Detailed Explanation of Object
11) Swing (Status)
Point number: 10
Object name: SwingStatus_XXX (XXX: A/C unit address)
Object type: Binary Input
Meaning: This object is to monitor the air direction of the A/C.
Present_Value property:
ACTIVE: Swing_On
INACTIVE: Swing_Off
12) Fan Speed (Setting)
Point number: 11
Object name: FanSpeedCommand_XXX (XXX: A/C unit address)
Object type: Multistate Output
Meaning: This object is to set the airflow of the A/C.
Present_Value property:
Indoor
1:
Low
2:
Middle
3:
High
4:
Auto
Remarks: The A/C will disregard the command which the object which can't select the operation mode.
Therefore, controlled/monitored system shouldn't use the object which can't select the
operation mode.
13) Fan Speed (Status)
Point number: 12
Object name: FanSpeedStatus_XXX (XXX: A/C unit addresss)
Object type: Multistate Input
Meaning: This object is to monitor the airflow of the A/C.
Present_Value property:
Indoor
1:
Low
2:
Middle
3:
High
4:
Auto
Remarks: Present_value property will be set to "1:Low" as the default result if the property has
not been set in the past.
78 BACnet Gateway
Vent
Low
High
Super High
Auto
Vent
Low
High
Super High
Auto