8) Operation Mode (Setting)
Point number: 7
Object name: ModeCommand_XXX (XXX: A/C unit address)
Object type: Multistate Output
Meaning: This object is used to set the operation modes of the air conditioner.
Present_Value property:
Indoor
1:
Cool
2:
Dry
3:
Fan
4:
Auto
5:
Heat
Remarks: 1. The Present_Value property will be set to "1: Cool" as the default value if property
has never been set in the past.
2. The air conditioner will ignore the command to an object that does not have right to
select operation mode. Therefore, the controlled/monitored system must not use this
object for the air conditioner without the right to select operation mode.
9) Operation Mode (Status)
Point number: 8
Object name: ModeStatus_XXX (XXX: A/C unit address)
Object type: Multistate Input
Meaning: This object is used to monitor the operation modes of the air conditioner.
Present_Value property:
Indoor
1:
Cool
2:
Dry
3:
Fan
4:
Auto
5:
Heat
10) Swing (Setting)
Point number: 9
Object name: SwingCommand_XXX (XXX: A/C unit address)
Object type: Binary Output
Meaning: This object is to set the air direction of the indoor unit.
Present_Value property:
ACTIVE: Run
INACTIVE: Stop
Vent
HEX
Auto
Normal
-
-
Vent
HEX
Auto
Normal
-
-