Installation Instructions

Model NRC
Network Ring Card
INTRODUCTION
Features
A6V10322639_b_en_--
The Model NRC Network Ring card from Siemens Industry,
Inc. is a card that networks multiple FireFinder-XLS systems
together in a Class X (Style 7) ring. The NRC can also be
configured for Class B (Style 4) operation in systems where
a ring is not required, as an alternative to the NIC-C card.
It provides communication between its host FireFinder-XLS
system and other FireFinder-XLS systems on an XNET network.
It replaces the NIC-C when a ring connection is needed.
The NRC can also be used to connect an NCCNT-G to the
XNET network. In this configuration, all events occurring on
the FireFinder-XLS network are displayed at the NCCNT-G.
One NRC is required in each FireFinder-XLS system on the
network. This NRC must reside in the same enclosure as the
PMI/PMI-2.
The NRC supervises the network to ensure proper opera-
tion. Any faults that are detected by the NRC are reported to
the PMI/PMI-2 for annunciation. In addition, the NRC has
diagnostic LEDs that indicate which faults have been found.
The NRC performs ground fault detection on its outgoing
ring port.
The NRC isolates faults to the individual link in trouble. When
wired for Class X (Style 7), network ring communication
continues unaffected.
An RJ-12 monitor jack is included for connection of XNET
diagnostic tools. In addition, RJ-45 and USB jacks are
included for firmware download. These jacks are located on
the front bezel.
Figure 1
NRC Network Ring Card
Siemens
Siemens Industry
Siemens
Industry
Industry, , , , , Inc.
Siemens
Siemens
Industry
Building
Building
Building
Building T T T T T ec
Building
ec
ec
echnologies Di
ec
hnologies Division
hnologies Di
hnologies Di
hnologies Di
NRC
RESET
POWER
CARD FAIL
TROUBLE
MONITOR
PORT
ETHERNET
USB
Industry
Inc.
Inc.
Inc.
Inc.
vision
vision
vision
vision

Advertisement

Table of Contents
loading

Summary of Contents for Siemens NRC

  • Page 1: Installation Instructions

    The Model NRC Network Ring card from Siemens Industry, Inc. is a card that networks multiple FireFinder-XLS systems together in a Class X (Style 7) ring. The NRC can also be configured for Class B (Style 4) operation in systems where a ring is not required, as an alternative to the NIC-C card.
  • Page 2: Operation

    3. XNET communications problems between the PMI/PMI-2 and the NRC. PRE-INSTALLATION The NRC does not have a network address but it does need to be included in the Zeus configuration. INSTALLATION The NRC plugs perpendicularly into one slot in the CC-2 or CC-5 card-cage via two 96-pin DIN connectors (only 64-pins are used) and can occupy any slot in the card cage.
  • Page 3: Firmware Upgrades

    Help for additional details. Find NRC Software Version To check for the current version of NRC software in an installed NRC, go to the PMI/ PMI-2 and press the Menu button, select Report, press the More Info button and select the PMI. Press the Configuration soft key and “Touch” Appl Rev for the Application Version.
  • Page 4 Remove all system power before installation, first battery then AC. (To power up, WIRING connect the AC first, then the battery.) All field wiring to the NRC is connected to the terminal blocks of the CC-2 or CC-5 card cage slot in which it is installed. To connect the field wiring: Loosen the screw of the terminal by turning it counterclockwise.
  • Page 5 Figure 6 NRC Class B (Style 4) Network Wiring WIRING OF NRC TO FIBER MODULES FN2006 AND FN2007 See the FN2006/FN2007 Installation Instructions, P/N A6V10315048, for wiring and fiber connections. Installation of the fiber modules in the XLS system requires one bracket, model COM-BRK, per fiber module.
  • Page 6: Wiring Configurations

    CONNECTION CONNECTION CONNECTION CONNECTION CONNECTION CONNECTION FOM: FOM: FOM: FN2006/FN2007 FN2006/FN2007 FN2006/FN2007 OPTICAL OPTICAL FIBER PAIR FIBER PAIR Figure 10 OPTICAL FIBER PAIR Typical Class X (Style 7) Installation with optical fiber only Siemens Industry, Inc. A6V10322639_b_en_-- Building Technologies Division...
  • Page 7: Electrical Ratings

    FOM: FN2006/ FN2007 OPTICAL Figure 12 FIBER PAIR Typical Class X (Style 7) Installation with optical fiber and wire FOM = Fiber Optic Module, Model FN2006 (Single mode) or FN2007 (Multi-mode) ELECTRICAL RATINGS Siemens Industry, Inc. A6V10322639_b_en_-- Building Technologies Division...
  • Page 8 This page has been left intentionally blank. Siemens Industry, Inc. Siemens Canada Limited P/N A5Q00059298 Document ID A6V10322639_b_en_-- Building Technologies Division Building Technologies Division Florham Park, NJ 2 Kenview Boulevard Brampton, Ontario L6T 5E4 Canada...