Field Supplied Refrigerant Piping Type ACR copper is the only approved refrigerant pipe material for use with LG Multi F air conditioning products. ACR rated tubing is the only type that ships with yellow caps. Approved tubing for use with Multi F products will be marked “R410 RATED” along the length of the tube.
Field-Provided Isolation Ball Valves LG maintains a neutral position on using isolation valves in VRF refrigerant piping systems. LG does not endorse any manufacturer of isola- tion valves. It is recognized that installing isolation valves may simplify future maintenance requirements, and, if used, considerations should be taken including, but not limited to, the following: •...
Page 24
Multi F MAX Y-Branch Kit PMBL5620 The LG supplied Y-Branch Kit PMBL5620 MUST be used when two branch distribution units are connected to one Multi F MAX system. Field-supplied fittings are not permitted. Each Y-branch kit comes with two (2) Y-branches (one for the liquid line and one for the vapor line) and insulation covers.
Page 25
Tube wall thickness should meet local code requirements and be approved for an operating pressure of 551 psi. If local code does not specify wall thickness, LG suggests using tube thickness per table below. When bending tubing, try to keep the number of bends to a minimum, and use the largest radii possible to reduce the equivalent length of installed pipe;...
Page 49
2. Store a minimal amount of cable in the handy box. Any additional cable should be coiled and stored near the indoor unit control panel. 3. If additional cable length is needed, order a thirty-three (33) foot LG Wired Remote Group Control Extension cable (Model No. PZCWRC1).
Page 50
Hanging the Wired Controller, continued. • Connect indoor unit and wired controller using included connection cable. • Use an LG-manufactured extension cable (sold separately) if the distance between wired remote controller and the indoor unit is >32.8 feet. Figure 72: Indoor Unit to Wired Controller Connection (Controller Appearance May Vary Depending on Model Chosen).
Page 55
Power wiring to the indoor units and branch distribution unit(s) (Multi F MAX only) was installed per all local electrical code requirements. LG-supplied cable was used between each indoor unit and its zone controller. No cables were spliced and no wire caps are present.
Page 60
Who to call for assistance Freight Damage and Unit Replacements Your LG Manufacturer Representative Missing Parts Your LG Manufacturer Representative Freight Damage and Unit Replacements Your LG Manufacturer Representative Received Wrong Indoor Unit Model Your LG Manufacturer Representative Installation, Startup, and Commissioning Technical Assistance 1-888-865-3026 For warranty information, visit www.lghvac.com.
Page 61
20001747 ISO 9001: 2008 LG ELECTRONICS INC. LG Electronics, U.S.A., Inc. LG Customer Information Center, Commercial Products Commercial Air Conditioning Division 1-888-865-3026 USA 4300 North Point Parkway Follow the prompts for commercial A/C products and parts. Alpharetta, Georgia 30022 IM_Multi_F_CeilingCassette_9_15 www.lg-vrf.com...