Installation of Remote Controller
• Although the room temperature sensor is in the indoor unit, the remote controller should be installed in such
places away from direct sunlight and high humidity.
Installation of the remote controller
• Select places that are not splashed with water.
• Select controller position after receiving customer approval.
• The room temperature sensor is built in the indoor unit.
• This remote controller equipped with liquid crystal display. If this position is higher or lower, display is difficult
to see.(The standard height is 1.2 ~1.5m high)
Routing of the remote controller cord
• Keep the remote controller cord away from the refrigerant piping and the drain piping.
• To protect the remote controller cord from electrical noise, place the cord at least 5cm away from other power
cables. (audio equipment. television set, etc.)
• If the remote controller cord is secured to the wall, provide a trap at the top of the cord to prevent water
droplets from running.
WIRED REMOTE CONTROL INSTALLATION
DISASSEMBLING
Front case
Lever carefully
Remote control
the box open
using a screw
driver, etc.
• Fix the under plate on the wall
Face of wall
Under plate
Screw (accessory)
ELECTRICAL WIRING
(Main board)
• Separate the under plate from Remote
controller box.
box body
• Fix the cord clamps on the wall by ø 3 tapping screws (accessory).
• Fix the remote controller cord.
CN REMO
Wire and make sure that teminal
numbers are matched on unit side and
remote control side.
The maximum length of the cord is 100m.
If the length of the cord exceeds 50m,
use a wire size greater than 0.5mm
• Attach insulator to under plate.
Remote control
2
.
Installation Manual 13
Installation
Cord clamp
(accessory)