Selecting the Best Location
DANGER
To avoid the possibility of fire,
cause serious bodily injury or death.
Install a fence to prevent vermin from crawling into the unit or unauthorized individuals from accessing it.
where acidic solution and spray (sulfur) are often used as this may cause serious bodily injury or death.
where oil, steam, or sulfuric gas are present as this may cause serious bodily injury or death.
Select a location for installing the outdoor unit that will meet the following conditions:
• Where there is enough strength to bear the weight of the unit.
• Include space for drainage to ensure condensate flows properly out of the unit when it is in heating mode.
• Include enough space for air flow and for service access.
Dont's
• Where the unit will be subjected to direct thermal radiation from other heat sources.
• Where operating sound from the unit will disturb inhabitants of surrounding buildings.
• Where the unit will be exposed to direct, strong winds.
To ensure the outdoor unit operates properly, certain measures are required in locations where there is a possibility of heavy snowfall or
severe wind chill or cold:
1. Prepare for severe winter wind chills and heavy snowfall, even in areas of the country where these are unusual phenomena.
2. Position the outdoor unit so that its airflow fans are not buried by direct, heavy snowfall. If snow piles up and blocks the airflow, the
system may malfunction.
3. Remove any snow that has accumulated by 4 inches or more on the top of the outdoor unit.
4. Place the outdoor unit on a raised platform at least 20 inches higher than the average annual snowfall for the area. In environments where
there is a possibility of heavy snow, the frame height must be more than two (2) times the amount of average annual snowfall, and should
not exceed the width of the outdoor unit. If the frame width is wider than the outdoor unit, snow may accumulate.
5. Install a snow protection hood.
6. To prevent snow and heavy rain from entering the outdoor unit, install the suction and discharge ducts facing away from direct winds.
7. Additionally, the following conditions should be taken into consideration when the unit operates in defrost mode:
• If the outdoor unit is installed in a highly humid environment (near an ocean, lake, etc.), ensure that the site is well-ventilated and has a lot
of natural light. (Example: Install on a rooftop.)
• Sidewalks or parking lots near the outdoor unit may accumulate moisture after unit operates in defrost mode that can turn to ice.
The indoor unit may take longer to provide heat, or heating performance will be reduced in winter if the unit is installed:
1. In a narrow, shady location.
2. Near a location that has a lot of ground moisture.
3. In a highly humid environment.
4. In an area in which condensate does not drain properly.
Ambient Air Conditions
•
Avoid exposing the unit to discharge from boiler stacks, chimneys, steam relief ports, other air conditioning units, kitchen vents, plumb-
ing vents, or substances that may degrade performance or cause damage to the unit.
• When installing multiple outdoor units, avoid placing the units where discharge of one outdoor unit will blow into the inlet side of an adja-
cent unit.
Avoid exposing the unit to sources of extreme temperature or gases to prevent serious bodily injury.
PLACEMENT CONSIDERATIONS
do not install the unit in an area where combustible gas may generate, flow, stagnate, or leak. Failure to do so will
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG " is a registered trademark of LG Corp.
Do not install the unit in a location
Do not use the unit in environments
APPLICATION GUIDELINES | 51