/10 Siemens Hardware overview RX CA2N3804en_06 Building Technologies 25 May 2009...
Page 39
(RXA: Only thermic or motoric can be set by means of DIP switches) Selectable in tools (RXA: Only thermic or motoric can be set by means of DIP switches) Not selectable in tools select 3rd party motoric 9/10 Siemens Hardware overview RX CA2N3804en_06 Building Technologies 25 May 2009...
Page 41
RXB21.1 Room controllers RXB22.1 For fan-coil applications FC-10, FC-11, FC12 with Konnex bus communications (S-mode and LTE mode) The RXB21.1 and RXB22.1 room controllers are used for temperature control in individual rooms. For 2-pipe or 4-pipe fan-coil systems, with or without change-over ...
Page 42
For details, refer to the FNC description of functions, document CA110385. When DESIGO RXB controllers are integrated into a building automation and control system, or into a Synco system, additional functions become available such as time scheduling, central control of setpoints, etc.
Page 43
internal relay for electric heating one 3-position actuator coil RXZ20.1 Accessories: Terminal covers Ordering When ordering please specify the quantity, product name, type code and application group. Example: Room controllers, type RXB21.1/FC-10 3/16 Siemens RXB21.1, RXB22.1 Room controllers CM2N3873en_06 Building Technologies 02 Apr 2010...
Page 44
Compatibility The RXB2… room controller is compatible with field devices from Siemens Building Technologies and with KNX / EIB-compatible third-party devices. For details, refer to the DESIGO RX hardware overview, CA2N3804. Design The RXB2... controllers consist of a housing base, a housing cover and the printed circuit board with connection terminals.
Page 45
The conductors must be secured with cable ties (see diagram). Ensure that the power is off before inserting or Warning! removing plug-in terminals connected to a mains voltage. 5/16 Siemens RXB21.1, RXB22.1 Room controllers CM2N3873en_06 Building Technologies 02 Apr 2010...
Page 46
HandyTool QAX34.3 The tool socket is a proprietary socket. Notes A Siemens connecting cable must be used (e.g. PXA-C1). When connected to Ethernet, the device on the other end may be damaged! Caution! The tools ETS3 and ACS, even if connected to a tool socket, require an interface: ...
Page 47
This is acceptable because the two sequences never operate at the same time. With low loads (< 2VA) the voltage tolerance may be greater than +20% (see technical data). 7/16 Siemens RXB21.1, RXB22.1 Room controllers CM2N3873en_06 Building Technologies 02 Apr 2010...
Page 48
Function test A special test mode (ETS3 Professional or "HandyTool") is available for operation of the outputs. Further, if the digital inputs have been activated, they can be interrogated. 8/16 Siemens RXB21.1, RXB22.1 Room controllers CM2N3873en_06 Building Technologies 02 Apr 2010...
Page 49
Inductive load L/R Max. 7 ms Relay type Monostable Contact rating with AC voltage Max. admissible load (resistive only) Max. 1.8 kW External fuse (essential) Max. 10 A 9/16 Siemens RXB21.1, RXB22.1 Room controllers CM2N3873en_06 Building Technologies 02 Apr 2010...
Page 50
Building Services Management Manual – Fundamental principles, and ... – Applications Zentralverband Elektrotechnik- und Elektronikindustrie e.V. (ZVEH) (Central association for the electrical and electronic engineering industry), Stresemannallee 19D-60596 Frankfurt a. M, Germany. 10/16 Siemens RXB21.1, RXB22.1 Room controllers CM2N3873en_06 Building Technologies...
Page 51
1 2 3 4 5 6 7 8 2 KNX / EIB data cable (CE–) 6 RxD 3 Not used 7 PPS2 (CP+) / TxD 4 Not used 8 PPS2 (CP–) 11/16 Siemens RXB21.1, RXB22.1 Room controllers CM2N3873en_06 Building Technologies 02 Apr 2010...
Page 52
1 2 3 4 5 6 7 8 2 KNX / EIB data cable (CE–) 6 RxD 3 Not used 7 PPS2 (CP+) / TxD 4 Not used 8 PPS2 (CP–) 12/16 Siemens RXB21.1, RXB22.1 Room controllers CM2N3873en_06 Building Technologies 02 Apr 2010...
Page 53
For information on the compatibility of field devices with the RXB21.1 and RXB22.1 Note room controller, refer to the various application descriptions (see the FNC description of functions, document CA110385) 13/16 Siemens RXB21.1, RXB22.1 Room controllers CM2N3873en_06 Building Technologies 02 Apr 2010...
Page 54
(max. 2 STA72E / STP72E actuators per Y1 output on the UA1T) Notes – The UA1T requires an AC 24 V supply voltage – The UA1T is not suitable for the connection of 3-position actuators. 14/16 Siemens RXB21.1, RXB22.1 Room controllers CM2N3873en_06 Building Technologies 02 Apr 2010...
Page 55
Dimensions Dimensions in mm Without terminal cover 51,5 With terminal covers 112,4 107,8 15/16 Siemens RXB21.1, RXB22.1 Room controllers CM2N3873en_06 Building Technologies 02 Apr 2010...
Page 57
RXB24.1 Room controller For chilled ceiling and radiator applications CC-02 with Konnex bus communications (S-mode and LTE mode) The RXB24.1 room controller is used for temperature control in individual rooms. For chilled ceiling and radiator systems PI control ...
Page 58
For details, refer to the CLC and RAD description of functions, document CA110384. When DESIGO RXB controllers are integrated into a building automation and control system, or into a Synco system, additional functions become available such as time scheduling, central control of setpoints, etc.
Page 59
Example: Room controllers, type RXB24.1/CC-02 Compatibility The RXB24.1 room controller is compatible with field devices from Siemens Building Technologies and with KNX / EIB-compatible third-party devices. For details, refer to the DESIGO RX hardware overview, CA2N3804. Design The RXB24.1 controller consists of a housing base, a housing cover and the printed circuit board with connection terminals.
Page 60
The cable is connected to the room controller by breaking out the perforated cable entry guide. Removing the terminal cover 4 / 16 Siemens RXB24.1 – Room controller CM2N3874en_04 Building Technologies 02 Apr 2010...
Page 61
KNX / EIB bus (terminals CE+ and CE-) for communication with: PX/KNX interface (to DESIGO INSIGHT) Interface OCI700 (to Synco) Other DESIGO RXB controllers KNX / EIB compatible field devices (e.g. temperature sensor) 5 / 16 Siemens RXB24.1 – Room controller...
Page 62
HandyTool QAX34.3 HandyTool QAX34.3 The tool socket is a proprietary socket. Notes A Siemens connecting cable must be used (e.g. PXA-C1). When connected to Ethernet, the device on the other end may be Caution! damaged! The tools ETS3 and ACS, even if connected to a tool socket, require an interface: ...
Page 63
This is acceptable because the two sequences never operate at the same time. With low loads (< 2VA) the voltage tolerance may be greater than +20% (see technical data). 7 / 16 Siemens RXB24.1 – Room controller CM2N3874en_04 Building Technologies...
Page 64
"Appl." and "Loc" in the commissioning stage. Function test A special test mode (ETS3 Professional and HandyTool) is available for operation of the outputs and interrogation of the inputs. 8 / 16 Siemens RXB24.1 – Room controller CM2N3874en_04 Building Technologies 02 Apr 2010...
Page 65
KNX / EIB (electrically isolated) Transceiver TP-UART 5 mA Bus current Baud rate 9.6 kbit/s Bus topology Refer to KNX / EIB manual (Reference documentation, see next page) 9 / 16 Siemens RXB24.1 – Room controller CM2N3874en_04 Building Technologies 02 Apr 2010...
Page 66
Building Services Management Manual – Applications Zentralverband Elektrotechnik- und Elektronikindustrie e.V. (ZVEH) (Central association for the electrical and electronic engineering industry) Stresemannallee 19D-60596 Frankfurt a. M, Germany. 10 / 16 Siemens RXB24.1 – Room controller CM2N3874en_04 Building Technologies 02 Apr 2010...
Page 67
1 2 3 4 5 6 7 8 2 KNX / EIB data cable (CE–) 6 RxD 3 Not used 7 PPS2 (CP+) / TxD 4 Not used 8 PPS2 (CP–) 11 / 16 Siemens RXB24.1 – Room controller CM2N3874en_04 Building Technologies 02 Apr 2010...
Page 68
For information on the compatibility of field devices with the RXB24.1 room controller, refer to the various application descriptions (see the CLC and RAD description of functions, document CA110384) 12 / 16 Siemens RXB24.1 – Room controller CM2N3874en_04 Building Technologies...
Page 69
(max. 2 STA72E/STP72E actuators per Y1 output on the UA1T) Notes – The UA1T requires an AC 24 V supply voltage – The UA1T is not suitable for the connection of 3-position actuators. 13 / 16 Siemens RXB24.1 – Room controller CM2N3874en_04 Building Technologies 02 Apr 2010...
Page 70
Dimensions Dimensions in mm Without terminal cover 51,5 With terminal covers 112,4 107,8 14 / 16 Siemens RXB24.1 – Room controller CM2N3874en_04 Building Technologies 02 Apr 2010...
Page 73
DESIGO RX QAX34.3 Room unit with PPS2 interface For use with: – Equipment from the RXC, RXB, RXL and RXA (PPS2) ranges – DESIGO PX automation stations – Devices with a PPS2 interface Measurement of the room temperature Bias switch for adjustment of the room temperature setpoint ...
Page 74
LCD panel. The housing and mounting plate are plastic. Opening the housing Index and manufacturing date Siemens QAX34.3 – Room unit with PPS2 interface CM2N1640en_04 Building Technologies 30 Jun 2009...
Page 75
Economy operating mode Automatic fan control Comfort operating mode Automatic fan control Comfort operating mode Manual fan control, fan speed 1 Siemens QAX34.3 – Room unit with PPS2 interface CM2N1640en_04 Building Technologies 30 Jun 2009...
