Installation
Selection of the best location
Indoor unit
Install the air conditioner in the location that satisfies the fol-
lowing conditions.
• The place shall easily bear a load exceeding four times the
indoor unit's weight.
• The place shall be able to inspect the unit as the figure.
• The place where the unit shall be leveled.
• The place shall easily connect with the outdoor unit.
• The place where the unit is not affected by an electrical
noise.
• The place where air circulation in the room will be good .
• There should not be any heat source or steam near the
unit
Confirm the positional relationship between the unit and
suspension bolts.
• Installation the ceiling opening to clean the filter or service
under the product.
Capacity(Btu/h)
A
7/9/12/15k
600
18/24k
600
(Length: mm)
B
900
1100
Inspection hole
(600 x 600)
Control box
600
Side view
(unit: mm)
• Suitable dimension "H" is necessary to get a slooe
to drain as aiven in the fiaure
Low static Duct type
B(Min)
A(Min)
Service Space
B
Installation Manual 7
Installation
600
H=20 or more
Ceiling
A