ET 141 High Limit Control Thermostat Description The ET 141 high limit control thermostat is duct mounted and has a rigid bulb, bi-metal rod and tube construction. Application Normally, the thermostat is used as a high limit control when a "lock-out" type control is desired or required by local code.
Page 2
Technical Instructions ET 141 High Limit Control Thermostat Document Number 155-021P25 September 28, 2004 Operation and The setpoint adjustment knob (see Figure 2) permits adjustment of the setpoint between Adjustment 25°F and 215°F (-4°C and 101°C). The temperature differential is factory set, non-adjustable, and approximately 20°F (11°C), depending on the rate of temperature change.
ET 141 High Limit Control Thermostat Technical Instructions Document Number 155-021P25 September 28, 2004 Installation 1. Select a mounting location for the thermostat in the duct (or plenum). The location must allow the sensing element to measure the average temperature in the duct.
Technical Instructions ET 141 High Limit Control Thermostat Document Number 155-021P25 September 28, 2004 When the temperature increases to above the setpoint, the circuit opens. When the Wiring Diagram reset lever is pressed after the sensed temperature decreases to approximately 20F°...
Page 5
ET 141 High Limit Control Thermostat Technical Instructions Document Number 155-021P25 September 28, 2004 Supply Air Applications 1. After completing the installation and wiring procedures, turn on the power to the circuit. 2. Raise the supply air temperature to the setpoint temperature.