Page 76
Until the controller recognizes the room unit as a PPS2 by controller user, the display reads: Ready for 1 s after recognition by the controller, the room unit is ready for operation operation Siemens QAX34.3 – Room unit with PPS2 interface CM2N1640en_04 Building Technologies 30 Jun 2009...
Page 77
If the room unit is connected to a room controller in the DESIGO RXB, RXL or RXC Displaying the “Wink” function of KNX/EIB range, the display can be used as an aid to commissioning. If the commissioning tool and L...
Page 78
Solid or stranded conductors 0.8 … 2.5 mm Single cable length between controller See installation guides: and room unit DESIGO RXC: CA110334, DESIGO RXB & RXL: CM110381 DESIGO RXA: CA2Z3884 DESIGO PX: CA110396 Cable type 2-core, twisted pair, unscreened Housing protection...
Page 79
PPS2 interface, power supply Device power supply, PPS2 data (positive) CP– Device power supply, PPS2 data (negative) Wiring diagram The example below shows the room unit connected to a DESIGO RXB room controller. PPS2 = Twisted pair QAX34.3 room unit RXB… room controller Siemens QAX34.3 –...
Page 80
Dimensions Dimensions in mm 23,8 89,45 2006 - 2009 Siemens Switzerland Ltd. Subject to change Siemens QAX34.3 – Room unit with PPS2 interface CM2N1640en_04 Building Technologies 30 Jun 2009...
Page 81
CLC and RAD description of functions for CC-02 (CLC and RAD applications: see document CM110671). Related documents CM1Y9775 RXB integration, S-mode. CM1Y9776 RXB / RXL integration – Individual addressing. CM1Y9777 Third-party integration. CM1Y9779 Working with ETS. CM110384en_03 Siemens Building Technologies 28 Feb 2009...
Page 82
Local control of room operating mode via the Temporary Comfort mode input ......................51 5.4.7 Effective room operating mode ..............52 2/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Contents 28 Feb 2009...
Page 83
Window switch (LTE mode) ................ 98 9.2.2 Presence detector (LTE mode)..............98 9.2.3 Dewpoint sensor (LTE mode) ..............98 Peripheral functions ..................99 3/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Contents 28 Feb 2009...
Page 84
Case 6: Separate display, separate schedules .........137 14.7 Case 7: Separate display, shared Synco schedule........138 Working with different tools..............139 4/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Contents 28 Feb 2009...
First edition Copyright This document may be duplicated and distributed only with the express permission of Siemens, and may be passed only to authorized persons or companies with the required technical knowledge. Quality assurance These documents have been prepared with great care.
Swiss headquarters. E-mail: fieldsupport-zug.ch.sbt@siemens.com. Please note that without prejudice to your statutory rights, Siemens accepts no liability for any losses resulting from non-observance or improper observance of the points referred to above.
We recommend the following products: Manufacturer Type Designation Siemens Building Technologies ACX95.320/ALG Power supply 320 mA Siemens Automation and Drives 5WG1 125-1AB01 Power supply 160 mA 5WG1 125-1AB11 Power supply 320 mA 5WG1 125-1AB21 Power supply 640 mA RXB Konnex controller communications The RXB Konnex controllers support communications as defined in the Konnex specification.
• Outside temperature zones. • Heat distribution zones. • Refrigeration distribution zones. For further details, refer to the Konnex specification. 8/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Introduction 28 Feb 2009...
A list of all S-mode communication objects is located in section 12.5; see a detailed description of the Konnex data types in section 12.10. 9/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
Page 90
All communication objects operating in LTE mode are described as follows: communication objects Possible partner function Known partner devices blocks HVACMode 110 HVACS Siemens: HVAC-Mode Scheduler Synco RM700 TimeswitchZone 2) 104 PMC Program to HVAC-Mode Conversion The name of the LTE communication object is entered here.
Refer to the EIB manual for more details. Open the project and select a device. To start parameterization, select Edit, Edit parameters. 11/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Definitions / Tools...
This information can be found in the ACS description. In the ACS Service program, select Plant, Open to open the plant. To start parameterization, select Applications, Parameter settings: 12/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
Major parameterization. – All parameters. Parameters The parameter numbers and their functions are described in the sections below. 13/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Definitions / Tools 28 Feb 2009...
The numbers of the parameters are listed in sections 12.7 and 12.8, and in the descriptions of the functions. A table of parameters with enumerations fort he HandyTool is shown in Section 12.9. 14/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
Page 95
P033 Comfort cooling setpoint. P034 Comfort heating setpoint. P035 Precomfort heating setpoint. P036 Economy heating setpoint. P240 Device status. 15/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Definitions / Tools 28 Feb 2009...
*002 can assume the values 0 … 15. *003 can assume the values 1 … 255. Example: 0.2.27 Each address must be unique within a plant. 16/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Definitions / Tools...
• If the parameter set matches the connected controller, start download (display flashes). • If connected successfully, "P1" is displayed (see 2.5.2). 17/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Definitions / Tools...
% entry. – Motorized actuators open at 100% 1.5 times the runtime, and close at 0% 1.5 times the runtime. 18/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Definitions / Tools...
Page 99
To exit test mode, press >- (Escape) 2 - 3 times (depending on the situation). If no further button is pressed for 5 minutes, the controller automatically reassumes Normal mode and all physical outputs are switched back. 19/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
It can be used for operation in – S-mode. – LTE-mode and S-mode. The send heartbeat and receive timeout are described in section 10.1. 20/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Select communications mode...
Synco device to process the Zone = ---, 1...31 information (e.g. RMU7xx or RMB7xx). 21/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Select communications mode 28 Feb 2009...
Page 102
See also "Master/slave", page 94. Select the menu option Communication. ETS3 Professional 22/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Select communications mode 28 Feb 2009...
Page 103
• If the geogr zone or a TS zone has value = -1 for one of the three values, the entire zone is out of service. 23/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03...
G: 2.2.1 G: 3.7.1 G: 2.1.1 D = Device address, G = Geographical zone (Apartment . Room . Subzone). 24/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Select communications mode 28 Feb 2009...
Page 105
Settings on the control The RMB795 control unit only allows for setting the room group, i.e. the geographical unit zone (apartment). 25/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Select communications mode...
Page 106
Each KNX member requires an individual device address, entered in the floor plan above with D:11x. The device address in our example was assigned based on the bus topology. 26/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
Implementation upon Upon commissioning, enter the settings for the same-name data points in the devices commissioning according to the created list. 27/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Select communications mode...
CLC and RAD applications. • If not 2-pipe fan coil is selected, heating and refrigeration demand is sent simultaneously to generation. 28/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
Alternatively: _Select View, Open Catalog . Select one or several devices, copy them and insert them in the line. Select the application under Commissioning . ACS Service 29/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Applications / Parameters...
The following sections describe how to set parameters, with only slight differences between the two PC tools. The display is the main difference. 30/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
Room operating modes Description The operating modes in DESIGO RXB are Comfort, Precomfort, Economy and Protection. In addition, the controller has a frost Protection limit, at which an alarm can be triggered. Each room operating mode has separately adjustable heating and cooling sequence setpoints.
Overview 32/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes 28 Feb 2009...
The key point in time is the moment at which the state changes (edge). If another source of third priority later changes the state, the last known change is valid . 33/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
R W C T U 0 1 1 0 0 1.019 0 = Closed DPT_WindowDoor 1 = Open 34/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes 28 Feb 2009...
• Priority 3 influences are disabled (schedule occupancy, presence detector, room unit, and Temporary Comfort mode). • Application: Extended building vacancy. 35/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes...
It controls the room operating mode of a room controller while the building is in use. Outside the building-in-use period, it is disabled. 36/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
Page 117
R W C T U 0 1 1 0 0 20.003 0 = Occupied DPT_OccMode 1 = Standby 2 = Unoccupied 37/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes 28 Feb 2009...
Page 118
In the case of integration into a building automation and control system, the data is mapped to the following output communication object: PPS2 38/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes...
• The Effective occupancy or Temporary Comfort mode (both priority 3) can cause the Effective room operating mode to change again last command wins. 39/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
R W C T U 0 1 1 0 0 1.017 1 = Trigger DPT_Trigger 0 = Not used 40/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes 28 Feb 2009...
12.00 and 13.00 ( standby ). • In Room 3, the window is opened briefly once in the morning and once at night (1). 42/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03...
Page 123
• Room 2 is occupied in the evening beyond the building-in-use period (4). However, at the end of the building-in-use period, the room operating mode still changes to Economy. An alarm can be triggered if required. 43/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
Page 124
Protection Presence detector Room 2 Occupied Unoccupied Effective room operating mode Comfort Room 2 Precomfort Economy Protection 44/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes 28 Feb 2009...
The key point in time is the moment at which the state changes (edge). If another source of third priority later changes the state, the last known change is valid . 45/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
R W C T U 0 1 1 0 0 1.019 0 = Closed DPT_WindowDoor 1 = Open 46/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes 28 Feb 2009...
• The Protection room operating mode has priority 1, i.e. presence detector and room units are disabled. 47/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
(see page 102); alternatively an EIB/KNX presence detector connected to the EIB/KNX bus may be used (see diagram below). The two inputs are OR-linked: If one signals presence, presence applies. 48/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
Page 129
R W C T U 1 0 1 1 0 20.003 0 = Occupied DPT_OccMode 1 = Standby 2 = Unoccupied 49/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes 28 Feb 2009...
Auto means: "changes to Auto ". 1) Comfort mode is active for the predefined Temporary Comfort period (see page 103). The room controller then returns to Economy. 50/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
• The Effective occupancy or the room unit (both priority 3) can cause the Effective room operating mode to change again last command wins. 51/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
Page 132
R W C T U 1 0 1 1 0 1.001 0 = Off DPT_Switch 1 = On 52/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes 28 Feb 2009...
Comfort room operating mode is then initiated locally via the room unit (room 1) or presence detector (room 2). 53/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
Page 134
Room without room unit Occupied Presence detector Unoccupied Room 2 Comfort Effective room Precomfort operating mode Room 2 Economy Protection 54/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes 28 Feb 2009...
