hit counter script

LG V-net PQDSBCDVM0 Installation Manual page 17

Dry contact for demand control
Hide thumbs Also See for V-net PQDSBCDVM0:
Table of Contents

Advertisement

- Detail of the control step for analog input signal
SW_ STEP
D
E
Notes
• Do not change a command too quickly.
Keep the command 30 seconds at least, otherwise it will cause a damage to outdoor unit.
Input Voltage
0
1
2
3
4
5
6
7
8
9
10
0
1
2
3
4
5
6
7
8
9
10
Setting and using method
Comp capacity
Of outdoor unit(%)
No control
100
90
80
70
60
50
45
40
COMP OFF
ALL OFF
COMP OFF
40
45
50
60
70
80
90
100
100
100
Installation manual 17