APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 9 of 46)
ADDR
REGISTER NAME
380E
Field Unit 1 Port
380F
...Repeated for Field Unit 2
381E
...Repeated for Filed Unit 3
382D
...Repeated for Filed Unit 4
383C
...Repeated for Filed Unit 5
384B
...Repeated for Filed Unit 6
385A
...Repeated for Filed Unit 7
3869
...Repeated for Filed Unit 8
Field Unit Process Card Ports (Read/Write Setting)
3878
Field Unit 1 Process Card Port
3879
Field Unit 2 Process Card Port
387A
Field Unit3 Process Card Port
387B
Field Unit 4 Process Card Port
387C
Field Unit 5 Process Card Port
387D
Field Unit 6 Process Card Port
387E
Field Unit 7 Process Card Port
387F
Field Unit 8 Process Card Port
Field Unit CT VT Settings (Read/Write Setting) (6 modules)
3890
Remote Phase CT x Origin 1
3891
Remote Phase CT x Origin 2
3892
Remote Ground CT x Origin 1
3893
Remote Ground CT x Origin 2
3894
AC Bank Redundancy Type
3895
Remote Phase CT 1 Primary
3896
Remote Phase CT 1 Secondary
3897
Remote Ground CT 1 Primary
3898
Remote Ground CT 1 Secondary
3899
Remote Phase VT 1 Connection
389A
Remote Phase VT 1 Secondary
389B
Remote Phase VT 1 Ratio
389D
Remote Auxiliary VT 1 Connection
389E
Remote Auxiliary VT 1 Secondary
389F
Remote Auxiliary VT 1 Ratio
38A1
...Repeated for module number 2
38B2
...Repeated for module number 3
38C3
...Repeated for module number 4
38D4
...Repeated for module number 5
38E5
...Repeated for module number 6
Field Unit Contact Inputs (Read/Write Setting) (40 modules)
3900
Field Contact Input 1 ID
3906
Field Contact Input 1 Origin
3907
Field Contact Input 1 Input
3908
Field Contact Input 1 Failsafe Value
3909
Field Contact Input 1 Debounce Time
390A
Field Contact Input 1 Events
390B
...Repeated for Field Contact Input 2
3916
...Repeated for Field Contact Input 3
3921
...Repeated for Field Contact Input 4
392C
...Repeated for Field Contact Input 5
3937
...Repeated for Field Contact Input 6
3942
...Repeated for Field Contact Input 7
394D
...Repeated for Field Contact Input 8
3958
...Repeated for Field Contact Input9
GE Multilin
RANGE
1 to 4
0 to 7
0 to 7
0 to 7
0 to 7
0 to 7
0 to 7
0 to 7
0 to 7
0 to 16
0 to 16
0 to 16
0 to 16
0 to 2
1 to 65000
0 to 1
1 to 65000
0 to 1
0 to 1
25 to 240
1 to 24000
0 to 6
25 to 240
1 to 24000
---
0 to 8
1 to 18
0 to 1
0 to 16
0 to 1
C30 Controller System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F001
---
1
F244
---
1
F244
---
1
F244
---
1
F244
---
1
F244
---
1
F244
---
1
F244
---
1
F244
---
1
F247
---
1
F247
---
1
F248
---
1
F248
---
1
F261
1 (Dependability
---
1
F001
---
1
F123
---
1
F001
---
1
F123
---
1
F100
---
0.1
F001
---
1
F060
---
1
F166
---
0.1
F001
---
1
F060
---
1
F205
---
1
F256
---
1
F001
---
1
F108
ms
0.5
F001
---
1
F102
DEFAULT
1
6 (H1a)
4 (H2a)
B
2 (H3a)
0 (H4a)
7 (H1b)
5 (H2b)
3 (H3b)
1 (H4b)
0 (none)
0 (none)
0 (none))
0 (none)
Biased)
1
0 (1 A)
1
0 (1 A)
0 (Wye)
664
1
1 (Vag)
664
1
"FCI 1"
0 (none)
1
0 (Off)
20
1 (Enabled)
B-17