The key point in time is the moment at which the state changes (edge). If another source of third priority later changes the state, the last known change is valid . 55/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
However, the room controller can be used to force enabling of priority 3 influences via local Comfort mode by ignoring enable Comfort . PPS2 56/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes...
The following LTE-mode communication object is provided for central control: K N X Enable Comfort (input) Possible partner function blocks) Known partner devices EnableComfort 110 HVACS Siemens: HVAC-Mode Scheduler Synco RMB795 Timeswitch zone 104 PMC Programs to HVAC-Mode Conversion Possible states are:...
Auto means: "changes to Auto ". 1) Comfort mode is active for the predefined Temporary Comfort period (see page 103). The room controller then returns to Economy. 59/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
Comfort room operating mode is then initiated locally via the room unit (room 1) or presence detector (room 2). 60/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
Page 141
Occupied Presence Unoccupied detector Room 2 Comfort Precomfort Effective room operating mode Economy Room 2 Protection 61/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes 28 Feb 2009...
If there is no bus connection, the controller assumes the following defaults: • Use = Building in use. • Occupancy = Occupied. 62/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes...
PPS2 The presence detector is connected directly to a digital input of the room controller (see page 102). 63/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes 28 Feb 2009...
The table below shows the effect of the /Auto button on the Effective room operating mode of the room controller. 64/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes...
Comfort (2); when the window is opened (3), after timer expiration (4), or after pressing again the /Auto button (5), the room operating mode returns to Economy . 65/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
Page 146
/ Auto button Auto on room unit Room 3 Comfort Effective room operating mode Room 3 Precomfort Economy Protection. 66/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes 28 Feb 2009...
Bus outputs LTE mode In LTE mode, the current and effective setpoints are not transmitted to the building automation and control system. 68/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Setpoint calculation...
Select the Room Temperature Setpoints tab. ETS3 Professional ACS Service The setpoints can be modified under Room temp setpoints : 69/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Setpoint calculation 28 Feb 2009...
Setpoints heating (input) Setpoints cooling (input) Possible partner Known partner devices function blocks) Siemens: TempRoomSetpSetHeat Siemens SBT proprietary Synco RMB795 TempRoomSetpSetCool Geographical zone Important! Setpoints changed by a tool (e.g. HandyTool) are overwritten by PX-KNX during room STOP controller startup!
LTE-mode, the central setpoint shift is transmitted via the following communication objects (triplets): Setpoint shift heating (input) Setpoint shift cooling (input) Possible partner Known partner devices function blocks) Siemens: TempRoomSetpSetHeatShift 115 HVACOPT Synco RMB795 TempRoomSetpSetCoolShift HVAC Optimizer Geographical zone Local setpoint shift If setpoints are shifted locally and corrected by the controller, local shift is applied.
Page 153
Send heartbeat Value R W C T U 1 0 1 1 0 9.002 Floating point (K) DPT_Value_Tempd 73/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Setpoint calculation 28 Feb 2009...
No sensor No sensor connected. Only measured value Uses the signal, see "analog input B1", page 112. acquisition 74/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Temperature measurement 28 Feb 2009...
7.1.4 Sensor correction The value of the local sensors (PPS2 and B1) can be corrected in the tools (see page 115). 75/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Temperature measurement...
In LTE mode, the room air temperature from directly connected sensors is mapped as follows: Room temperature output (output) Possible partner function Known partner devices blocks) TempRoom 390 UHD Siemens: UserHVACDisplay Synco RMH760 / RMB795 RMU710 / 20 / 30 Geographical zone 76/140 Siemens...
For a Konnex sensor the send heartbeat must be set to "Cyclical sending enabled" Note! STOP Room temperature (input) Possible partner function blocks) Known partner devices TempRoom 321 RTS Siemens: Room Temperature Sensor Synco RMH760 Geographical zone RMU710 / 20 / 30 QAW740 77/140 Siemens...
In LTE mode, the outside temperature is sent in a zone intended specifically for that purpose. Outside temperature input (input) Possible partner function blocks) Known partner devices TempOutside 320 OTS Siemens: Room Temperature Sensor Synco RMH760 Outside temperature RMU710 / 20 / 30 zone RMB795 / RMS705...
The table below shows the possible combinations: Actuator Controller Outputs required type Thermal RXB24.1 Motorized RXB24.1 Electro- RXB24.1 mechanic (ON / OFF) 79/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Control sequences 28 Feb 2009...
Page 160
Parameterization The actuator type used must be defined at the engineering stage: Select Edit parameters, Sequences : ETS3 Professional 80/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Control sequences 28 Feb 2009...
Page 161
This is especially important for fast running actuators. For electromechanic actuators, the actuator running time can be adapted. For fast actuators , select valve type "Motoric 3rd party devices ". 81/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
Page 162
Running time heat surf valve 150 s 0 ... 360 s *064 Offset heating surface valve 0 ... 360 s *066 82/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Control sequences 28 Feb 2009...
ETS3 Professional Note The two fields at the bottom appear only if "LTE and S-mode" is selected in the Communication menu. 83/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Control sequences...
To override the radiator valve actuator, the test mode must be activated via the Note communication object Application mode (see page 105). 84/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Control sequences...
1600 seconds "OPEN" (1s On, 1 s Off) 400 s "CLOSE" (1s On, 19 s Off) The long cycle time ensures that the valves are fully opened and closed. In a network containing several room controllers, the opening of the Siemens thermic actuators is staggered to prevent the heating load from fluctuating.
Page 166
*080 Enable the function The following conditions must be fulfilled: – The room controller must be in Comfort room operating mode. 86/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Control sequences...
(5% – 1 sec ON / 19 sec OFF). Then thus also receive pulses from the controller when closed. 87/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
Cooling surface output (output) Possible partner function blocks Known partner devices ActPosSetpCoolStageA 352 HVA HVAC Valve Actuator Geographical zone 88/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Control sequences 28 Feb 2009...
Page 169
The two fields at the bottom only are shown if "LTE and S-mode" are selected in the Communication menu. ACS Service Select menu item Sequences : 89/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Control sequences...
The example below shows central dewpoint monitoring combined with passive dewpoint monitoring provided by the DESIGO RXB controller. The flow temperature is increased in accordance with a centrally calculated dewpoint temperature. If the dewpoint temperature in the room exceeds the flow temperature, condensation forms and the cooling valve closes.
R W C T U 1 0 1 1 0 1.005 0 = No alarm 1 = Alarm (condensation) DPT_Alarm 91/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Control sequences 28 Feb 2009...
• For CLC02, no electromechanic actuators are permitted due to load. (FNC: 10, 12, Notes • Also, thermal valves cannot run parallel operation of Y1 / Y2 and Y3 / Y4. 92/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
Heating and cooling alternately, with the heating value. Motorized actuators: Heating and cooling valve driven to the heating position. 93/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Control sequences 28 Feb 2009...
The slave controller is controlled by a master controller via the KNX bus. The master and slave controllers operate in parallel. The room temperature is measured only by the master. 94/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
Note You need 4 group addresses (GA1 … GA4) regardless of the number of slaves. Select Master/Slave: ETS3 Professional 95/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Master/slave 28 Feb 2009...
This binding ensures that both controllers react when a dewpoint sensor becomes active. If several slaves are equipped with dewpoint sensors, the correct evaluation is required for the logic block. 96/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
Geogr. zone and M/S zone do not necessarily need to match. In reality, however, it makes sense as seeing which slave belongs to which master is obvious immediately. ACS Service Select Master/Slave: 97/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Master/slave...
For master/slave mode, only the master's presence detector is evaluated without special measures, which also influences the slave controllers. Window switches on the slaves are NOT considered. 98/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
Master Slave RXB... RXB... units with buttons for setpoint shift. Auto QAX33.1 QAX34.1 99/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Master/slave 28 Feb 2009...
Communication or General functions or Central functions . See Section 10.1 10.2 7.1.2 10.3 10.4 10.6 10.8 10.14 100/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies General / central functions 28 Feb 2009...
Page 181
HandyTool General and central functions are set using parameters 117 – 137 (see the individual sections for detailed information). 101/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies General / central functions...
Do not connect the same type of sensor / functions to both digital inputs. Note The controller would ignore the second input. 102/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies General / central functions...
Basic setting *131, *132 0 = Disabled/ Off 0 = Disabled 1 = Enabled / On 103/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies General / central functions 28 Feb 2009...
In LTE mode, the energy demand is determined by two signals: Heat demand heating surface (output) Possible partner function blocks Known partner devices EnergyDemRD 153 RHDTTU Siemens: Radiator Energy Demand Synco RMH760 Distribution zone, Transformer TU RMU710 / 20 / 30...
*) Exit from Test (7) is only possible with the sequence Off (6) + normal mode (0). The following communication object is used in LTE mode: Application mode (input) Possible partner function blocks Known partner devices ContrMode 104 PMC Siemens: Programs to HVAC-Mode Conversion Synco RMB795 Time switch 109 BOS zone Building/Occ-Mode Source...
Precooling (Precool, 5) This function is used to cool rooms to the Comfort cooling setpoint prior to actual occupancy. Y [%] 106/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies General / central functions...
Protection heating setpoint again. When the room temperature rises above the Protection setpoint, the controller reverts to the original application mode (see page 105). 107/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
(communication object Application mode , see page 105). Terminate function The function is disabled via the building automation and control system. 108/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies General / central functions...
0 1 1 0 0 1.003 Yes (fixed 42 hours) 0 = Disabled / Off DPT_Enable 1 = Enabled / On 109/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies General / central functions...
This ensures that the control station does not miss alarms. K N X AlarmInfo_CS (Output) Possible partner function blocks Known partner devices AlarmInfo_CS Siemens Synco RMU710 / 20 / 30, RMH760, RMB795, RMS705 Broadcast AlarmText_CS (Output) Possible partner function blocks...
Free: Bus = 1 = Contact closed Contact closed Contact open Free: Bus = 1 = Contact open Contact open Contact closed 111/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies General / central functions 28 Feb 2009...
