Detector/Base Adapter
The SIEMENS Model DB-ADPT detector/base adapter
interfaces Series 11 detectors with previously installed
DB-3S bases. For Series 3 air duct detector models
AD-3P, AD-3ILP, and SA-3P, use Series 11 Air Duct
Update Kit AD-11UK, which contains both the DB-ADPT and
the required DA-304 air duct cover for Series 11 detectors.
When replacing a detector with a different model, be
aware that existing detector accessories connected
to the base or air duct housing that were compatible
with the old detector may not be compatible with the
new detector. Always read the Installation Instruc-
tions accompanying the detector to determine detec-
tor and accessory compatibility.
Siemens Building Technologies, Inc.
8 Fernwood Road
Florham Park, New Jersey 07932
P/N 315-094200-6
WARNING:
Siemens Building Technologies, Ltd.
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 CN

Fire Safety

Advertisement

loading

Summary of Contents for Siemens DB-ADPT

  • Page 1: Fire Safety

    Series 11 detectors with previously installed DB-3S bases. For Series 3 air duct detector models AD-3P, AD-3ILP, and SA-3P, use Series 11 Air Duct Update Kit AD-11UK, which contains both the DB-ADPT and the required DA-304 air duct cover for Series 11 detectors. WARNING:...
  • Page 2 For DB-3S Bases: 1. Remove the existing detector from the DB-3S base. 2. To install the DB-ADPT adapter into the DB-3S base, align the notch in the outer flange of the adapter to the raised surface on the outer ring of the base (Refer to Figure 1).
  • Page 3 Figure 1 Installing the DB-ADPT to the DB-3S Base For Series 3 Airduct Housings using the AD-11UK Air Duct Update Kit: 1. Remove the sensing compartment cover from the existing duct housing. 2. Remove the existing detector from the duct housing.
  • Page 4 4. Push the adapter down into the base and rotate clockwise to engage electrical connections. The adapter will automatically stop and lock into place. 5. Install a Series 11 detector following the installation instructions included with the detector and then install the new DA-304 sensing compartment cover.