hit counter script

LG LS-H0766KA2 Service Manual page 46

Room air conditioner
Table of Contents

Advertisement

Troubleshooting Guide
Evacuation
(All amount of refrigerant leaked)
Vacuum pump
• Procedure
(1) Connect the vacuum pump to the center hose
of charge set center hose
(2) Evacuation for approximately one hour.
– Confirm that the gauge needle has moved
toward -76 cmHg (vacuum of 4 mmHg or less).
46 Room Air Conditioner
Indoor unit
Lo
OPEN
Liquid side
3-Way
valve
Gas side
3-Way
valve
CLOSE
(3) Close the valve (Lo side) on the charge set,
turn off the vacuum pump, and confirm that
the gauge needle does not move (approxima-
tely 5 minutes after turning off the vacuum
pump).
(4) Disconnect the charge hose from the vacuum
pump.
– Vacuum pump oil.
If the vacuum pump oil becomes dirty or
depleted, replenish as needed.
Use vacuum pump equipped with check value
applied to be prevented from flowing backward.
Outdoor unit
Open
Open

Advertisement

Table of Contents
loading

Table of Contents

Uploaded: cache9/manual/768188/Lg-Ls-H0766ka2.html%3Fpage%3D46.gz