LG MULTI V ARNU073BGA4 Installation Manual page 66

Ducted indoor units
Hide thumbs Also See for MULTI V ARNU073BGA4:
Table of Contents

Advertisement

WIRING
Low-Static Built-In B3/B4 Chassis
CONNECTOR
CN-POWER
CN-MOTOR1
CN-MOTOR2
CN-VM
CN-FLOAT
CN-ZONE
CN-EEV
CN-OPTION
CN-EXT
CN-DISPLAY
CN-CC
CN-PTC
CN-PIPE/OUT
CN-LEAK
CN-PIPE/IN
CN-REMO
CN-ROOM
CN-D/PUMP
CN-485
DIP Switch Setting
SW3
GROUP CONTROL
DRY CONTACT
SW4
MODE
SW5
CONTINUOUS FAN
*For Gen 4 Multi V ducted indoor units, DIP switches 1, 2, 6 through 8 must be set to OFF. These DIP switches are used for
other models.
**To enable Generation 4 features, outdoor unit DIP Switch No. 3 must be set to ON. Please refer to the Multi V IV, Multi V Wa-
ter IV, Multi V S Engineering Manual for additional information.
66
Table 33: Low-Static Built-In B3/B4 Chassis Wiring Diagram
PURPOSE
AC Power supply
Fan motor output
Fan motor output
Sub PC power supply
Float switch input
Zone controller
EEV Output
Optional PCB EPROM
External ON / OFF controller
Display
Dry contact
Auxiliary heater
Discharge pipe sensor
Refrigerant leak detector
Suction pipe sensor
Wired remote controller
Room sensor
Drain pump output
Communication
Table 34: B3, B4 Unit DIP Switch Settings.
Off
On
Master
Slave
Variable
Auto
Off
On
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
AC Power line
Motor output of BLDC
Motor output of BLDC
Power supply connection
Float switch sensing
Zone controller connection
EEV control output
Option PCB connection
External ON / OFF controller connection
Display of indoor status
Dry Contact connection
Connection for Auxiliary Heater
Pipe out thermistor
Refrigerant leak detector connection
Pipe in thermistor
Wired remote control connection
Room air thermistor
AC output for drain pump
Connection between indoor and outdoor units
Group control setting using 7-Day Programmable Controller; selects Master /
Slave on each indoor unit
Sets operation mode for optional Dry Contact accessory
1. Variable: Auto or Manual Mode can be set through 7-Day Programmable
Controller or Wireless Remote Controller (factory default setting is Auto if
there is no setting)
2. Auto: For Dry Contact, it is always Auto mode
Selects continuous fan for ducted indoor units.
1. On: Indoor unit fan will always operate at a set fan speed, except when
the system is off, or the outdoor unit is in defrost mode (when the oudoor unit
is in defrost mode, the fan will operate at super low fan speed)
2. Off: Indoor unit fan speed can be changed by on / off