Download Print this page
Honeywell ADEMCO 4297 Installation And Setup Manual
Honeywell ADEMCO 4297 Installation And Setup Manual

Honeywell ADEMCO 4297 Installation And Setup Manual

V-plex loop extender module

Advertisement

Quick Links

For Use With Control/Communicators Supporting V-Plex

GENERAL INFORMATION

The ADEMCO 4297 V-Plex
accessory for use with Ademco control panels that support
V-Plex (polling loop) devices.
signals from the control panel via its "input" loop, and then
re-transmits
boosted copies
"extension" loop.
The 4297 draws power for its internal circuitry and its
extension loop from a supplementary power supply such as
the control panel's auxiliary power output.
Also, the 4297 isolates open and short circuit faults
occurring
on
its
extension
loop. These characteristics allow the 4297 module to be
used to extend the control panel's polling loop, to provide
additional polling loop current, and to provide electrically
isolated branch loops.
The 4297 module is fully supervised and causes the control
panel to trigger supervision fault indications for devices
wired to the extension loop when operating power to the
module fails, or when an open or short circuit occurs on the
extension loop.
Refer to the control panel's installation
instructions for the type of supervision fault indication
provided.
Important Notes:
* The 4297 cannot be used to increase the number of
polling loop zones supported by the control panel.
* The 4297 is not designed to be used in a Class A
wiring configuration.
MOUNTING
For UL burglary and all fire installations:
Mount the 4297 module inside a UL Listed enclosure such as
the control panel's enclosure. Note that the enclosure must
be UL Listed for the desired application; i.e., use an attack-
resistant enclosure with a tamper switch for commercial
burglary applications.
For non-UL certified installations:
Mount the 4297 module directly on a surface using the
slotted holes located on the back of its housing (mounting
screws provided). Feed the wires through the slot on the side
or through the breakout located on the back of the housing.
Affix the connections label provided to the inside of the 4297
module's cover or in the control panel cabinet, if used.
WIRING CONNECTIONS
The 4297 module provides a 9-position terminal block for
making power, earth ground and polling loop connections.
The screw terminal assignments on this terminal block are
described in Figure 1.
UL NOTE: Use only 14-22 gauge wire.
For ULC fire installations, the 4297 can be used to
connect the fire alarm control panel to the Vista fire
ULC
transmitter. It is not to be used to connect fire alarm
detectors to the ADEMCO (Vista) fire transmitter.
INSTALLATION AND SETUP GUIDE
®
loop extender module is an
The 4297 module receives
of
these
signals
via its
loop
from
its
V-Plex
FOR IMPEDANCES BELOW WHICH
GROUND FAULTS WILL BE
ANNUNCIATED, REFER TO THE
"SUMMARY OF CONNECTIONS"
input
LABEL FOR THE CONTROL PANEL.
*
FOR CE INSTALLATIONS
TERMINAL 3 MUST BE
CONNECTED TO
EARTH GROUND
Figure 1. 4297 Wiring Connections
Power Supply Connections
The 4297 module can draw power for its internal circuitry
and its extension loop from a supplementary power supply
such as the control panel's auxiliary power output.
Figure 2.
• All power-limited wiring must be separated from non-power
U L
limited and high-voltage wiring by 1/4" (6.4 mm).
• Refer to the control panel installation instructions for
programming / installation requirements.
When Using One 4297
Use one 4297 to extend the polling loop, to provide additional
polling loop current, or to provide an extension loop which is
electrically isolated from the input loop.
Make the connections shown in Figure 3 when only one 4297
module is used. Make sure that the wire run length limits
indicated in Table 1 are not exceeded.
When Using Multiple 4297s
Use multiple 4297s to provide up to eight extension loops
which are electrically isolated from each other, or to provide
more current than one 4297 can supply.
Make the connections shown in Figure 4 when multiple 4297
modules are used. Do not wire 4297 modules in series (i.e.,
do not wire one module's extension loop to another module's
input loop). Do not use more than eight 4297 modules in
parallel unless otherwise stated in the control panel's
installation instructions. Make sure that the wire run length
limits indicated are not exceeded.
Important Notes:
* Twisted pair is recommended for all polling loop wire runs.
* If an intercom system is being used, keep the polling loop
wiring as far from the intercom wiring as possible
(minimum 6 inches). If this spacing cannot be achieved, use
shielded wire. Note that use of shielded wire reduces the
maximum permissible polling loop wire run length, as
indicated in Table 1 on page 2.
ADEMCO 4297
®
Loop Extender Module
®
Loop Devices
EXTENSION POLLING LOOP
9
+
}
(CLASS B, STYLE 3)
8
MAX LINE IMPEDANCE
7
}
INPUT POLLING LOOP
(FROM CONTROL) (CLASS B,
+
6
STYLE 3)
5
}
4
(NO CONNECTION)
*
3
12VDC POWER INPUT (FROM
2
}
CONTROL PANEL OR A SUP-
PLEMENTAL POWER SUPPLY
1
+
LISTED FOR THE APPLICATION)
NOTES:
1.
WHEN A SUPPLEMENTARY POWER SUPPLY IS USED, CONNECT IT TO
TERMINALS 1 & 2. CONNECT THE POWER SUPPLY (-) TO AUX POWER (-)
ON THE CONTROL PANEL. USE A CLASS II (POWER LIMITED) SUPPLY.
2.
WHEN USING AN EXTERNAL POWER SOURCE, CONNECTIONS MUST
BE MADE TO A UL864/UL1481 REGULATED POWER SUPPLY.
3.
ALL CIRCUITS ARE SUPERVISED AND POWER LIMITED.
ELECTRICAL SPECIFICATIONS:
POLLING LOOP VOLTAGE: 8-11 VDC
INPUT POWER VOLTAGE: 12 VDC
INPUT POWER CURRENT: 180MA
:400MA (LOOP SHORTED)
4. USE ONLY 14-22 GAUGE WIRE.
20Ω
See

Advertisement

loading

Summary of Contents for Honeywell ADEMCO 4297

  • Page 1: General Information

    For Use With Control/Communicators Supporting V-Plex Loop Devices INSTALLATION AND SETUP GUIDE GENERAL INFORMATION ® The ADEMCO 4297 V-Plex loop extender module is an EXTENSION POLLING LOOP accessory for use with Ademco control panels that support (CLASS B, STYLE 3) –...
  • Page 2: Wiring Requirements

    WIRE RUN LENGTH NOTE MUST NOT EXCEED: USE A CLASS II (POWER LIMITED) POWER GAUGE LENGTH SUPPLY WHICH IS UL LISTED FOR THE 100 FT DESIRED FIRE AND/OR BURGLARY 150 FT APPLICATION. FOLLOW THE POWER SUPPLY'S INSTRUCTIONS REGARDING BACKUP 225 FT BATTERY AND AC/BATTERY SUPERVISION INPUT POLLING LOOP (FROM CONTROL).
  • Page 3 Recharge Time: Up to 48 hours Miscellaneous: PTC thermistor provides reverse battery For the latest warranty information, please go to: connection protection www.honeywell.com/security/hsc/resources/wa Extension Polling Loop Rating: Output Current: 128mA max. Do not draw more than 128mA on any individual extension loop wire run.
  • Page 4 2 Corporate Center Drive, Suite 100 P.O. Box 9040, Melville, NY 11747  Copyright 2009 Honeywell International Inc. www.honeywell.com/security ÊN7571V4lŠ N7571V4 11/13 Rev. A...