Type Send heartbeat States R W C T U 9.001 1 0 1 1 0 DPT_Value_Temp 112/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies General / central functions 28 Feb 2009...
Device state *240 Note In Service mode the device state is always = 0 because the application is not running. 113/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies General / central functions...
Standard display (only room units with LCD) Room temperature *109 Setpoint display (only room units with LCD) Relative *110 114/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room unit 28 Feb 2009...
Page 195
LCD display. Parameter Value HandyTool Temperature unit (Only room units with LCD). *108 Celsius (°C) (basic setting). Fahrenheit (°F) 115/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room unit 28 Feb 2009...
Page 196
If "Absolute setpoint shift" is selected, the LCD displays a scale that illustrates the shift as it happens: 10385Z20 Note To reset the setpoint shift, refer to page 116/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room unit 28 Feb 2009...
After switching on the operating voltage, the controller flashes for 3 to 5 seconds in different patterns. If other patterns appear during normal operation, this indicates an error. 117/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies KNX information...
• Each group address must have a recipient to acknowledge the telegram, otherwise unwanted repeat-telegrams are generated. • Further notes on reducing bus load, see pages 23 and 83. 118/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
– RCCRC Radiator & Chilled Ceiling Room Control – RTS Room Temperature Sensor – ALSrc 1002 Alarm Source 121/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies KNX information 28 Feb 2009...
Running time heat surface valve Offset heating surface valve Outside temp 0% valve pos Outside temp max valve pos Maximum valve pos 122/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies KNX information 28 Feb 2009...
Page 203
Operating system version KNX interface version Device state HandyTool: Visible but not used by the application Handytool: cannot be mapped 123/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies KNX information 28 Feb 2009...
Master/slave zone (subzone) Max valve position Measured value correction Off-delay occupancy detector Offset cooling surface valve Offset heating surface valve 124/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies KNX information 28 Feb 2009...
Page 205
Time switch zone (room) Time switch zone (subzone) HandyTool: Visible but not used by the application HandyTool: cannot be mapped 125/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies KNX information 28 Feb 2009...
Rapid ventilation (earlier: air purge) Reset setpoint offset Night purge Application set Application version Operating system version KNX interface version Device state 126/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies KNX information 28 Feb 2009...
9 = Fan only 10 = Free Cool 11 = Ice 20 = NoDem 255 = NUL Other: reserved 127/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies KNX information 28 Feb 2009...
Page 208
DPT_TempRoom 3 floating point values (16) (16) (16) SetpSetShiftF16[3] - Comfort (3 x EIS5) - Precomfort - Economy 128/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies KNX information 28 Feb 2009...
ACS : CLC01 shows the lower limit of 21°C for the Comfort cooling setpoint. Answer Setpoint data are only updated when the application (RAD01, CLC01, ...) has been selected. 129/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies 28 Feb 2009...
Page 210
The master-controller and slave-controller data is synchronized regularly. If a value changes just after synchronization, it may be a few minutes until it is resynchronized. 130/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03...
Page 211
Example: an RXB controller receives the room temperature from a bus sensor. A bus display is used to display the room temperature. The display must get the signal directly from the bus sensor. 131/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
Synco Synco Geographical zone Geographical zone Time switch zone Heat demand zone Refrigeration demand zone 132/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Integration of RXB in DESIGO/Synco 28 Feb 2009...
• Energy demand: to DESIGO. DESIGO INSIGHT PXC... PXC... PX KNX PXM20 Individual addressing Konnex 133/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Integration of RXB in DESIGO/Synco 28 Feb 2009...
Synco Synco Geographical zone Geographical zone Time switch zone Heat demand zone Refrigeration demand zone 134/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Integration of RXB in DESIGO/Synco 28 Feb 2009...
Synco Synco Geographical zone Geographical zone Time switch zone Heat demand zone Refrigeration demand zone 135/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Integration of RXB in DESIGO/Synco 28 Feb 2009...
Synco Synco Geographical zone Geographical zone Time switch zone Heat demand zone Refrigeration demand zone 136/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Integration of RXB in DESIGO/Synco 28 Feb 2009...
Synco Synco Geographical zone Geographical zone Time switch zone Heat demand zone Refrigeration demand zone 137/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Integration of RXB in DESIGO/Synco 28 Feb 2009...
Synco Synco Geographical zone Geographical zone Time switch zone Heat demand zone Refrigeration demand zone 138/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Integration of RXB in DESIGO/Synco 28 Feb 2009...
An upload is necessary to avoid losing the data from Step 1. The ETS project is missing (no upload possible). The ETS project is NOT updated. 139/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
Page 220
140/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Working with different tools 28 Feb 2009...
Page 221
Related documents CM110384 CLC and RAD functions description for CC-02 CM1Y9775 RXB integration, S-mode. CM1Y9776 RXB / RXL integration – individual addressing. CM1Y9777 Third party integration. CM1Y9779 Working with ETS. CA1N3804 DESIGO RX hardware overview. CM110671en_02 Siemens Building Technologies 14.03.2008...
Page 222
2/16 Siemens RXB application library (KNX) CM110671en_02 Building Technologies CLC & RAD – chilled ceiling and radiator applications from CC-02 14.03.2008...
Page 223
Y [%] 70281 Output signal. Room temperature. Effective heating setpoint Heating sequence. Heating valve. TR [°C] 3/16 Siemens RXB application library (KNX) CM110671en_02 Building Technologies CLC & RAD – chilled ceiling and radiator applications from CC-02 14.03.2008 RAD01 – LTHW radiator...
Page 224
Room units. Versions available with temperature sensor, setpoint shift, /Auto switch and LCD display. Compatible controllers. RAD01 runs on RXB24.1/CC-02 4/16 Siemens RXB application library (KNX) CM110671en_02 Building Technologies CLC & RAD – chilled ceiling and radiator applications from CC-02 14.03.2008...
Page 225
Y1 ... Y4: Max. 9.5 VA each (see data sheet 3874). Note A current list of compatible devices is available in the DESIGO RX hardware overview (N3804). 5/16 Siemens RXB application library (KNX) CM110671en_02 Building Technologies CLC & RAD – chilled ceiling and radiator applications from CC-02 14.03.2008...
Page 226
Master or slave Master Ordering The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. 15 Room controllers, type RXB24.1 with application group CC-02.
Page 227
Y [%] Output signal. Room temperature. Effective cooling setpoint Cooling sequence. Cooling valve. TR [°C] 7/16 Siemens RXB application library (KNX) CM110671en_02 Building Technologies CLC & RAD – chilled ceiling and radiator applications from CC-02 14.03.2008 CLC01 – Chilled ceiling...
Page 228
Room units. Versions available with temperature sensor, setpoint shift, /Auto switch and LCD display. CLC01 runs on RXB24.1/CC-02. Compatible controllers. 8/16 Siemens RXB application library (KNX) CM110671en_02 Building Technologies CLC & RAD – chilled ceiling and radiator applications from CC-02 14.03.2008...
Page 229
Observe the max. simultaneous load on outputs Y1 ... Y4: Max. 9.5 VA each (see data sheet N3874). Note A current list of compatible devices is available in the DESIGO RX hardware overview (N3804). 9/16 Siemens RXB application library (KNX) CM110671en_02 Building Technologies CLC & RAD – chilled ceiling and radiator applications from CC-02 14.03.2008...
Page 230
Master or slave Master Ordering The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. 15 Room controllers, type RXB24.1 with application group CC-02.
Page 231
Effective cooling setpoint Heating sequence. Cooling sequence. Heating valve. Cooling valve. TR [°C] 11/16 Siemens RXB application library (KNX) CM110671en_02 Building Technologies CLC & RAD – chilled ceiling and radiator applications from CC-02 14.03.2008 CLC02 – Chilled ceiling and radiator...
Page 232
Room units. Versions available with temperature sensor, setpoint shift, /Auto switch and LCD display. Compatible controllers. CLC02 runs on RXB24.1/CC-02 12/16 Siemens RXB application library (KNX) CM110671en_02 Building Technologies CLC & RAD – chilled ceiling and radiator applications from CC-02 14.03.2008...
Page 233
Identical devices must not be connected to both inputs. Note A current list of compatible devices is available in the DESIGO RX hardware overview (N3804). 13/16 Siemens RXB application library (KNX) CM110671en_02 Building Technologies CLC & RAD – chilled ceiling and radiator applications from CC-02 14.03.2008...
Page 234
Reset setpoint offset Enabled / Disabled Disabled Master/slave Master/slave Master or slave Master 14/16 Siemens RXB application library (KNX) CM110671en_02 Building Technologies CLC & RAD – chilled ceiling and radiator applications from CC-02 14.03.2008 CLC02 – Chilled ceiling and radiator...
Page 235
Ordering The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. Room controllers, type RXB24.1 with application group CC-02. Example RXB24.1/ CC-02 Note The controllers are delivered with the basic settings shown above.
Page 236
16/16 Siemens RXB application library (KNX) CM110671en_02 Building Technologies CLC & RAD – chilled ceiling and radiator applications from CC-02 14.03.2008 CLC02 – Chilled ceiling and radiator...
Page 237
RXB (KNX) applications library FNC Description of functions for FC-10, FC-11, FC-12 (FNC applications see document CM110672) Supplementary documents CM1Y9775 RXB Integration – S-Mode CM1Y9776 RXB / RXL Integration – Individual Addressing CM1Y9777 3rd Party Integration CM1Y9778 Synco Integration CM1Y9779 Working with ETS CM110385en_05 Building Technologies...
Page 238
Local control of room operating mode with a room unit ......41 5.3.6 Local control of room operating mode via the Temporary Comfort mode input ......................42 2/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
Page 239
8.1.3 Heating/cooling output ................84 8.1.4 Actuator type selection ................85 8.1.5 Values representing valve actuator positions ..........89 3/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Contents 28 Feb 2009...
Page 240
Heating and cooling demand ..............127 11.6 Heating/cooling signal output ..............128 11.7 Special functions ..................128 11.8 Boost heating (Morning Warmup, 2) ............129 4/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Contents 28 Feb 2009...
