Connection Limitations - Continued
Table 27: Single Zone Extended Pipe Refrigerant Piping System Limitations
Pipe Length
(ELF = Equivalent Length of
pipe in Feet)
Elevation
(All Elevation Limitations are
Measured in Actual Feet)
Additional Refrigerant Needed (oz/ft)
Table 28: Single Zone Mega (HEV and HEV1) / Mega 115V Pipe Refrigerant Piping System Limitations
Pipe Length
(ELF = Equivalent Length of
pipe in Feet)
Elevation
(All Elevation Limitations are
Measured in Actual Feet)
Additional Refrigerant Needed (oz/ft)
REFRIGERANT PIPING CONNECTIONS
Longest total equivalent piping length
Shortest total equivalent piping length
Distance between fittings and indoor units
or outdoor units
If outdoor unit is above indoor unit
If outdoor unit is below indoor unit
Longest total equivalent piping length
Shortest total equivalent piping length
Distance between fittings and indoor or
outdoor units
If outdoor unit is above indoor unit
If outdoor unit is below indoor unit
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Refrigerant Piping System Limitations
LS240HLV
164.0
9.8
20 inches
98.4
98.4
0.38
LS090HEV, LS090HEV1/
LS180HEV, LS180HEV1/
LS120HEV, LS120HEV1
LS240HEV, LS240HEV1
49.2
9.8
20 inches
22.9
22.9
0.22
LS300HLV
LS360HLV
164.0
164.0
9.8
9.8
20 inches
20 inches
98.4
98.4
98.4
98.4
0.38
0.38
LS090HXV/
LS120HXV
65.6
49.2
9.8
9.8
20 inches
20 inches
32.8
23
32.8
23
0.33
0.22
37