Convertible Surface Mounted and Ceiling Suspended Indoor Units Installation Manual Convertible Surface Mounted Indoor Unit Ceiling Mounted Convertible Surface Mounted Indoor Unit Wall Mounted Ceiling Suspended Indoor Unit...
Page 2
Do not throw away or destroy this manual. Please read carefully and store in a safe place for future reference. The instructions below must be followed to prevent product malfunction, property damage, injury or death to the user or other people. Incorrect operation due to ignoring any instructions will cause harm or damage.
ARNU243VJA2 24,200 Btu/h These units are part of an LG Variable Refrigerant Flow (VRF) Heating, Ventilation, and Air Conditioning (HVAC) system. All of these units operate on 208–230 V, 60 Hz, 1-phase power. Install these unit(s) in the location(s) specified by your architectural blueprints, HVAC system layout drawings, or other appropriate docu- ments.
If no mounting height was specified by the building designer, place the handy box approximately 55 inches above the finished floor. 2. Pull LG communications cable between the zone controller handy box and the indoor unit. A 30 foot cable comes with the wall-mounted zone controller.
Follow the procedure below for brazing. Note: All joints are brazed in the field. Multi V outdoor unit refrigeration system components contain very small capillary tubes, small orifices, electronic expansion valves, oil separators, and heat exchangers that can easily become blocked.
• Use field-provided 1/2” thick (or more) closed cell insulation. The thickness may need to be increased based on ambient conditions and local codes. • All refrigerant a condensate piping including field-provided isolation ball valves and flexible pipe connection kits provided by LG should be wrapped.
The polarity of the communications cable connections is important. When connecting the communications cable conductors at each Multi V™ system component (Figure 20), be careful the conductor connected the to the IDU(A) terminal on the outdoor unit is connected to the 3(A) terminals at each indoor unit.
Page 25
If the distance between the zone controller and indoor unit exceeds 30 feet, purchase an LG zone controller communications extension cable (32 feet, Model No. PZCWRCG3). This extension cable has a female connector on one end and a male connector on the other.
Final Checks before Leaving Site Use the checklist on the following pages to verify all tasks have been completed prior to calling for the Multi V system to be commissioned. Place the System ID and Indoor Unit ID at the top of the page, sign and date. Provide a copy to your company’s project manager or your Multi V System Commissioning Technician.
Page 36
20001747 ISO 9001: 2008 LG ELECTRONICS INC. LG Electronics LG Customer Information Center, Commercial Products Commercial Air Conditioning Division 1-888-865-3026 USA 11405 Old Roswell Road Follow the prompts for commercial A/C products and parts. Alpharetta, Georgia 30009 www.lg-vrf.com VRF-IM-DK-001-US 013D29...