Page 241
Case 6: Separate display, and separate time schedulers ......163 15.7 Case 7: Separate display, and shared Synco time scheduler ....164 Working with different tools............... 165 5/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
First edition Copyright This document may be duplicated and distributed only with the express permission of Siemens, and may be passed only to authorized persons or companies with the required technical knowledge. Quality assurance These documents have been prepared with great care.
Swiss headquarters. E-mail: fieldsupport-zug.ch.sbt@siemens.com. Please note that without prejudice to your statutory rights, Siemens accepts no liability for any losses resulting from non-observance or improper observance of the points referred to above.
We recommend the following products: Manufacturer Type Designation Siemens Building Technologies ACX95.320/ALG Power supply 320 mA Siemens Automation and Drives 5WG1 125-1AB01 Power supply 160 mA 5WG1 125-1AB11 Power supply 320 mA 5WG1 125-1AB21 Power supply 640 mA RXB Konnex controller communications RXB Konnex controllers support communication as per the Konnex specification.
The timeswitch zone is a "geographical" zone used for special purposes • Outside temperature zones • Heat distribution zones For further details, refer to the Konnex specification. 10/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
Note A list of all S mode communication objects is located in section 13.5; a detailed description of the Konnex data types in section 0. 11/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
Page 248
All communication objects which operate in LE-mode are described as follows: communication objects Possible partner- Known partner devices function blocks HVACMode 110 HVACS Siemens HVAC-Mode Scheduler Synco RM700 Timeswitch zone 2) 104 PMC Program to HVAC-Mode Conversion Enter the name of the LTE communication object here.
Refer to the EIB manual for more details. Open the project and select a device. To start the parameter setting, select Edit, Edit parameters. 13/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
This information can be found in the ACS description. In the ACS Service program, select Plant, Open to open the plant. To start the parameter setting, select Applications, Parameter settings: 14/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
"Extended" parameter – All parameters. setting Parameter The parameter numbers and the functions are described in the sections below. 15/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Definitions / Tools 28 Feb 2009...
The parameter numbers are located in sections 13.7 and 13.8 as well as in the sections Note where the functions are described. A table of parameters with enumerations fort he HandyTool is shown in Section 13.9. 16/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
Page 253
P035 Economy cooling setpoint P036 Economy heating setpoint P038 Min supply air temperature P039 Max supply air temperature P240 Device state 17/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Definitions / Tools...
*003 can be set to a value in the range 1 … 255 e.g. 0.2.27 Each address may occur once only in a given plant. 18/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
Press > (Escape) to return to the storage number and select a different number. • If the parameter set matches the connected controller, start download (display flashes). • If connected successfully, "P1" is displayed (see 2.5.2). 19/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
T 42 (0 = Relay deenergized; 1 = energized). T 43 Relay Q34 (0 = Relay deenergized; 1 = energized). 20/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Definitions / Tools...
Page 257
To exit test mode, press >- (Escape) 2 - 3 times (depending on the situation). If no further button is pressed for 5 minutes, the controller automatically reassumes Normal mode and all physical outputs are switched back. 21/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
It can be used for operation in – S-mode – LTE-mode and S-mode The Send heartbeat and Receive timeout are described in Section 11.1. 22/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
This zone also includes a Synco device to Zone = ---, 1...31 process the information (e.g. RMH7xx or RMB7xx). 23/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Select communication mode...
Page 260
See also "Master/slave", page 117. Select Communication. ETS3 Professional 24/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Select communication mode...
Page 261
• If in the Geogr. zone or in the Time switch zone one of the values is = –1, the entire zone is "Out of service". 25/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12...
D: 109 G: 2.2.1 G: 3.7.1 G: 2.1.1 D = device address, G = geographical zone (Apartment.Room.Subzone) Legend 26/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Select communication mode 28 Feb 2009...
Page 263
– Each room group in the RMB795 central control unit All devices which, together, shall form one room group must be assigned the same apartment number. 27/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
Page 264
Each KNX user requires an individual device address – on the floor plan of the preceding page shown as D:11x. The device addresses in our example were assigned in accordance with the bus’ topology. 28/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
In agreement with the list created, the settings of the data points with the same names are to be made on the devices during commissioning. commissioning 29/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
Notes zones. • If no 2-pipe fan coil is used, heat and refrigeration demand signals are sent simultaneously to the primary plant. 30/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Select communication mode...
Product Finder and insert them in the line. Alternatively: Select View, Open catalog . Select one or several devices, copy and insert them in the line. 31/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
Parameter settings The following chapters describe how to set the parameters, which differs only slightly among the two PC tools. Only the display differs. 32/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
Room operating modes Description The room operating modes available with DESIGO RXB are Comfort, Precomfort, Economy and Protection. In addition, there is a frost protection limit, at which, for example, an alarm can be triggered. Each room operating mode has separately adjustable heating and cooling setpoints.
The key factor is the moment at which the state changes (trigger edge). If the mode is later changed by another source of priority 3, the last change applies . 35/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
R W C T U 0 1 1 0 0 1.019 0 = Closed 1 = Open DPT_WindowDoor 36/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room operating modes 28 Feb 2009...
• Inputs of priority 3 are disabled ( Occupancy time schedule, presence detector, room unit, and Temporary Comfort mode) • Application: Longer periods of non-use of the building 37/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room operating modes...
It controls the room operating mode of a room controller throughout the period when the building is in use. Outside the building-in-use period, it is disabled. 38/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12...
Page 275
R W C T U 0 1 1 0 0 20.003 0 = Occupied DPT_OccMode 1 = Standby 2 = Unoccupied 39/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room operating modes 28 Feb 2009...
Page 276
In the case of integration into a building automation and control system, the data is mapped to the following output communication object: PPS2 40/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
• The Effective occupancy or Temporary Comfort mode (both Priority 3) can cause the effective room operating mode to change again the last command always applies. 41/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
R W C T U 0 1 1 0 0 1.017 1 = Trigger DPT_Trigger 0 = Not used 42/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room operating modes 28 Feb 2009...
12.00 to 13.00 (Standby). • In Room 3 the window is opened briefly, once in the morning and once at night (1). 44/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12...
Page 281
(4). However, at the end of the building-in-use period the room operating mode still changes to Economy mode . An alarm can also be tripped, if required. 45/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12...
The key factor is the moment at which the state changes (trigger edge). If the mode is later changed by another source of priority 3, the last change applies. 47/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
R W C T U 0 1 1 0 0 1.019 0 = Closed DPT_WindowDoor 1 = Open 48/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room operating modes 28 Feb 2009...
Economy are Priority 3 and can therefore later be changed by a presence detector or room unit. • The room operating mode Protection has first priority, and the presence detector and room units are therefore disabled. 49/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
(see page 126); alternatively an EIB/KNX presence detector connected to the EIB/KNX bus may be used (see diagram below). The two inputs are OR-linked: If one signals presence, presence applies. 50/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
Page 287
R W C T U 1 0 1 1 0 20.003 0 = Occupied DPT_OccMode 1 = Standby 2 = Unoccupied 51/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room operating modes 28 Feb 2009...
Auto" means: "Changes to Auto" 1) Comfort mode is operative for the pre-defined Temporary Comfort period (see page 126). The room controller then reverts to Economy. 52/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
• The Effective occupancy or room unit (both Priority 3) can cause the effective room operating mode to change again the last command always applies. 53/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
R W C T U 1 0 1 1 0 1.001 0 = Off DPT_Switch 1 = On 54/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room operating modes 28 Feb 2009...
• Overall, the building is in use from 06.00 to 20.00 ( Protection mode from 20.00 to 06.00 hours). • Rooms 1 and 2 must be available from 08.00 to 18.00 hours (Precomfort) 55/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
Page 292
Room without room unit Presence detector Room 2 Occupied Unoccupied Effective room op. mode Comfort Room 2 Precomfort Economy Protection 56/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room operating modes 28 Feb 2009...
The key factor is the moment at which the state changes (trigger edge). If the mode is later changed by another source of priority 3, the last change applies. 57/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
In the room controller however, the Priority 3 influences can be enabled forcibly, by ignoring the Enable Comfort input (via the parameter Local Comfort mode ). PPS2 58/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room operating modes...
The following LTE-mode communication object is provided for central control: K N X Enable Comfort (input) Possible partner-function blocks Known partner devices EnableComfort 110 HVACS Siemens: HVAC-Mode Scheduler Synco RMB795 Timeswitch zone 104 PMC Programme to HVAC-Mode Conversion The states are:...
Auto means: “changes to Auto” 1) Comfort mode is operative for the pre-defined Temporary Comfort period (see page 126). The room controller then reverts to Economy. 61/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
• Overall, the building is in use from 06.00 to 20.00 (Protection mode from 20.00 to 06.00 hours). • Rooms 1 and 2 must be available from 08.00 to 18.00 hours (Precomfort) 62/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
If there is no bus connection, the controller assumes the following defaults: • Use = Building in use • Occupancy = Occupied 64/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room operating modes...
• The room unit (which is also Priority 3) can cause the effective room operating mode to change again the last command always applies. 65/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
= Unoccupied Auto Precomfort Comfort Economy Auto Comfort during Temporary Comfort period Protection Auto Protection, unchanged 66/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room operating modes 28 Feb 2009...
Comfort (2). It reverts to Economy when the window is opened, (3) when the timer period expires (4), or when the /Auto switch is pressed again (5). 67/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
Page 304
Auto on the room unit Room 3 Comfort Effective room operating mode Room 3 Precomfort Economy Protection 68/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room operating modes 28 Feb 2009...
6.1.3 Bus outputs LTE mode In LTE-mode, the current and effective setpoints are not transmitted to the building automation and control system. 70/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Setpoint calculation...
Select Room temperature setpoints . ETS3 Professional The setpoints can be modified under Room temp setpoints : ACS Service 71/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Setpoint calculation...
