Monitoring and Controlling point of indoor and ventilator

Applicable monitoring and controlling point for the indoor and ventilator are listed below.
Object Name's XX is indoor's address number.
Name
1
Run/Stop (setting)
2
Run/Stop (status)
3
Lock (setting)
4
Lock (status)
5
Filter Sign
6
Filter Sign reset
7
Operation Mode (setting)
8
Operation Mode (status)
9
Swing (setting)
10 Swing (status)
11 Fan speed (setting)
12 Fan speed (status)
13 Set Room Temperature
14 Room Temperature
15 Alarm
16 Error Code
17 User Mode(setting)
18 User Mode(status)
19 Set Temperature (status)
Accumulator Power Distribution
20
(status)
21 AC Operation Mode (setting)
22 AC Operation Mode (status)
23 AC ON/OFF (setting)
24 AC ON/OFF (status)
25 Humidify (setting)
26 Humidify (status)
27 Set Upper Temperature (setting)
28 Set Lower Temperature (setting)
29 Set Upper Temperature (status)
30 Set Lower Temperature (status)
31 Mode Lock (setting)
32 Mode Lock (status)
Functional Specifications BACnet Gateway
Object Name
StartStopCommand_XXX
StartStopStatus_XXX
LockCommand_XXX
LockStatus_XXX
FilterSign_XXX
FilterSignReset_XXX
ModeCommand_XXX
ModeStatus_XXX
SwingCommand_XXX
SwingStatus_XXX
FanSpeedCommand_XXX
FanSpeedStatus_XXX
SetRoomTemp_XXX
RoomTemp_XXX
Alarm_XXX
MalfunctionCode_XXX
UserModeCommand_XXX
UserModeStatus_XXX
SetTempStatus_XXX
AccumPowerStatus_XXX
Hrv_ModeCommand_XXX
Hrv_ModeStatus_XXX
HrvStartStopCommand_XX
X
HrvStartStopStatus_XXX
HrvHumidifyCommand_XXX
HrvHumidifyStatus_XXX
SetUpperTempCommand_X
XX
SetLowerTempCommand_X
XX
SetUpperTempStatus_XXX
SetLowerTempStatus_XXX
ModeLockCommand_XXX
ModeLockStatus_XXX
Object Type
Indoor
Binary Output
O
Binary Input
O
Binary Output
O
Binary Input
O
Binary Input
X
Binary Value
X
Multistate Output
O
Multistate Input
O
Binary Output
O
Binary Input
O
Multistate Output
O
Multistate Input
O
Analog Value
O
Analog Input
O
Binary Input
O
Analog Input
O
Multistate Output
X
Multistate Input
X
Analog Input
O
Analog Input
O
Multistate Output
X
Multistate Input
X
Binary Output
X
Binary Input
X
Binary Output
X
Binary Input
X
Analog Value
O
Analog Value
O
Analog Input
O
Analog Input
O
Binary Output
O
Binary Input
O
Installation/Owner Manual 51
Vent
O
O
O
O
O
O
O
O
X
X
O
O
X
X
O
O
O
O
X
X
O
O
O
O
O
O
X
X
X
X
X
X

Advertisement