Controller Options
Vertical Air Handling indoor units include LG-supplied wired controller (PQRCV-
CL0QW), but other optional LG-supplied wired controllers are available. The wireless
handheld controller (Model No. PQWRHQ0FDB) is also an optional accessory with
use of the wired controller.
• Operation Display Panel: Displays operation conditions.
• Temperature Control Button: Sets desired temperature.
• Fan Speed Button: Sets desired fan speed.
• On / Off Button: Turns system operation on and off.
• Mode Selection Check Button: Selects the operation mode: Cooling, Heating, Auto, Dry
(Dehumidification), or Fan.
Each function displays on the LED for about three (3) seconds when the power is first cycled on.
Wired Controller Connections
Controllers can connect to the indoor unit in one of two different ways.
1. LG Wired Remote Extension Cable with Molex plug (PZCWRC1; sold separately) that connects to the CN-REMO terminal on the
indoor unit PCB.
2. Field-supplied controller cable that connects to the indoor unit terminal block (must be at least UL2547 or UL1007, and at least FT-6
rated if local electric and building codes require plenum cable usage). Communication cable from indoor unit to remote controller(s)
is to be 22 AWG, 3-conductor, twisted, stranded, unshielded. Wiring must comply with all applicable local and national codes.
Figure 68: PZCWRC1 LG Wired Remote Extension Cable.
FAN
SPEED
TEMP
OPER
MODE
When using field-supplied controller cable, be sure to connect the yellow to yellow (communications wire), red to red (12V power
wire), and black to black (ground wire) terminals from the remote controller to the indoor unit terminal blocks.
Figure 69: Wired Controller Connection on the Indoor Unit Terminal Block.
CN-REMO
Indoor Unit Terminal Block
YL
RD BK
1(L1 ) 2 (L2)
12V
Power Ground
Comm.
ELECTRICAL SYSTEM INSTALLATION
Verify the connectors are properly inserted.
Extension cable
GND
3
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Figure 67: PQRCVCL0QW Wired Controller.
C/BOX Cable (Plug type)
To Indoor Unit
CN-REMO
Terminal

Wall Controller Installation

FA N
SPEED
TEMP
OPER
MODE
49