Setpoints heating (Input) Setpoints cooling (Input) Possible partner Known partner devices function blocks Siemens: TempRoomSetpSetHeat Siemens SBT proprietary Synco RMB795 TempRoomSetpSetCool Geographical zone Setpoints that have been changed by a tool (e.g. HandyTool) are overwritten by Note! STOP PX-KNX during start-up of the room controller! Central setpoint shift •...
(triplets): Setpoint shift for heating (Input) Setpoint shift for cooling (Input) Possible partner Known partner devices function blocks TempRoomSetpSetHeatShift Siemens: 115 HVACOPT Synco RMB795 TempRoomSetpSetCoolShift HVAC Optimizer Geographical zone Local setpoint shift If setpoints are shifted locally and corrected by the controller, local shift is applied.
Page 311
Send heartbeat Value R W C T U 1 0 1 1 0 9.002 Floating point (K) DPT_Value_Tempd 75/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Setpoint calculation 28 Feb 2009...
Supply air (cascade) Supply air temperature for cascade control. The sensor is automatically configured as a supply air sensor if application FNC08 is selected. 76/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
• In order to determine the average value, the sensor must be configured as a room Notes temperature sensor • The signal is not averaged in the case of return air sensors and KNX sensors. 77/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
1 0 1 1 0 9.001 Floating point (°C) DPT_Value_Temp Note Invalid temperatures are mapped to the bus as 0 °C. 78/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Temperature measurement...
Room temperature output (Output) Possible partner function Known partner devices blocks TempRoom 390 UHD Siemens: UserHVACDisplay Synco RMH760 / RMB795 Geographical zone RMU710 / 20 / 30 Return air temperature output (Output) Possible partner function Known partner devices...
Room temperature (Input) Possible partner function blocks Known partner devices TempRoom 321 RTS Siemens: Room Temperature Sensor Synco RMH760 Geographical zone RMU710 / 20 / 30 QAW740 Return air temperature (Input)
The tool displays the actuators suitable for the selected application. Selection occurs at the engineering stage (see page 85). 81/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12...
Selecting the control The control sequence must be selected when the controller is engineered: sequence Heating only, Cooling only or Changeover. 82/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences...
Page 319
The tool displays the actuators suitable for the selected application. The valve type must be selected at the engineering stage (see page 85). 83/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
The following communication object is used in LTE-mode: H/C changeover (Input) Possible partner function blocks Known partner devices ChangeOverStatusWater 342 WCOS Siemens: Water Changeover Status Sensor Synco RMU710 / 20 / 30 Distribution zone, heating RMB795 / RMS705 Distribution zone, cooling 8.1.3...
The RXB2… room controllers also support the use of motorized EIB/KNX bus KNX/EIB bus actuators actuators. In the tool, select Bus motorized . 85/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
Page 322
The sequence starts after synchronization. Parameterization The actuator type used must be defined at the engineering stage: Select Edit parameters, Sequences : ETS3 Professional 86/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences...
Page 323
This is especially important for fast running actuators. For electromechanic actuators, the actuator running time can be adapted. For fast actuators , select valve type "Motoric 3rd party devices ". 87/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
Page 324
0 ... 360 s *062 Offset heating valve 0 ... 360 s *071 Offset cooling valve 0 ... 360 s *072 88/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences 28 Feb 2009...
Since EIB/KNX bus actuators are available from a variety of manufacturers, the name of their S-mode input communication object varies accordingly. 89/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
Page 326
The two fields at the bottom of the dialog box only appear if "LTE and S-mode" was selected under Communication . Select Sequences . ACS Service 90/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
Heating and cooling alternately, with the Heating value Motorized actuators: Heating and cooling valve driven to the Heating position 91/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences 28 Feb 2009...
Select Sequences . ETS3 Professional 92/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences...
R W C T U 1 0 1 1 0 5.001 0...100% 0 = 0% DPT_Scaling 255 = 100% 93/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences 28 Feb 2009...
Valid Valid The full travel of the damper is 0…100%. The actuator moves to the position defined by the heating value. 94/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences...
Changeover with Change-over disabled electric heater (see page 97) TR [°C] Further details: see sections 8.1.3 through 8.1.7. 96/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences 28 Feb 2009...
R W K T U 0 1 1 0 0 1.003 0 = Disabled DPT_Enable 1 = Enabled 97/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences 28 Feb 2009...
Page 334
See Parameters in the last column of the table below Short name Basic setting Parameter Electric heater Modulating *056 1-step Modulating 98/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences 28 Feb 2009...
Page 335
Select Sequences, Power consumption : ACS Service HandyTool Parameter Short name Basic setting *057 Power consumption el heater 99/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences 28 Feb 2009...
The radiator as an additional heating sequence has its own settings for the valve actuator and runtime. The principles are described in section 8.1.4 . 100/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
Page 337
Running time heat surface valve 150s 0…360 s *064 (motorized actuators) Offset heating surface valve 0 ... 360 s *066 101/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences 28 Feb 2009...
2 bus signals (see 11.5 , Heating and cooling demand ). In S-mode, this demand is summarized in Heating demand room . 8.5.4 Radiator valve actuator override See also section 8.1.7. 102/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences...
The heat output calculated by the controller is achieved as follows: LTHW radiators with The valve is opened to the heat output value [%]. motorized valve actuators 103/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
Page 340
1600 seconds "OPEN" (1s On, 1 s Off) 400 s "CLOSE" (1s On, 19 s Off) The long cycle time ensures that the valves are fully opened and closed. In a network containing several room controllers, the opening of the Siemens thermic actuators is staggered to prevent the heating load from fluctuating.
SpEcm Economizer setpoint = Outdoor temp. min. damper position SpFr Frost protection limit value TO [°C] SpFr SpEmc SpC 105/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences 28 Feb 2009...
1K between the Outside air temp. min. damper pos. setpoint and the cooling setpoint of the effective room operating mode. 106/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12...
1 = Enable = automatic control The following communication object is used in LTE-mode: Enable dampers (Input) Possible partner function blocks Known partner devices 115 HVACOpt Siemens: DisableDamper HVAC-Optimizer Geographical zone The use of the outside-air damper can only be implemented in conjunction with the RXB21.1 controller.
Room controller FNC08 This function is possible in conjunction with motorized valve actuators only . Note! STOP 108/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences 28 Feb 2009...
0.5 °C *038 temperature Maximum supply air 35 °C Comfort cooling setpoint to 40 °C 0.5 °C *039 temperature 109/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences 28 Feb 2009...
Supply air temperature output (Output) Possible partner function Known partner devices blocks TempSupplyAir 390 UHD Siemens: UserHVACDisplay Synco RMH760 / RMB795 Geographical zone RMU710 / 20 / 30 When "supply air " is configured, the controller retrieves this value after a reset.
Heating sequence Cooling sequence 1. Fan speed 3 2. Fan speed 3 3. Fan speed 3 TR [°C] 111/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Fan control 28 Feb 2009...
Page 348
Receive timeout Value R W K T U 0 1 1 0 0 5.001 0...100% DPT_Scaling 255 = 100% 112/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Fan control 28 Feb 2009...
User Fan Speed Setting Geographical zone Fan parameter setting Select Fan control, Fan speeds. ETS3 Professional 9.2.1 9.2.2 7.1.2 9.2.4 9.2.3 113/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Fan control 28 Feb 2009...
Single-speed fan control with relay Q14. 2-speed Two-speed fan control with relays Q14 and Q24. Three-speed fan control with relays Q14, Q24 and Q34. 3-speed 114/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Fan control...
Economy ) is available even if no return air sensor is parameterized. Note! For tool architecture reasons, those time values are visible and settable in ACS and in the HandyTool although not supported by the controller. 115/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
Page 352
Precomfort and Comfort , fan speed 1 is enabled for the minimum runtime and the periodic fan kick starts. • A QAX34.1 room unit displays the value of B1. 116/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
The slave controller is controlled by a master controller via the KNX bus. The master and slave controllers operate in parallel. The room temperature is measured only by the master. 117/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
(Company Specific) Note You need four group addresses (GA1 … GA4) independent of the number of slaves. Select Master/Slave: ETS3 Professional 118/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Master/slave 28 Feb 2009...
This binding ensures that both controllers react when a presence detector becomes active. If several slaves are equipped with presence detectors, the correct evaluation is required for the logic block. 119/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
Geogr. zone und M/S zones need not be the same. However, every day work is easier because you see directly to which master a slave belongs. Select Master/Slave: ACS Service 120/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
For master/slave mode, only the master's presence detector is evaluated without special measures, which also influences the slave controllers. Presence detectors on the slaves are NOT considered. 121/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
Master Slave RXB... RXB... room units with push- buttons for setpoint adjustment. Auto QAX33.1 QAX34.1 122/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Master/slave 28 Feb 2009...
Central functions . See Section 11.1 11.2 11.3 11.4 11.5 11.8 11.10, 11.14 11.16 123/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies General and central functions 28 Feb 2009...
Page 360
We recommend to use this feature. HandyTool The general and central functions are set with parameters 117 – 137. For detailed information, refer to the individual sections. 124/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
HandyTool Parameter Short name Basic setting *128 Receive timeout 60 min Send heartbeat *127 45 min 125/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies General and central functions 28 Feb 2009...
0 ... 90 min 1 min *119 Off-delay occupancy detector 5 min 0 ... 90 min 1 min *120 126/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies General and central functions 28 Feb 2009...
In LTE mode the energy demand is determined by two signals: Heating coil energy demand (Output) Possible partner function blocks Known partner devices EnergyDemAH 154 AHDTTU Siemens: Air Heater Energy Demand Synco RMH760 Distr. zone, heating Transformer TU RMU710 / 20 / 30...
FNC18 generates an additional energy demand signal for the heating surface: Energy demand heating surface (Output) Possible partner function blocks Known partner devices EnergyDemRD 153 RHDTTU Siemens: Radiator Energy Demand Synco RMH760 Distr zone, heating Transformer TU RMU710 / 20 / 30...
