WIRING CONNECTION
10
Connecting Cables between Indoor Unit and Outdoor Unit
<Outdoor Unit Power Supply : 1 Ph>
1(L) 2(N) 3
1
) L (
( 2
) N
1(L) 2(N) 3
POWER SUPPLY
* The feature can be changed according to type of model.
!
CAUTION
The power cord connected to the outdoor unit should be complied withIEC 60245 or HD 22.4
S4 (This equipment shall be provided with a cord set complying with the national regulation.
The connecting cable connected to the outdoor unit should be complied with IEC 60245 or
HD 22.4 S4 (This equipment shall be provided with a cord set complying with the national
regulation.)
10(13/32) ± 3(1/8) mm(inch)
If the supply cord is damaged, it must be replaced by a special cord or assembly availible
from the manufacturer of its service agent.
Indoor unit
Outdoor unit
When the connection line between the in-
door unit and outdooor unit is over
NORMAL
40(131.2) m(ft), connect the telecommuni-
CROSS-SECTIONAL
cation line and power line separately.
AREA 0.75mm
2
<Outdoor Unit Power Supply : 3 Ph>
1(L) 2(N) 3
1(L) 2(N) 3
POWER SUPPLY
Model
Indoor unit
Outdoor unit
Phase(Ø) Area(mm
2
)
1
2.5 (12AWG)
3
1
3
1
4.0 (10AWG)
3
2.5 (12AWG)