This function is used to raise the temperature in a room as quickly as possible to the Precomfort heating setpoint at the end of the night setback period. Objective: Preheat the room for heating. 129/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
Terminating the function – The function is disabled via the building automation and control system. – When the outside air damper is disabled 130/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
– Thermal valves are preheated (see page 86). – The control algorithm but not the complete application is restarted. Limitations Test mode is possible only with S-mode objects! 131/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
Temperature control is switched off and the heating and cooling coils are disabled. Outside air is only introduced if the room temperature is between the Economy heating and Economy cooling setpoints. 132/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
The function must be enabled via the building automation and control system (communication object Application mode , see page 128). Terminating the function The function is disabled via the building automation and control system. 133/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
Here, the device listens on the bus and sends an alarm when it has highest alarm priority. This ensures that the management station does not miss any alarms. AlarmInfo_CS (Output) Possible partner function blocks Known partner devices Siemens AlarmInfo_CS Synco RMU710 / 20 / 30, RMH760, RMB795, RMS705 Broadcast...
May be used freely in applications with single-speed or 2-speed fan, (see page 114). The setting of parameters for unused inputs is described in Section 11.2, page 126. 136/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
1.001 0 = Off (voltage-free) 0 1 1 0 0 DPT_Switch 1 = On (AC 24V) 137/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies General and central functions 28 Feb 2009...
Device state *240 Hinweis In Service mode the device state is always = 0 because the application is not running. 138/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies General and central functions...
Standard display (only room units with LCD) Room temperature *109 Standard display (only room units with LCD) Relative *110 139/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room unit 28 Feb 2009...
Page 376
LCD display. Parameter Value HandyTool Temperature unit (only room units with LCD) *108 Celsius (°C) (basic setting) Fahrenheit (°F) 140/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room unit 28 Feb 2009...
Page 377
If "Absolute setpoint adjustment" is selected, the LCD panel displays a scale which illustrates the adjustment as it happens: 10385Z20 Note To reset the setpoint shift, refer to page 141/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room unit...
• No application selected (see 4.1). flashing • Loading. – Download from ETS3 or ACS. – Room unit QAX34.3 in HandyTool mode. 142/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies KNX information...
• Each group address must have a receiver to acknowledge the telegram, otherwise unwanted repeat-telegrams are generated. • For additional hints for reducing the bus load see pages 25 and 90. 143/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
Room Temperature Sensor – RNATS Return Air Temperature Sensor – FSA Fan Speed Actuator – ALSrc 1002 Alarm Source 146/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies KNX information 28 Feb 2009...
Outside temp min damper pos Running time outside air damper Minimum damper position Outside temp 0% valve pos Outside temp max valve pos 147/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies KNX information...
Page 384
Operating system version KNX interface version Device state HandyTool: In FNC20, runtime damper heating HandyTool: In FNC20, runtime damper cooling 148/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies KNX information 28 Feb 2009...
Heating coil outp bus valve Heating surface output bus valve actuator KNX interface version Local Comfort mode 139, Master/slave 149/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies KNX information 28 Feb 2009...
Page 386
Running time outside air damper Send heartbeat 139, Setpoint display 139, Setpoint offset range 139, Standard display Temperature sensor. 150/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies KNX information 28 Feb 2009...
Page 387
HandyTool: In FNC20, output bus damper actuator HandyTool: Cannot be mapped HandyTool: Visible, but not used by application FNC08: always Supply air 151/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies KNX information...
Rapid ventilation (earlier: air purge) Reset setpoint offset Night purge Application set Application version Operating system version KNX interface version Device state 152/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies KNX information 28 Feb 2009...
Check to make sure that neither the operating booklet nor the plant image is active. Both applications cause a lot of bus traffic and thus slow down reading back parameters. 155/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
Page 392
Answer for LTE mode: Master/slave zones must be identical for master and slave. Create master/slave group addresses and add communication object. Answer for S-mode: 156/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
Page 393
Example: an RXB controller receives the room temperature from a bus sensor. A bus display is used to display the room temperature. The display must get the signal directly from the bus sensor. 157/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
Geographical zone Synco Synco Synco Geographical zone Geographical zone Timeswitch zone Heating demand zone Cooling demand zone 158/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Integrate RXB in DESIGO/Synco 28 Feb 2009...
Konnex Geographical zone Synco Synco Synco Geographical zone Timeswitch zone Heating demand zone Cooling demand zone 160/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Integrate RXB in DESIGO/Synco 28 Feb 2009...
Geographical zone Synco Synco Synco Geographical zone Geographical zone Timeswitch zone Heating demand zone Cooling demand zone 161/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Integrate RXB in DESIGO/Synco 28 Feb 2009...
Geographical zone Synco Synco Synco Geographical zone Geographical zone Timeswitch zone Heating demand zone Cooling demand zone 162/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Integrate RXB in DESIGO/Synco 28 Feb 2009...
Geographical zone Synco Synco Synco Geographical zone Geographical zone Timeswitch zone Heating demand zone Cooling demand zone 163/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Integrate RXB in DESIGO/Synco 28 Feb 2009...
Geographical zone Synco Synco Synco Geographical zone Geographical zone Timeswitch zone Heating demand zone Cooling demand zone 164/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Integrate RXB in DESIGO/Synco 28 Feb 2009...
Page 401
If a controller has been commissioned with ETS in S-Mode and is now being used with ACS in LTE-Mode : You must delete the group addresses separately with ETS; otherwise communication problems may occur. 165/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
Page 402
166/166 Building Technologies RXB application library from V2.36 FNC Description of functions for FC-10, FC-11, FC-12CM110385en_05 – 1BTabl Building Automation 1BTable of contents – Fehler! Formatvorlage nicht definiert. 28 Feb 2009...
Page 403
RXB application library (KNX) FNC – Fancoil applications from FC-10, FC-11, FC-12 (See separate document CM110385 for the FNC description of functions). For RXB... Application Page 21.1 21.1 22.1 Two-pipe fan coil with changeover FNC02 FNC03 Two-pipe fan coil with changeover and electric reheater FNC04 Four-pipe fan coil FNC05...
Page 404
2/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies 30.11.2007...
Page 405
Heating sequence. Cooling sequence. Heating/cooling valve. Fan speed 1. Fan speed 2. Fan speed 3. TR [°C] 3/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC02 – Two-pipe fan coil with changeover 30.11.2007...
Page 406
/Auto and fan speed control, and LCD display. Compatible controllers. FNC02 is supplied with RXB21.1/FC-10. 4/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC02 – Two-pipe fan coil with changeover...
Page 407
Do not connect the fans in parallel (or use cut-off relays). Note A current list of compatible devices is available in the DESIGO RX hardware overview (N3804). 5/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC02 –...
Page 408
Enabled / Disabled Enabled Reset setpoint offset Enabled / Disabled Disabled Master/slave Master/slave Master or slave Master 6/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC02 – Two-pipe fan coil with changeover 30.11.2007...
Page 409
Ordering The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. Room controllers RXB21.1 with application group FC-10 RXB21.1/FC-10 Example Note The controllers are delivered with the basic settings shown above.
Page 410
8/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC02 – Two-pipe fan coil with changeover 30.11.2007...
Page 411
Contactor or solid state relay for electric heating TR [°C] TR [°C] coil. 9/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC03 – Two-pipe fan coil with changeover and electric reheater 30.11.2007...
Page 412
/Auto and fan speed control, and LCD display. Compatible controllers. FNC03 is supplied with RXB22.1/FC-12. 10/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC03 – Two-pipe fan coil with changeover and electric reheater...
Page 413
7) External fuse, max. 10 A (protects pcb tracks). Note A current list of compatible devices is available in the DESIGO RX hardware overview (N3804). 11/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC03 –...
Page 414
5 min On-delay occupancy detector 0 ... 90 min 5 min Off-delay presence detector 12/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC03 – Two-pipe fan coil with changeover and electric reheater...
Page 415
Master or slave Master Ordering The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. Room controllers RXB22.1 with application group FC-12 RXB22.1/FC-12 Example Note The controllers are delivered with the basic settings shown above.
Page 416
14/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC03 – Two-pipe fan coil with changeover and electric reheater 30.11.2007...
Page 417
Heating sequence. Cooling sequence. Heating valve. Cooling valve. Fan speed 1. TR [°C] Fan speed 2. Fan speed 3. 15/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC04 – Four-pipe fan coil 30.11.2007...
Page 418
Available with temperature sensor, setpoint adjuster, button for /Auto and fan speed control, and LCD display. Compatible controllers. FNC04 is supplied with RXB21.1/FC-10. 16/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC04 – Four-pipe fan coil...
Page 419
Do not connect the fans in parallel (or use cut-off relays). Note A current list of compatible devices is available in the DESIGO RX hardware overview (N3804). 17/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC04 –...
Page 421
Ordering The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. Room controllers RXB21.1 with application group FC-10 RXB21.1/FC-10 Example Note The controllers are delivered with the basic settings shown above.
Page 422
20/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC04 – Four-pipe fan coil 30.11.2007...
Page 423
Safety thermostat electric reheater. Fan (1… 3-speed). Heating valve. Cooling valve. K N X Electric reheater. 21/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC05 – Four-pipe fan coil with electric reheater 30.11.2007...
Page 424
Effective cooling setpoint. Heating sequence. Cooling sequence. Fan speed 1. Fan speed 2. Fan speed 3. 22/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC05 – Four-pipe fan coil with electric reheater 30.11.2007...
Page 425
/Auto and fan speed control, and LCD display. Compatible controllers. FNC05 is supplied with RXB22.1/FC-12. 23/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC05 – Four-pipe fan coil with electric reheater...
Page 426
7) External fuse, max. 10 A (protects pcb tracks). Note A current list of compatible devices is available in the DESIGO RX hardware overview (N3804). 24/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC05 –...
Page 427
Enabled / Disabled Enabled Reset setpoint offset Enabled / Disabled Disabled Master/slave Master/slave Master or slave Master 25/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC05 – Four-pipe fan coil with electric reheater 30.11.2007...
Page 428
Ordering The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. Room controllers RXB22.1 with application group FC-12 RXB22.1/FC-12 Example Note The controllers are delivered with the basic settings shown above.
Page 429
Cooling valve. Fan speed 1. Fan speed 2. TR [°C] Fan speed 3. 27/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC08 – Four-pipe fan coil with room supply air cascade 30.11.2007...
Page 430
/Auto and fan speed control, and LCD display. Compatible controllers. FNC08 is supplied with RXB21.1/FC-10. 28/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC08 – Four-pipe fan coil with room supply air cascade...
Page 431
4) Do not connect the fans in parallel (or use cut-off relays). Note A current list of compatible devices is available in the DESIGO RX hardware overview (N3804). 29/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC08 –...
Page 432
Master or slave Master Ordering The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. Room controllers RXB21.1 with application group FC-10 RXB21.1/FC-10 Example Note The controllers are delivered with the basic settings shown above.
Page 433
Outside air damper. Fan speed 1. Fan speed 2. Fan speed 3. TR [°C] 31/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC10 – Two-pipe fan coil with changeover and outside air damper...
Page 434
/Auto and fan speed control, and LCD display. Compatible controllers. FNC10 is supplied with RXB21.1/FC-11. 32/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies – Two-pipe fan coil with changeover and outside air damper...
Page 435
4) Do not connect the fans in parallel (or use cut-off relays). Note A current list of compatible devices is available in the DESIGO RX hardware overview (N3804). 33/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies –...
Page 436
0 ... 90 min 5 min 0 ... 90 min 5 min Off-delay presence detector 34/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies – Two-pipe fan coil with changeover and outside air damper...
Page 437
Master or slave Master Ordering The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. Room controllers RXB21.1 with application group FC-11 RXB21.1/FC-11 Example Note The controllers are delivered with the basic settings shown above.
Page 438
36/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies – Two-pipe fan coil with changeover and outside air damper 30.11.2007...
Page 439
Outside air damper. Fan speed 1. Fan speed 2. Fan speed 3. TR [°C] 37/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC12 – Four-pipe fan coil with outside air damper 30.11.2007...
Page 440
/Auto and fan speed control, and LCD display. Compatible controllers. FNC12 is supplied with RXB21.1/FC-11. 38/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC12 – Four-pipe fan coil with outside air damper...
Page 441
4) Do not connect the fans in parallel (or use cut-off relays). Note A current list of compatible devices is available in the DESIGO RX hardware overview (N3804). 39/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC12 –...
Page 442
Enabled Reset setpoint offset Enabled / Disabled Disabled Master/slave Master/slave Master or slave Master 40/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC12 – Four-pipe fan coil with outside air damper 30.11.2007...
Page 443
Ordering The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. Room controllers RXB21.1 with application group FC-11 RXB21.1/FC-11 Example Note The controllers are delivered with the basic settings shown above.
Page 444
42/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC12 – Four-pipe fan coil with outside air damper 30.11.2007...
Page 445
Q14 Fan speed 1. Q24 Fan speed 2. TR [°C] Q34 Fan speed 3. 43/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC18 – Two-pipe fan coil (changeover) and radiator 30.11.2007...
Page 446
/Auto and fan speed control, and LCD display. Compatible controllers. FNC18 is supplied with RXB21.1/FC-11. 44/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC18 – Two-pipe fan coil (changeover) and radiator...
Page 447
3) Do not exceed the max. simultaneous load on outputs Y1 ... Y4: 9.5 VA (see data sheet 3873). 4) Do not connect the fans in parallel (or use cut-off relays). 45/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12...
Page 448
4) Do not connect the fans in parallel (or use cut-off relays). Note A current list of compatible devices is available in the DESIGO RX hardware overview (N3804). 46/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC18 –...
Page 449
No display / Room Room temperature. temperature / Setpoint Setpoint display Absolute / Relative Relative 47/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC18 – Two-pipe fan coil (changeover) and radiator 30.11.2007...
Page 450
Master or slave Master Ordering The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. Room controllers RXB21.1 with application group FC-11 RXB21.1/FC-11 Example Note The controllers are delivered with the basic settings shown above.
Page 451
Cooling sequence. Damper actuator. Fan speed 1. Fan speed 2. Fan speed 3. TR [°C] 49/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC20 – Four-pipe fan coil, controlled by one damper 30.11.2007...
Page 452
Do not exceed the max. simultaneous load on outputs Y1 ... Y4: 9.5 VA (see data sheet 3873). Do not connect the fans in parallel (or use cut-off relays). 50/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12...
Page 453
No display / Room Room temperature. temperature / Setpoint Setpoint display Absolute / Relative Relative 51/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC20 – Four-pipe fan coil, controlled by one damper 30.11.2007...
Page 454
Master or slave Master Ordering The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. Room controllers RXB21.1 with application group FC-10 RXB21.1/FC-10 Example Note The controllers are delivered with the basic settings shown above.
Page 455
KN X DESIGO™ RXB, RXL Installation guide CM110381en_01 Building Technologies 28 Feb 2009...
Page 456
Bus lengths and distances ..............17 4.5.4 Network address ..................19 4.5.5 Limits .......................19 4.5.6 Zones and zone addresses..............19 4.5.7 Area and line couple, IP router..............20 4.5.8 Filter worksheets ..................21 2 / 22 Siemens Installation guide RXB, RXL CM110381en_01 Building Technologies Contents 28 Feb 2009...
The table below lists the third-party trademarks used in this document and their legal owners. The use of trademarks is subject to international and domestic provisions of the law. Trademarks Legal owner DESIGO Siemens Building Technologies Synco Siemens Building Technologies Konnex®, KNX®, EIB® Konnex Association, B - 1831 Brussels-Diegem Belgium, http://www.knx.org/...
1.3.2 Copyright This document may be duplicated and distributed only with the express permission of Siemens, and may be passed only to authorized persons or companies with the required technical knowledge. 1.3.3 Quality assurance These documents were prepared with great care.
The RXB controllers are compatible with the DESIGO and Synco systems from RXB controller Siemens Building Technologies. The communications component on the RXB controllers are based on Konnex technology and support the S-mode and LTE mode. The devices are certified for Konnex and are labeled with the KNX logo.
3.1.2 Transformer design AC 24 V The DESIGO RXB controller is powered by AC 230 V; the RXL controller by AC 24 Controllers with AC 230 V power internally generates the AC 24 V power supply for connected field devices.
– The KNX bus wire must be connected with the proper polarity. – The simple wiring length between controllers, or controller and room device must be considered for the overall wiring length of the KNX bus. 7 / 22 Siemens Installation guide RXB, RXL CM110381en_01 Building Technologies...
• The maximum power is 1.8 kW ohm load. Larger loads close the contact too much. • A external fuse of max. 10 A is planned to protect room controller circuits. 8 / 22 Siemens Installation guide RXB, RXL CM110381en_01 Building Technologies...
EMC). Cable screens must always be throughout and have solid coverage. Any break in the screening significantly reduces the effect of screening. 10 / 22 Siemens Installation guide RXB, RXL CM110381en_01 Building Technologies Periphery wiring (without bus)
Page 465
The bus wire (KNX, PPS2) cannot be wired in parallel to increase the cross section. Parallel wiring is, however, permitted for power, valve actuators and analog signals, e.g. temperature sensors. 11 / 22 Siemens Installation guide RXB, RXL CM110381en_01 Building Technologies...
(Larger value requires a proportional shortening of permissible cable lengths). Cable screen not required (devices without screened connection) Bus terminating resistor Not required 12 / 22 Siemens Installation guide RXB, RXL CM110381en_01 Building Technologies Konnex bus technology 28 Feb 2009...
(3 x AC 400 V). 4.2.2 Terminating resistor Konnex networks do NOT require bus terminating resistors. 13 / 22 Siemens Installation guide RXB, RXL CM110381en_01 Building Technologies Konnex bus technology 28 Feb 2009...
Each controller consumes 5 mA. Thus, select the supply according to the number of controllers. We recommend the following products: Manufacturer Product No. Designation Siemens Building Technologies ACX95.320/ALG Power Supply 320 mA Siemens Automation Technologies 5WG1 125-1AB01 Power Supply 160 mA...
= Heart Beat RXL communication is proprietary and NOT Konnex compatible. It serves to RXL communication communicate with a DESIGO management station of a Synco control unit. 15 / 22 Siemens Installation guide RXB, RXL CM110381en_01 Building Technologies Konnex bus technology...
3.15.0 Area 2 2.0.0 Main line 2 2.1.0 2.2.0 2.3.0 2.15.0 Area 1 1.0.0 Main line 1 0.1.0 0.2.0 1.1.0 1.2.0 1.3.0 1.15.0 16 / 22 Siemens Installation guide RXB, RXL CM110381en_01 Building Technologies Konnex bus technology 28 Feb 2009...
Bus power supply max. 350 m. Distance between two bus devices max. 700 m. Total length of all lines on one line max. 1,000 m. 17 / 22 Siemens Installation guide RXB, RXL CM110381en_01 Building Technologies Konnex bus technology 28 Feb 2009...
Page 472
Total length The permissible total length of 1,000 meter in the line is exceeded, if device N5 is integrated in the bus at the given bus wiring. 18 / 22 Siemens Installation guide RXB, RXL CM110381en_01 Building Technologies Konnex bus technology...
Zones and zone addresses In LTE mode (together with Synco devices), set up various zones. We recommend using worksheets for engineering. See Synco intranet, Excel worksheet under Synco700: https://intranet10.sbt.siemens.com/business/building_comfort/products/controllers_ hvac/ Relevant zone and their settings ranges for RXB / RXL Geographic zones: •...
Note For large plants with Synco, use Siemens area/line couplers as of version R2 (stamped R2), since only these couplers contain the LTE filter worksheet (see Section 4.5.8.2). routers are required when you need to connect a KNX network to an IP Use of IP routers network.
Additional information is available in the product and function description (including with each device) or at: www.automation.siemens.com/et/gamma/ Note For large plants with Synco, use Siemens IP routers as of version R4 (stamped R4), since only these IP routers contain the LTE filter worksheet (see Section 4.5.8.2). 4.5.8 Filter worksheets 4.5.8.1...